Heatiator CB4842IR, CB4236IR Gas Information, Fuel Conversion, Gas Pressure, Gas Connection

Page 25

11 Gas Information

A. Fuel Conversion

Make sure the appliance is compatible with available gas types.

Conversions must be made by a qualified service technician using Hearth & Home Technologies specified and approved parts.

B. Gas Pressure

Optimum appliance performance requires proper input pressures.

Gas line sizing requirements will be determined in ANSI Z221.3 National Fuel Gas Code in the USA and CAN/ CGA B149 in Canada.

Pressure requirements are:

 

Gas Pressure

Natural Gas

Propane

 

Minimum inlet pressure

5.0 in. w.c.

11.0 in. w.c.

Maximum inlet pressure

10.0 in. w.c.

13.0 in. w.c.

 

Manifold pressure

3.5 in. w.c.

10.0 in. w.c.

C. Gas Connection

Refer to Reference Section 16.A. for location of gas line access in appliance.

Gas line may be run through knockout(s) provided on either side or the bottom of the appliance.

The gap between supply piping and gas access hole may be caulked with high temperature caulk or stuffed with non-combustible, unfaced insulation to prevent cold air infiltration.

Ensure that gas line does not come in contact with outer wrap of the appliance. Follow local codes.

Pipe incoming gas line into valve compartment.

Connect incoming gas line to the 1/2 in. (13 mm) connection on manual shutoff valve.

WARNING! Risk of Fire or Explosion! Support control when attaching pipe to prevent bending gas line.

A small amount of air will be in the gas supply lines.

WARNING! Risk of Fire or Explosion! Gas build-up dur- ing line purge could ignite.

WARNING! Risk of Fire or Explosion! High pressure will damage valve. Low pressure may cause explosion.

Verify inlet pressures. Verify minimum pressures when other household gas appliances are operating.

Install regulator upstream of valve if line pressure is greater than 1/2 psig.

Purge should be performed by qualified service technician.

Ensure adequate ventilation.

Ensure there are no ignition sources such as sparks or open flames.

Light the appliance. It will take a short time for air to purge from lines. When purging is complete the appliance will light and operate normally.

WARNING

Fire Risk.

Explosion Hazard.

High pressure will damage valve.

Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1/2 psig.

Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1/2 psig.

Note: Have the gas supply line installed in accordance with local codes, if any. If not, follow ANSI 223.1. Installation should be done by a qualified installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter).

Note: A listed (and Commonwealth of Massachusetts approved) 1/2 in. (13 mm) T-handle manual shut-off valve and flexible gas connector are connected to the 1/2 in. (13 mm) control valve inlet.

If substituting for these components, please consult local codes for compliance.

WARNING! Risk of Fire, Explosion or Asphyxiation! Check all fittings and connections with a non-corrosive commercially available leak-check solution. DO NOT use open flame. Fittings and connections could have loos- ened during shipping and handling.

WARNING! Risk of Fire! DO NOT change valve settings. This valve has been preset at the factory.

D. High Altitude Installations

NOTICE: If the heating value of the gas has been reduced, these rules do not apply. Check with your local gas utility or authorities having jurisdiction.

When installing above 2000 feet elevation:

In the USA: Reduce burner orifice 4% for each 1000 feet above 2000 feet.

In CANADA: Reduce burner orifice 10% for elevations between 2000 feet and 4500 feet. Above 4500 feet, consult local gas utility.

Heatilator • Caliber BV Series • 4040-262 • Rev M • 08/09

25

Image 25
Contents Models CB4236IR CB4842IR Vent Gas Appliance Installation and OperationWhat to do if you smell gas Homeowner Reference Information CongratulationsInstaller Guide Table of ContentsUser Guide  a Limited Lifetime Warranty Warranty Hearth & Home Technologies IncThis warranty is void if WarrantyListing and Code Approvals Operating Instructions Gas Fireplace SafetyYour Fireplace Remote Controls, Wall Controls and Wall Switches Fixed Glass AssemblyFan Kit optional Clear SpaceLighting Instructions IPI For Your Safety Read Before LightingFrequently Asked Questions  L. Flame Adjustment ControlInitial Break-in Procedure After Fireplace is LitMaintenance Tasks-Homeowner Maintenance and ServiceMaintenance Tasks-Qualified Service Technician Typical Appliance System Getting StartedTools and Supplies Needed Design and Installation ConsiderationsInspect Appliance and Components Negative Pressure Selecting Appliance Location Framing and ClearancesConstructing the Appliance Chase Width Height Depth Model Rough Opening Rough Opening ClearancesMantels Mantel and Wall ProjectionsMantel Legs or Wall Projections Vent Termination Minimum Clearances Termination LocationsVent System Configuration Vent Information and DiagramsVent Guidelines Pipe Clearances to Combustibles Vent Clearances and FramingWall and Ceiling Penetration Framing Vertical Penetration FramingGas and Electrical Connections Appliance PreparationAssembly of Vent Sections Installing Vent PipeInstall Attic Insulation Shield Secure Vent SectionsFuel Conversion Gas InformationGas Pressure Gas ConnectionOptional Accessories Requirements Wiring RequirementsIntellifire Ignition System Wiring Electrical Service and RepairWall Switch Installation for Fan Optional Junction Box InstallationFacing Material FinishingAppliance Setup Glass Assembly Install the Log AssemblyFirescreen Air Shutter Setting Install Louvers and TrimHood Intellifire Ignition System TroubleshootingHave accumulated on flame sensing rod Reference Materials Appliance Dimension DiagramCB4236IR  B. Service Parts ListCB4842IR Service Parts ListIPI Valve Assembly  C. Optional Components Model # Description Optional ComponentsContact Information