Step 2.2 Optional: Extending the power cable
1Prepare the following tools.
Tools | Spec | Shape |
Crimping |
| |
pliers |
| |
|
| |
Connection | 20xØ6.5 |
|
sleeve (mm) | (HxOD) |
|
Insulation | Width 19 mm |
|
tape |
| |
|
| |
Contraction | 70xØ8.0 (LxOD) |
|
tube (mm) |
| |
|
|
2As shown in the figure, peel off the shields from the rubber and wire of the power cable.
•Peel off 20 mm of cable shields from the pre- installed tube.
CAUTION
•For information about the power cable specifications for indoor and outdoor units, refer to the installation manual.
•After peeling off the tube wire, you must insert a contraction tube.
4Using a crimping tool, compress the two points and flip it over and compress another two points in the same location.
• The compression dimension should be 8.0.
Compression dimension
•After compressing it, pull both sides of the wire to make sure it is firmly pressed.
Method 1 | Method 2 |
Compress it 4 times. | Compress it 4 times. |
5 mm | 5 mm |
5Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation tape.
Three or more layers of insulation are required.
Method 1 | Method 2 |
Insulation tape | Insulation tape |
Power cable
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 20 |
|
|
| 20 |
|
|
| 20 |
|
| |
|
|
|
|
|
|
|
| 60 |
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 120 |
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| 180 |
|
|
|
| (Unit: mm) |
|
40 mm | 35 mm |
|
6Apply heat to the contraction tube to contract it.
Contraction tube
7After tube contraction work is completed, wrap it with the insulation tape to finish.
20
(Unit: mm)
3Insert both sides of core wire of the power cable into the connection sleeve.
•Method 1: Push the core wire into the sleeve from both sides.
•Method 2: Twist the wire cores together and push it into the sleeve.
Method 1 | Method 2 | ||
|
|
| |
|
|
|
|
Connection sleeve | Connection sleeve |
Insulation tape
CAUTION
•Make sure that the connection parts are not exposed to outside.
•Be sure to use insulation tape and a contraction tube made of approved reinforced insulating materials that have the same level of withstand voltage with the power cable. (Comply with the local regulations on extensions.)
Installation
English 35