Desa CLD3924NTB, CLD3018PTA Installation, Ventilation AIR, Ventilation Air From Inside Building

Page 7

AIR FOR COMBUSTION

AND VENTILATION

Continued

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an un- confined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be oper- ated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Section

5.3or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un- confined space. When ventilating to an adjoining unconfined space, you must provide two perma- nent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent open- ings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-con- trolled power vent. Heated air entering the attic will activate the power vent.

 

Outlet

Ventilated

 

Attic

 

Air

 

 

Outlet

 

 

Air

 

To Attic

 

 

 

 

To

 

 

Crawl

Inlet

 

Space

 

 

Air

 

 

 

Inlet Air

Ventilated

 

Crawl Space

 

 

Figure 3 - Ventilation Air from Outdoors

INSTALLATION

NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your pri- mary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help

Ventilation

Grills

Into Adjoining

12"

Ventilation Grills

Into Adjoining Room,

circulate the heat throughout the house. In the event of a power

Room,

Or

Option 2

outage, you can use this heater

Option 1

Remove

Door into Adjoining Room, Option 3

as your primary heat source.

12"

WARNING: A qualified ser- vice person must install heater. Follow all local codes.

Figure 2 - Ventilation Air from Inside

Building

113101-01A

www.desatech.com

7

Image 7
Contents Patent Pending 24 Variable MANUALLY-CONTROLLED ModelsTable of Contents Safety Information Product Identification AIR for Combustion Ventilation Product FeaturesLocal Codes UnpackingDetermining if You Have a Confined or Unconfined Space Determining FRESH-AIR Flow for Fireplace LocationUnusually Tight Construction Confined Space and Unconfined SpaceVentilation Air From Outdoors InstallationVentilation AIR Ventilation Air From Inside BuildingLog Size Side Wall Ceiling Check GAS TypeMinimum Firebox Size Minimum Noncombustible Material Clearances Material Requirements for Distance a Safe InstallationMantel Clearances Determining Minimum Mantel Clearance when Using a HoodDetermining Minimum Mantel Clearance Floor Clearances Minimum Mantel Clearances When Using HoodDiameter ins Area sq. ins Installing Damper Clamp Accessory for Vented OperationInstalling Heater Base Assembly Chimney Minimum PermanentInstallation Items Needed Connecting to GAS SupplyPropane/LP NaturalTest Pressures In Excess Of 1/2 Psig 3.5 kPa Checking GAS ConnectionsTest Pressures Equal To or Less Than 1/2 Psig 3.5 kPa Installing Back Log Pressure Testing Heater Gas ConnectionsInstalling Crossover Logs What to do if YOU Smell GAS Operating HeaterIgnitor Button Control Knob Lighting InstructionsVariable Control Operation Manual Lighting ProcedureTo Turn OFF GAS To Appliance Ignitor Button Control Knob Burner Primary AIR Holes Inspecting BurnersThermostat Control Operation Pilot Flame PatternODS/PILOT and Burner Cleaning MaintenanceBurner Injector Holder and Pilot AIR Inlet Hole Service Hints Technical ServiceReplacement Parts Observed Problem Possible Cause Remedy TroubleshootingSee Cleaning and Mainte Statement above Gas leak. See WarningFor Masonry and FACTORY- Built Metal Fireplace Optional Positioning Thermostat Sensing BulbStatement on Locating Thermostat Sensing Fireplace Hood SpecificationsAccessories Equipment Shutoff Valve GA5010Parts Central Illustrated Parts Breakdown Variable MANUALLY-CONTROLLED Winchester OAK Models Parts ListIllustrated Parts Breakdown THERMOSTATICALLY-CONTROLLED Royal English OAK Model Keep this Warranty Warranty InformationLimited Warranty VENT-FREE GAS Fireplace

CGS2718PA, CGS2718NA, CGS3124PA, CGS3124NA, SGS3124PA, SGS3124NA, CLD3018PTA, CLD3018NTA, CLD3924PTB, CLD3924NTB, CGS3124PA, CLD3924NTB, CLD3018PTA, CGS2718PA specifications

Desa CGS2718NA, SGS3124NA, CGS2718PA, CLD3018PTA, and CLD3924NTB are part of the prestigious lineup from Desa, renowned for their high-quality heating solutions. These models combine modern design with advanced technologies, ensuring efficient heating for various residential applications.

The CGS2718NA and CGS2718PA stand out for their compact size and versatile functionality. Both feature a stylish design that seamlessly blends with various home decors. Equipped with advanced infrared heating technology, these models deliver efficient warmth without the need for extensive ventilation. They are ideal for supplemental heating in rooms, offering quick warmth to specific areas while maintaining energy efficiency.

Next in line is the SGS3124NA, a model that takes comfort to the next level with its robust heating capacity. This unit is engineered with durable construction and user-friendly controls, allowing homeowners to easily adjust the temperature according to their preferences. Its ceramic heating elements provide an even heat distribution, ensuring that every corner of the room is warmed efficiently. This model is particularly suited for larger spaces, making it a popular choice for living rooms or open-concept areas.

The CLD3018PTA offers a unique combination of aesthetics and functionality. With various finishes and designs, it can seamlessly enhance the ambience of any space. The unit employs innovative thermal technology that helps reduce energy consumption while maximizing heat output. Integrated safety features, including overheat protection and an automatic shut-off function, provide peace of mind for families.

Lastly, the CLD3924NTB is designed for those seeking a high-performance heating solution. This model boasts an impressive heating capacity suitable for larger areas, making it perfect for homes with high ceilings or expansive layouts. The advanced control panel allows for precise temperature settings, and its quiet operation ensures that comfort is maintained without disruption.

Overall, these Desa models—CGS2718NA, SGS3124NA, CGS2718PA, CLD3018PTA, and CLD3924NTB—serve as an excellent investment for homeowners looking to enhance their comfort and efficiency. With a range of features, innovative technologies, and stylish designs, they cater to diverse heating needs, ensuring warmth and satisfaction in every home.