Samsung AR10NVFSCURNSV manual Adding refrigerant, Refrigerant

Page 39

3Open the valve of the low pressure side of manifold gauge anticlockwise.

4Evacuate the air in the connected pipes using the vacuum pump for about 15 minutes.

Make sure that pressure gauge shows -0.1 MPa

(-76 cmHg, 5 torr) after about 10 minutes. This procedure is very important to avoid a gas leak.

Close the valve of the low pressure side of manifold gauge clockwise.

Turn off the vacuum pump.

Check for 2 minutes if there is any pressure change.

Remove the hose of the low pressure side of manifold gauge.

5Set a valve cork of liquid and gas service port to the open position.

Step 3.4 Adding refrigerant

If you use a pipe longer than the length specified in the piping codes and standards, you must add 15g of refrigerant R-410A for each extra meter. If you use a pipe shorter than the length specified in the piping codes and standards, the evacuating time is normal.

Refer to the Service Manual for further details.

CAUTION

The remaining air in the Refrigeration cycle, which contains moisture, may cause malfunction on the compressor.

Always contact the service centre or a professional installation agency for product installation.

R-410A is a mixed type of refrigerant. It is necessary for recharging under conditions of liquid. When recharging refrigerant from the refrigerant cylinder to the equipment.

Before recharging, check whether the cylinder has a siphon or not. There are two ways to recharge the

refrigerant:

 

 

Siphon

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Charge the refrigerant

Charge the refrigerant turning

standing the cylinder upright.

the cylinder upside down.

<Cylinder with siphon>

<Cylinder without siphon>

NOTE

If R-410A refrigerant is charged with gas, the composition of the charged refrigerant changes and the characteristics of the equipment vary.

During the measuring operation of refrigerant quantity added use electronic scales. If cylinder doesn't have siphon, upset it.

Installation

English 39

Image 39
Contents Air conditioner Contents Correct disposal of batteries in this product Safety Information Failing to do so may result in electric shock or fireThis may result in electric shock or fire For Power Supply This may result in children seriously injuring themselves Do not touch the circuit breakerwith wet handsThis may result in electric shock This may result in electric shock or burnsDo not clean the inside of the air conditioner by yourself Do not operate the appliance with wet handsDo not drink the water from the air conditioner Display Timer indicatorOperation indicator Indoor Unit OverviewInserting batteries Remote Control OverviewRemote Control Operation Controlling temperatureOperation modes Controlling fan speed Controlling air flow directionHorizontal air flow manual Cool mode Cooling OperationStep cooling function Dehumidifying Operation Dry modeQuick Smart Features Auto modeFan mode Comfort function Fast functionBeep sound function Quiet functionSingle user function Cool mode When the Single user function starts,Button Cool mode Select Single user Energy-Saving OperationTimed on/Timed off function Good’sleep function Do not clean the display by using alkaline detergent Cleaning at a GlanceRunning Auto clean Cleaning duration MinutesCleaning the filter Troubleshooting An error is indicated Problem Solution Timed on/offFunction does not work Setting the time Indicator blinks Check whether the drains are clean. Clean them regularlyGeneral information Installation of the unitInstall the unit in a place where water can drain smoothly Power supply line, fuse, or circuit breakerChoosing the installation location Minimum clearances for the outdoor unitCases Unpacking the indoor unit Checking and preparing accessories and toolsAccessories UnpackingOptional accessories Accessories in the outdoor unit packageTools Drilling a hole through the wall Taping the pipes, cables, and drain hoseIndoor Unit Installation Optional Extending the power cable Prepare the following toolsApply heat to the contraction tube to contract it Installing and connecting the drain hose Install the drain hoseOptional Extending the drain hose Optional Changing the direction of the drain hose Shortening or extending the refrigerant pipes assembly pipe Fixing the installation plate When fixing the indoor unit on a wallWhen fixing the indoor unit on a window frame Fix the installation plate without inclining to one side When fixing the indoor unit on a gypsum boardOptional Fixing the outdoor unit to a wall with a rack Outdoor Unit InstallationPipes Fixing the outdoor unit in placeEvacuating the air Refrigerant Adding refrigerantInstallation Inspection Running the Smart Install modePerforming the gas leak tests LED Off, Blinking, OnPress the Power button to stop the trial operation Performing final check and trial operationPumping down for removing the product English English Questions or COMMENTS?