Samsung AR18NVFHEWKXMG manual Shortening or extending the refrigerant pipes assembly pipe

Page 38

1Cut out the appropriate knock-out piece (A, B, C) on the rear of the indoor unit unless you connect the pipe directly from the rear.

2Smooth the cut edges.

3Remove the protection caps of the pipes and connect the assembly pipe to each pipe. Tighten the nuts first with your hands, and then with a torque wrench, applying the following torque:

Outer diameter (mm)

Torque (N•m)

Torque (kgf•cm)

 

 

 

ø 6.35

14 to 18

140 to 180

 

 

 

ø 9.52

34 to 42

350 to 430

 

 

 

ø 12.70

49 to 61

500 to 620

 

 

 

ø 15.88

68 to 82

690 to 830

 

 

 

Step 2.7 Shortening or extending the refrigerant pipes (assembly pipe)

 

 

Pipe cutter

 

 

 

Pipe

 

90°

Oblique

Rough

Burr

NOTE

If you want to shorten or extend the pipes, see Step 2.7 Shortening or extending the refrigerant pipes (assembly pipe) on page 38.

4Cut off the remaining foam insulation.

5If necessary, bend the pipe to fit along the bottom of the indoor unit. Then pull it out through the appropriate hole.

The pipe should not project from the rear of the indoor unit.

The bending radius should be 100 mm or more.

6Pass the pipe through the hole in the wall.

NOTE

The pipe will be insulated and fixed permanently into position after finishing the installation and the gas leak test. For further details. see Step 4.1 Performing the gas leak tests on page 44.

D

 

90°±2°

 

 

 

A

45°±2°

 

 

 

 

L

 

 

R 0.4 to 0.8

Pipe

Flare

D

 

 

 

 

(Unit: mm)

Outer diameter (D)

Depth (A)

Flare dimension (L)

ø 6.35

1.3

8.7 to 9.1

ø 9.52

1.8

12.8 to 13.2

ø 12.70

2.0

16.2 to 16.6

ø 15.88

2.2

19.3 to 19.7

Flare nut

Installation

CAUTION

Tighten the flare nut with a torque wrench according to specified method. If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

Do not box in or cover the pipe connection. All refrigerant pipe connection must be easily accessible and serviceable.

Indoor outlet pipeConnecting pipe

Outer diameter (mm)

Torque (N•m)

Torque (kgf•cm)

 

 

 

ø 6.35

14 to 18

140 to 180

ø 9.52

34 to 42

350 to 430

 

 

 

ø 12.70

49 to 61

500 to 620

 

 

 

ø 15.88

68 to 82

690 to 830

 

 

 

38English

Image 38
Contents Air conditioner Contents Correct disposal of batteries in this product This may result in electric shock or fire Safety InformationFailing to do so may result in electric shock or fire For Power Supply This may result in electric shock or burns Do not touch the circuit breakerwith wet handsThis may result in electric shock This may result in children seriously injuring themselvesDo not drink the water from the air conditioner Do not clean the inside of the air conditioner by yourselfDo not operate the appliance with wet hands Indoor Unit Overview Timer indicatorOperation indicator DisplayRemote Control Overview Inserting batteriesOperation modes Remote Control OperationControlling temperature Horizontal air flow manual Controlling fan speedControlling air flow direction Step cooling function Cool modeCooling Operation Dry mode Dehumidifying OperationHeat mode Heating OperationFan mode Quick Smart FeaturesAuto mode Fast function Comfort functionQuiet function Beep sound functionEnergy-Saving Operation Single user functionTimed on/Timed off function Good’sleep function Cleaning duration Minutes Cleaning at a GlanceRunning Auto clean Do not clean the display by using alkaline detergentCleaning the filter Troubleshooting Does not work Setting the time Indicator blinks Problem Solution Cannot change the fanReplace the batteries in the remote control with new ones Check whether the drains are clean. Clean them regularlyTechnical Specifications Model27˚C 29˚C 20˚C Installation of the unit General informationInstallation manual Power supply line, fuse, or circuit breakerInstall the unit in a place where water can drain smoothly Cases Choosing the installation locationMinimum clearances for the outdoor unit Indoor unit Packing and UnpackingUnit mm Outdoor unitOptional accessories AccessoriesAccessories in the indoor unit package Tools Accessories in the outdoor unit packageDrilling a hole through the wall Taping the pipes, cables, and drain hose Indoor Unit Installation Apply heat to the contraction tube to contract it Optional Extending the power cablePrepare the following tools Optional Extending the drain hose Installing and connecting the drain hoseInstall the drain hose Or a fireOptional Changing the direction of the drain hose Shortening or extending the refrigerant pipes assembly pipe When fixing the indoor unit on a window frame Fixing the installation plateWhen fixing the indoor unit on a wall When fixing the indoor unit on a gypsum board Fix the installation plate without inclining to one sideOptional Fixing the outdoor unit to a wall with a rack Outdoor Unit InstallationRefrigerant pipes Cooling capacity and malfunction. Use a vacuum pump Leave the system in the standby modeEvacuating the air Adding refrigerant RefrigerantPerforming the gas leak tests Installation InspectionRunning the Smart Install mode Off, Blinking, On LEDPerforming final check and trial operation Pumping down for removing the productQuestions or COMMENTS?