9Gas Information

9Gas Information

A. Fuel Conversion

C. Gas Connection

Before making gas connections ensure appliance being in- stalled is compatible with the available gas type.

Any natural or propane gas conversions necessary to meet the appliance and locality needs must be made by a quali-

ed technician using Hearth & Home Technologies specifi ed and approved parts.

Note: Have the gas supply line installed in accordance with local building codes, if any. If not, follow ANSI 223.1. Installation should be done by a qualifi ed installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fi tter.)

B. Gas Pressure

Proper input pressures are required for optimum appliance performance. Gas line sizing requirements need to be made following NFPA51.

A. Fuel Conversion WARNING

Fire Risk

Explosion Risk

High pressure will damage valve.

Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1/2 psig.

Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1/2 psig.

Note: A listed (and Commonwealth of Massachusetts approved) 1/2 in. (13 mm) T-handle manual shut-off valve and fl exible gas connector are connected to the 1/2 in. (13 mm) control valve inlet.

If substituting for these components, please consult local codes for compliance.

Refer to Reference Section 16 for location of gas line access in appliance.

Note: Gas line may be run from either side of appliance using one of the knockouts provided. Hole in outer shell NOT to exceed 2-1/2 in. and should never penetrate the fi rebox.

C. Gas Connection WARNING

Fire Risk

Explosion Risk

Verify inlet pressures.

High pressure may cause overfire condition.

Low pressure may cause explosion.

Verify minimum pressures when other household gas appliances are operating.

Install regulator upstream of valve if line pressure is greater than 1/2 psig.

Pressure requirements for appliance are shown in table be- low. Minimum pressures must be met when other household gas appliances are operating.

Pressure

Natural Gas

Propane

Minimum Inlet Pressure

5.0 in. w.c.

11.0 in. w.c.

Maximum Inlet Pressure

7.0 in. w.c.

14.0 in. w.c.

Manifold Pressure

3.5 in. w.c.

10.0 in. w.c.

B. Gas Pressure WARNING

Gas Leak Risk

Support control when attaching pipe to prevent bending gas line.

Note: The gap between supply piping and gas access hole may be caulked with high temperature caulk or stuffed with non-combustible, unfaced insulation to prevent cold air infi ltration.

Ensure that gas line does not come in contact with outer wrap of appliance. Follow local codes.

Incoming gas line should be piped into the valve compartment and connected to the 1/2 in. connection on the manual shutoff valve.

Heatilator • GB4336/GB4992 • 4003-085 Rev H • 04/06

19

Image 19
Contents B-VentGas Appliance What to do if you smell gasModels GB4336, GB4336L GB4336I, GB4336IL GB4942, GB4942L GB4942I, GB4942ILGas Type Homeowner Reference InformationListing Label Information/Location Congratulations12 Appliance Setup Table of Contents5 Vent Information and Diagrams 8 Installing Vent PipeC. BTU Specifications D. High Altitude Installations1Listing and Code Approvals A. Appliance Certification2Getting Started A. Design and Installation ConsiderationsNegative Pressure B. Negative PressureAsphyxiation Risk D. Inspect the Appliance and Components C. Tools and Supplies NeededAny such action may cause a fire hazard A. Select Appliance Location 3Framing and ClearancesFire Risk Fire Risk B. Construct the Appliance ChaseFire Risk Odor Risk C. Clearancesto perpendicular wall D. Mantel ProjectionsTop of Appliance Drywall A 48 in 1219 mm B max Mantel Leg or Perpendicular Wall A1 in. 25mm minA. Vent Termination Minimum Clearances 4Termination LocationsFire Risk Explosion Risk Fire Risk Asphyxiation Risk 5Vent Information and DiagramsA. Vent Guidelines B. Vent System ConfigurationFire Risk Explosion Risk Vent supportsC. Vertical Penetration Framing 6Vent Clearances and FramingA. Pipe Clearances to Combustibles B. Wall Penetration FramingFire Risk Asphyxiation Risk A. Installing Outside Air Kit Damper AssemblyAppliance Preparation Risk of Smoke Spillageboth sides B. Gas and Electrical ConnectionsC. Securing and Leveling Appliance Nailing TabsC. Securing Vent Sections 8Installing Vent PipeB. Attach Vent to Firebox Assembly A. Assemble Vent SectionsB. Gas Pressure 9Gas InformationA. Fuel Conversion C. Gas ConnectionFire Risk Explosion Risk Asphyxiation Risk D. High Altitude InstallationsFire Risk Explosion Risk Gas build-upduring line purge may ignite10 Electrical Information A. Recommendation for WireB. Connecting to the Appliance C. Intellifire Ignition System WiringOptional Accessories Requirements D. Standing Pilot Ignition System WiringOptional Junction Box Wiring E. Junction Box Installation Fire Risk 11 FinishingA. Mantel Projections B. Facing MaterialD.Install the Refractory 12 Appliance SetupB. Clean the Appliance C. AccessoriesF. Log Removal/Replacement Fire Risk Combustion Fumes Risk I. Air Shutter SettingG. Glass Doors H. HoodSEVERE BURNS MAY RESULT 13 Operating InstructionsA. Before Lighting Appliance Fire Risk Burn Risk HOT! DO NOT TOUCHWithout C. High Limit Safety SwitchB. Check Appliance Draft Note to Qualified Service TechnicianLIGHTING INSTRUCTIONS D. Lighting the ApplianceWARNING RISK OF FIRE FOR YOUR SAFETY READ BEFORE LIGHTINGTO TURN OFF GAS TO APPLIANCE FOR YOUR SAFETY READ BEFORE LIGHTINGNATURAL GAS LIGHTING INSTRUCTIONSIssue F. Frequently Asked QuestionsE. After the Appliance is Lit Initial Break-inProcedurePossible Causes 14 TroubleshootingA. Standing Pilot Ignition System SymptomFrequent pilot outage SymptomPossible Causes Corrective ActionsCorrective Actions B. Intellifire Ignition SystemSymptom Possible CausesPilot sparks, but pilot will SymptomPossible Causes Corrective ActionsRisk of injury or property damage 15 Maintaining and Servicing the ApplianceClean When cleaning glass doorone is not present Maintenance and Service TasksMaintenance Tasks InspectModel A. Appliance Dimension Diagram16 Reference Materials Figure 16.1 Appliance DimensionsExploded Parts Diagram Service PartsB. Service Parts List GB4336 SERIESGB4336 Service PartsGB4336 SERIES Description of PartService Parts List Standing Pilot Valve AssemblyIntermittent Pilot Valve Assembly Service PartsGB4336 Service PartsGB4336 SERIES Description of PartBeginning Manufacturing Date 1/19/04 GB4942 SERIESService Parts Exploded Parts DiagramGB4942 Service PartsGB4942 SERIES # Description of PartService Parts List Service PartsStanding Pilot Valve Assembly Intermittent Pilot Valve AssemblyGB4942 Service PartsGB4942 SERIES # Description of PartUD4 Uninsulated Duct 4 in. 102 mm 42 in 1067 mm C. Optional ComponentsID4 Insulated Duct in. 102 mmThis page intentionally left blank This page intentionally left blank 1 Year Limited Warranty D. Limited Lifetime WarrantyGas Appliance Fireplace Limited Lifetime Warranty Limited Lifetime WarrantyDO NOT DISCARD THIS MANUAL E. Contact InformationHearth & Home Technologies Inc 1915 W. Saunders Street Mt. Pleasant, Iowa