Samsung AR24NSFHEWKNMG, AR24NVFHEWKXMG, AR18NVFHEWKXMG Performing final check and trial operation

Page 46

Installation

Step 4.3 Performing final check and trial operation

1Check the following:

Strength of the installation site

Tightness of pipe connection to detect gas leak

Electric wiring connection

Heat-resistant insulation of the pipe

Drainage

Grounding conductor connection

Correct operation (Take the following steps.)

2Press the (Power) button on the remote control to check the following:

The indicator on the indoor unit lights up.

The airflow blade opens and the fan gears up for operation.

3Press the (Mode) button to select Cool or Heat mode. Then take the following sub-steps:

In Cool mode, use the Temperature button to set the set temperature to 16 °C.

In Heat mode, use the Temperature button to set the set temperature to 30 °C.

Check whether, approximately 3 to 5 minutes later, the outdoor unit starts, and a cool or warm air blows out.

After12 minutes of stationary condition, check the indoor unit air treatment.

4Press the (Air swing) button to check whether the airflow blades work properly.

5Press the (Power) button to stop the trial operation.

Pumping down for removing the product

Pump-down is an operation intended to collect all the system refrigerant in the outdoor unit. This operation must be carried out before disconnecting the refrigerant tubing in order to avoid refrigerant loss to the atmosphere.

WARNING

After installing the product, be sure to perform leak tests on the piping connections. After pumping down refrigerant to inspect or relocate the outdoor unit, be sure to stop the compressor and then remove the connected pipes.

–– Do not operate the compressor while a valve is open due to refrigerant leakage from a pipe or an unconnected or incorrectly connected pipe. Failure to do so may cause air to flow into the compressor and too a high pressure to develop inside the refrigerant circuit, leading to an explosion or product malfunction.

1Hold down the (Power) button on the indoor unit for 5 seconds. Beep sounds immediately to indicate that the product is ready for pump down procedure.

2Let the compressor run for more than 5 minutes.

3Release the valve caps on High and Low pressure side.

4Use L-wrench to close the valve on the high pressure side.

5After approximately 1 minute, close the valve on the low pressure side.

6Stop operation of the air conditioner by pressing the (Power) button on the indoor unit or remote control.

7Disconnect the pipes.

CAUTION

Compressor damage may occur if the compressor is run at a negative suction pressure.

 

1

 

1 minute

Liquid service port

Gas service port

<High pressure>

<Low pressure>

2

Off

46English

Image 46
Contents Air conditioner Contents Correct disposal of batteries in this product Failing to do so may result in electric shock or fire Safety InformationThis may result in electric shock or fire For Power Supply This may result in electric shock or burns Do not touch the circuit breakerwith wet handsThis may result in electric shock This may result in children seriously injuring themselvesDo not operate the appliance with wet hands Do not clean the inside of the air conditioner by yourselfDo not drink the water from the air conditioner Indoor Unit Overview Timer indicatorOperation indicator DisplayRemote Control Overview Inserting batteriesControlling temperature Remote Control OperationOperation modes Controlling air flow direction Controlling fan speedHorizontal air flow manual Cooling Operation Cool modeStep cooling function Dry mode Dehumidifying OperationHeat mode Heating OperationAuto mode Quick Smart FeaturesFan mode Fast function Comfort functionQuiet function Beep sound functionEnergy-Saving Operation Single user functionTimed on/Timed off function Good’sleep function Cleaning duration Minutes Cleaning at a GlanceRunning Auto clean Do not clean the display by using alkaline detergentCleaning the filter Troubleshooting Does not work Setting the time Indicator blinks Problem Solution Cannot change the fanReplace the batteries in the remote control with new ones Check whether the drains are clean. Clean them regularlyTechnical Specifications Model27˚C 29˚C 20˚C Installation of the unit General informationInstall the unit in a place where water can drain smoothly Power supply line, fuse, or circuit breakerInstallation manual Minimum clearances for the outdoor unit Choosing the installation locationCases Indoor unit Packing and UnpackingUnit mm Outdoor unitAccessories in the indoor unit package AccessoriesOptional accessories Drilling a hole through the wall Accessories in the outdoor unit packageTools Taping the pipes, cables, and drain hose Indoor Unit Installation Prepare the following tools Optional Extending the power cableApply heat to the contraction tube to contract it Optional Extending the drain hose Installing and connecting the drain hoseInstall the drain hose Or a fireOptional Changing the direction of the drain hose Shortening or extending the refrigerant pipes assembly pipe When fixing the indoor unit on a wall Fixing the installation plateWhen fixing the indoor unit on a window frame When fixing the indoor unit on a gypsum board Fix the installation plate without inclining to one sideRefrigerant pipes Outdoor Unit InstallationOptional Fixing the outdoor unit to a wall with a rack Evacuating the air Leave the system in the standby modeCooling capacity and malfunction. Use a vacuum pump Adding refrigerant RefrigerantRunning the Smart Install mode Installation InspectionPerforming the gas leak tests Off, Blinking, On LEDPerforming final check and trial operation Pumping down for removing the productQuestions or COMMENTS?