Samsung AR24NSFHEWKNMG, AR24NVFHEWKXMG, AR18NVFHEWKXMG manual Adding refrigerant, Refrigerant

Page 43

3Open the valve of the low pressure side of manifold gauge anticlockwise.

4Evacuate the air in the connected pipes using the vacuum pump for about 15 minutes.

Make sure that pressure gauge shows -0.1 MPa (-76 cmHg, 5 torr) after about 10 minutes. This procedure is very important to avoid a gas leak.

Close the valve of the low pressure side of manifold gauge clockwise.

Turn off the vacuum pump.

Check for 2 minutes if there is any pressure change.

Remove the hose of the low pressure side of manifold gauge.

5Set a valve cork of liquid and gas service port to the open position.

Step 3.4 Adding refrigerant

If you use a pipe longer than the length specified in the piping codes and standards, you must add 15g of refrigerant R-410A for each extra meter. If you use a pipe shorter than the length specified in the piping codes and standards, the evacuating time is normal.

Refer to the Service Manual for further details.

CAUTION

The remaining air in the Refrigeration cycle, which contains moisture, may cause malfunction on the compressor.

Always contact the service centre or a professional installation agency for product installation.

R-410A is a mixed type of refrigerant. It is necessary for recharging under conditions of liquid. When recharging refrigerant from the refrigerant cylinder to the equipment.

Before recharging, check whether the cylinder has a siphon or not. There are two ways to recharge the

refrigerant:

 

 

Siphon

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Charge the refrigerant

Charge the refrigerant turning

standing the cylinder upright.

the cylinder upside down.

<Cylinder with siphon>

<Cylinder without siphon>

NOTE

If R-410A refrigerant is charged with gas, the composition of the charged refrigerant changes and the characteristics of the equipment vary.

During the measuring operation of refrigerant quantity added use electronic scales. If cylinder doesn't have siphon, upset it.

Installation

English 43

Image 43
Contents Air conditioner Contents Correct disposal of batteries in this product Failing to do so may result in electric shock or fire Safety InformationThis may result in electric shock or fire For Power Supply This may result in children seriously injuring themselves Do not touch the circuit breakerwith wet handsThis may result in electric shock This may result in electric shock or burnsDo not operate the appliance with wet hands Do not clean the inside of the air conditioner by yourselfDo not drink the water from the air conditioner Display Timer indicatorOperation indicator Indoor Unit OverviewInserting batteries Remote Control OverviewControlling temperature Remote Control OperationOperation modes Controlling air flow direction Controlling fan speedHorizontal air flow manual Cooling Operation Cool modeStep cooling function Dehumidifying Operation Dry modeHeating Operation Heat modeAuto mode Quick Smart FeaturesFan mode Comfort function Fast functionBeep sound function Quiet functionSingle user function Energy-Saving OperationTimed on/Timed off function Good’sleep function Do not clean the display by using alkaline detergent Cleaning at a GlanceRunning Auto clean Cleaning duration MinutesCleaning the filter Troubleshooting Check whether the drains are clean. Clean them regularly Problem Solution Cannot change the fanReplace the batteries in the remote control with new ones Does not work Setting the time Indicator blinksModel Technical Specifications27˚C 29˚C 20˚C General information Installation of the unitInstall the unit in a place where water can drain smoothly Power supply line, fuse, or circuit breakerInstallation manual Minimum clearances for the outdoor unit Choosing the installation locationCases Outdoor unit Packing and UnpackingUnit mm Indoor unitAccessories in the indoor unit package AccessoriesOptional accessories Drilling a hole through the wall Accessories in the outdoor unit packageTools Taping the pipes, cables, and drain hose Indoor Unit Installation Prepare the following tools Optional Extending the power cableApply heat to the contraction tube to contract it Or a fire Installing and connecting the drain hoseInstall the drain hose Optional Extending the drain hoseOptional Changing the direction of the drain hose Shortening or extending the refrigerant pipes assembly pipe When fixing the indoor unit on a wall Fixing the installation plateWhen fixing the indoor unit on a window frame Fix the installation plate without inclining to one side When fixing the indoor unit on a gypsum boardRefrigerant pipes Outdoor Unit InstallationOptional Fixing the outdoor unit to a wall with a rack Evacuating the air Leave the system in the standby modeCooling capacity and malfunction. Use a vacuum pump Refrigerant Adding refrigerantRunning the Smart Install mode Installation InspectionPerforming the gas leak tests LED Off, Blinking, OnPumping down for removing the product Performing final check and trial operationQuestions or COMMENTS?