CLEARANCES
Clearance to Combustibles
Back | 0" (0 mm) |
Side | 0" (0 mm) |
Floor | 0" (0 mm) |
Top | 0" (0 mm) |
Top Framing Edge | 1" (25mm) |
SEE MANTLE CHART FOR | |
MAXIMUM MANTLE DEPTH | |
| 2" x 4" HEADER |
| STAND OFF |
SEE MANTLE CHART | 3" (76 mm) HEIGHT |
ABOVE TOP OF | |
FOR MINIMUM HEIGHT | FIREPLACE |
OF MANTLE ABOVE UNIT |
|
FINISHED WALL |
|
(COMBUSTIBLE) |
|
| NAILING |
| FLANGES |
TOP FRAMING |
|
LEDGE |
|
GLASS FRONT |
|
(OPTIONAL) |
|
Figure 2
Combustible Material
No greeting cards, stockings or ornamentation of any type should be placed on or attached to the fireplace. The flow of heat can ignite combustibles.
Mantel Chart (Figure 3)
12” (305mm)
10” (254mm) |
| |
MANTEL |
| |
8” | COMBUSTIBLE TRIM AND MANTELS | |
ALLOWED IN SHADED AREA | ||
| ||
6” |
| |
12” |
|
4½”
3 3/4”
10 3/4”
|
| 3” |
|
| 2 1/4” |
8” |
| 1 ½” |
| 6” | |
| 3/4” | |
| 5” | |
|
|
4” 3”
2” 1”
TOP EDGE OF FIREPLACE
1/4”
(6.35mm)
Figure 3
Clearances (Figure 4)
Clearance from top front edge of fireplace to ceiling is 36" Clearance from side of fireplace to adjacent sidewall is 6".
Figure 4
LOCATING FIREPLACE
Note: When you install your Fireplace on wall corner positions, a minimum of 6 inches clearance must be maintained from the perpendicular side wall and the screened opening of the appliance.
Figure 5
Page 7 |