Vulcan-Hart BVP42FP32(F,L)N-1 Direct Ignition Propane/Lp Gas Conversion, Valve Conversion

Page 26
Maxitrol Valve Conversion

DIRECT IGNITION PROPANE/LP GAS CONVERSION

1.Turn off the gas supply.

2.Turn off the electrical supply to the appliance if so equipped.

3.Open or remove glass doors if applicable.

4.Remove top louver and lower bottom louver.

5.Remove logs from burner assembly.

VALVE CONVERSION

6.Remove plastic cap from regulator fitting. Unscrew fitting using a 7/16" wrench. Turn fitting over so end of fitting marked "LPG" is visible. Tighten fitting (snug only). Replace plastic cap.

7.Remove 1/4" screw from air shutter.

8.Located to the right of electrodes is a burner hold-down tab. Using needle-nose pliers, bend burner hold-down tab off the main burner.

9.Remove main burner by pivoting main burner forward as you slide main burner from left to right. Be careful as you remove main burner in order to protect the electrodes from being damaged.

10.Remove air shutter from orifice fitting.

11.Remove natural gas main burner orifice from orifice fitting.

12.Install propane/LP main burner orifice marked 1.35mm for BVD34FP50, marked 1.45 mm for BVD36FP52, or marked 1.65mm for BVP42FP52.

Important: Failure to install the correct orifice will result in unit over-firing that could overheat the appliance and result in a fire.

13.Replace air shutter onto orifice fitting. Air shutter must be threaded and bottomed-out onto orifice fitting.

14.Replace main burner onto burner assembly. Place main burner beneath electrodes, slide main burner from right to left into burner location, and pivot main burner away from you and into air shutter.

15.Set air shutter opening as indicated by the chart below. Tighten air shutter in place with 1/4" screw from step 7.

16.Using needle-nose pliers, bend burner hold-down tab over main burner.

17.Refer to log placement, pages 14 and 15 to place logs onto burner assembly.

Model

AIR SHUTTER

BURNER ORIFICE

 

SETTINGS

 

 

Opening "A"

Propane/LP Orifice

BVD34

5/16" (8mm)

1.35mm

BVD36

5/16" (8mm)

1.45mm

BVP42

Full Open

1.65mm

18.Loosen screw and attach a manometer or pressure gauge to the outlet pressure tap of the control valve.

19.Turn on the gas supply. Turn on the electrical supply to the appliance. Check for gas leaks using soap and water solution or leak detection solution. Bubbles indicate a leak that MUST be corrected. Do not use an open flame to test for gas leaks.

20.Check the air shutter opening. See chart and illustration below.

21.Relight the main burners and verify proper burner ignition and operation.

22.With the main burner burning, read the pressure on the manometer or pressure gauge. The pressure on the gauge should read between 9.8" and 10.2" w.c.

23.Turn off the gas supply. Turn off the electrical supply to the appliance.

24.Remove the manometer or pressure gauge. Tighten the screw in the pressure tap.

25.Turn on the gas supply. Turn on the electrical supply to the appliance.

26.Immediately test all gas line connections and the control valve for gas leaks using a soap and water solution or other gas detection solution. Bubbles indicate a leak that MUST be corrected. Do not use an open flame to test for gas leaks.

27.Using a ball point pen, fill out the conversion label that is supplied with the conversion kit. Place the conversion label adjacent to the rating plate.

28.Test operation of fireplace once again. Allow the fireplace to operate for at least 10 minutes and check flame coloration. Flames on rear of burner should be yellow without any orange-colored tip. Minor adjustment of the air shutter may be necessary to "tune in" the proper flame color.

