Vulcan-Hart BVD34FP50(F,L)N-1, BVP42FP52(F,L)N-1 Direct Ignition Troubleshooting

Page 25
DIRECT IGNITION TROUBLESHOOTING

DIRECT IGNITION TROUBLESHOOTING

With proper installation and maintenance, your new Gas Fireplace will provide years of trouble-free service. If you do experience a problem, refer to the troubleshooting guide below. This guide will assist a qualified service person in the diagnosis of problems and the corrective action to be taken. Refer to page 24 for initial startup and GAS Line purge instructions.

SYMPTOM

CHECK

ACTION

No spark when system is turned to “ON”

Check for 120V between black “hot” line

If 120V not present, check fuse or circuit

and reset cycle* has been completed.

at control module and “white” return at

breaker or repair wiring leading to

 

module.

fireplace.

Spark for six (6) seconds at ignitor, but no

a. Check that gas is turned on and system

Turn gas on and/or purge system.

ignition of burner.

purged.

 

 

b. Check that tips of ignitor are directly

Position electrodes so tips are directly

 

above ports on main burner. Spark is

above burner port ports and about ¼" to

 

between electrodes and not from one

3/8" above burner.

 

electrode to burner.

 

 

c. Check for 120V at each coil on the gas

If 120V present, but gas valve does not

 

valve and listen for click, indicating gas

click, replace gas valve.

 

valve is opening.

 

Spark for six (6) seconds, main burner

Check for clean ground path between

Clean, position according to wiring diagram,

lights, but goes out when spark stops.

electrode bracket and fireplace chassis.

and repair defective electric connections. If

 

Check wiring to wiring diagram label.

all electrical connections are clean and

 

Check for broken electrode on high-tension

correct, replace module.

 

lead attachment to module.

 

Main burner lights normally and then goes

a. Check ignitor to burner gap.

Igniter should be located 1/4" to 3/8" above

out.

 

burner area.

 

b. Check high-tension lead and connector

Replace spark electrode assembly.

 

for shorts.

 

 

c. Refer to installation instructions

Repair as required.

 

troubleshooting guide for issues such

 

 

as venting.

 

DIRECT IGNITION PROPANE/LP GAS CONVERSION

The conversion shall be carried out in accordance with the requirements of the provincial authorities having jurisdiction and in accordance with the requirements of the CSA B149.2 installation code (Canada) and with the requirements of the National Fuel Gas Code Z223.1/NFPA 54 (United States).

WARNING: This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer's instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in this instruction is not followed exactly, a fire, explosion, or production of carbon monoxide may result causing property damage, personal injury, or loss of life. The qualified service agency is responsible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer's instructions supplied with the kit.

Installer notice: Using an ink pen, fill out the required information on the conversion label. Remove the backing from label and stick label in a visible position on bottom of fireplace close to gas valve.

Installer notice: These instructions must be left with the appliance.

Instructions for converting your direct ignition fireplace from natural gas to propane/LP gas.

All direct ignition fireplaces are shipped from the factory equipped to operate on natural gas. To convert the direct ignition fireplace to operate on propane/LP gas, follow the instructions on Page

26.Please see the appropriate parts list for your model for parts included with the direct ignition fireplace.

Check the items in the kit with the parts list. Notify the supplier of any items that are missing before installing the conversion kit.

19400-3-0406

Page 25

Image 25
Contents The Keystone B Vent Zero Clearance Gas Fireplace B-VENT GAS FIREPLACEEFFECTIVE DATE APRIL Section TABLE OF CONTENTSIMPORTANT SAFETY INFORMATION That’s your signal to go into immediate action SAFETY INFORMATION FOR USERS OF LP GASLP-GASWARNING ODOR NO ODOR DETECTED - ODOR FADEInstructions to Installer INTRODUCTIONQualified Installing Agency Appliance CertificationFIREPLACE DIMENSIONS SPECIFICATIONSDim BVD34 BVD36LOCATING FIREPLACE CLEARANCESMantel Chart Figure Figure Combustible MaterialInstalling a New Main Gas Cock GAS SUPPLYChecking Manifold Pressures GAS SUPPLY CONTInstall the Fresh Air Kit - BVA1 INSTALLATIONFraming and Finishing Figure Vent Pipe ClearanceCombustible Surround Installation INSTALLATION CONTFinishing Figure General Maintenance VENTINGInstalling the Vent System in a Chase Vent RunsVent Size VENTING CONTNever downsize venting diameters Clearances Vent ConfigurationEMBER MATERIAL PLACEMENT ON BURNER LOG PLACEMENT 5 LOG SETEMBER PLACEMENT LOG PLACEMENT 3 LOG SETBOTTOM LOG LOCATOR PINS TOP BRANCH REAR LOG BOTTOM LOGGAS CONTROL KNOB SHOWN IN OFF POSITION OPERATING INSTRUCTIONS750 Millivolt System Initial LightingWall Switch, FWS-1optional OPERATING INSTRUCTIONS CONTFRBC Battery Operated Remote Control Electric 120 volt Operated Remote Control, FRECSTANDING PILOT WIRING DIAGRAM STANDING PILOT LIGHTING INSTRUCTIONS FOR YOUR SAFETY, READ BEFORE LIGHTINGLIGHTING INSTRUCTIONS TO TURN OFF GAS TO FIREPLACE4.Frequent pilot outage problem STANDING PILOT TROUBLESHOOTING6.Glass Sooting CHECK SAFETY SHUTDOWN PERFORMANCE STANDING PILOT PROPANE/LP GAS CONVERSIONSAFETY SHUTDOWN SYSTEM B-VENTFIREPLACESPILOT ORIFICE CONVERSION OPTIONAL REMOTE CONTROL 120V DIRECT IGNITION DIRECT IGNITION WIRING DIAGRAMDIRECT IGNITION LIGHTING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE LIGHTINGLIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCEDIRECT IGNITION PROPANE/LP GAS CONVERSION DIRECT IGNITION TROUBLESHOOTINGMaxitrol Valve Conversion DIRECT IGNITION PROPANE/LP GAS CONVERSIONVALVE CONVERSION Clean Burner and Control Compartment MAINTENANCE AND SERVICECleaning Procedure Glass Cleaning Optional KitsBVD34 & BVD36 PARTS LIST 19400-3-0406 BVD34 & BVD36 PARTS VIEWPage BVP42 PARTS LIST 19400-3-0406 BVP42 PARTS VIEWPage FBB4 OPTIONAL VARIABLE SPEED BLOWER INSTALLATION JUNCTION BOX FAN BLACK FAN SWITCH WHITE GROUND FBB4 OPTIONAL VARIABLE SPEED BLOWER INSTALLATIONBLOWER ASSEMBLY 110 VOLT ACSTANDARD MILLIVOLT VALVE MODELS JUNCTION BOX WIRING INSTALLATION INSTRUCTIONS120V DIRECT IGNITION VALVE MODELS OPTIONAL ACCESSORIES Page DECORATIVE ACCESSORIES19400-0-1005 Decorative Louver MissionSERVICE NOTES HOW TO ORDER REPAIR PARTS Page SERVICE NOTES19400-3-0406 19400-3-0406 SERVICE NOTESPage Page Empire Comfort Systems, Inc19400-3-0406