Maxitrol Valve Conversion

REGULATOR FITTING Manual background

NOTE: STAMPED WITH

GAS TYPE SET FOR USE

“A”

Page 26

19400-3-0406

Image 26
Contents EFFECTIVE DATE APRIL B-VENT GAS FIREPLACEThe Keystone B Vent Zero Clearance Gas Fireplace TABLE OF CONTENTS SectionIMPORTANT SAFETY INFORMATION LP-GASWARNING ODOR SAFETY INFORMATION FOR USERS OF LP GASThat’s your signal to go into immediate action NO ODOR DETECTED - ODOR FADEQualified Installing Agency INTRODUCTIONInstructions to Installer Appliance CertificationDim BVD34 SPECIFICATIONSFIREPLACE DIMENSIONS BVD36Mantel Chart Figure CLEARANCESLOCATING FIREPLACE Figure Combustible MaterialGAS SUPPLY Installing a New Main Gas CockGAS SUPPLY CONT Checking Manifold PressuresFraming and Finishing INSTALLATIONInstall the Fresh Air Kit - BVA1 Figure Vent Pipe ClearanceFinishing Figure INSTALLATION CONTCombustible Surround Installation Installing the Vent System in a Chase VENTINGGeneral Maintenance Vent RunsNever downsize venting diameters Clearances VENTING CONTVent Size Vent ConfigurationLOG PLACEMENT 5 LOG SET EMBER MATERIAL PLACEMENT ON BURNERBOTTOM LOG LOCATOR PINS LOG PLACEMENT 3 LOG SETEMBER PLACEMENT TOP BRANCH REAR LOG BOTTOM LOG750 Millivolt System OPERATING INSTRUCTIONSGAS CONTROL KNOB SHOWN IN OFF POSITION Initial LightingFRBC Battery Operated Remote Control OPERATING INSTRUCTIONS CONTWall Switch, FWS-1optional Electric 120 volt Operated Remote Control, FRECSTANDING PILOT WIRING DIAGRAM LIGHTING INSTRUCTIONS FOR YOUR SAFETY, READ BEFORE LIGHTINGSTANDING PILOT LIGHTING INSTRUCTIONS TO TURN OFF GAS TO FIREPLACE6.Glass Sooting STANDING PILOT TROUBLESHOOTING4.Frequent pilot outage problem SAFETY SHUTDOWN SYSTEM STANDING PILOT PROPANE/LP GAS CONVERSIONCHECK SAFETY SHUTDOWN PERFORMANCE B-VENTFIREPLACESPILOT ORIFICE CONVERSION DIRECT IGNITION WIRING DIAGRAM OPTIONAL REMOTE CONTROL 120V DIRECT IGNITIONLIGHTING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE LIGHTINGDIRECT IGNITION LIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCEDIRECT IGNITION TROUBLESHOOTING DIRECT IGNITION PROPANE/LP GAS CONVERSIONVALVE CONVERSION DIRECT IGNITION PROPANE/LP GAS CONVERSIONMaxitrol Valve Conversion Cleaning Procedure MAINTENANCE AND SERVICEClean Burner and Control Compartment Glass Cleaning Optional KitsBVD34 & BVD36 PARTS LIST Page BVD34 & BVD36 PARTS VIEW19400-3-0406 BVP42 PARTS LIST Page BVP42 PARTS VIEW19400-3-0406 FBB4 OPTIONAL VARIABLE SPEED BLOWER INSTALLATION BLOWER ASSEMBLY FBB4 OPTIONAL VARIABLE SPEED BLOWER INSTALLATIONJUNCTION BOX FAN BLACK FAN SWITCH WHITE GROUND 110 VOLT AC120V DIRECT IGNITION VALVE MODELS JUNCTION BOX WIRING INSTALLATION INSTRUCTIONSSTANDARD MILLIVOLT VALVE MODELS OPTIONAL ACCESSORIES 19400-0-1005 DECORATIVE ACCESSORIESPage Decorative Louver MissionSERVICE NOTES HOW TO ORDER REPAIR PARTS 19400-3-0406 SERVICE NOTESPage Page SERVICE NOTES19400-3-0406 19400-3-0406 Empire Comfort Systems, IncPage