Desa VGC18NR/PR Checking GAS Connections, Test Pressures Equal To or Less Than 1/2 Psig 3.5 kPa

Page 15

Installation

Continued

We recommend that you install a sediment trap in supply line as shown in Figure 14. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.

CAUTION: Avoid damage to gas control. Hold gas control with wrench when connecting it to gas piping and/or fittings.

CHECKING GAS CONNECTIONS

WARNING:Testallgaspiping and connections, internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detec-

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air.

4.Check all joints of gas supply piping system. Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Reconnect heater and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than 1/2

PSIG (3.5 kPa)

1. Close equipment shutoff valve (see Figure 15).

2. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air.

3. Check all joints from gas meter to equipment shutoff valve for natural gas or propane/LP supply to equipment shutoff valve for pro- pane/LP (see Figure 16 or Figure 17, page 16). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

4. Correct all leaks at once.

tion fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Equipment

Shutoff

Valve

Open

CAUTION: Make sure exter- nal regulator has been installed between propane/LP supply and heater. See guidelines un-

Closed

Figure 15 - Equipment Shutoff Valve

der Connecting to Gas Supply, page 13.

Pressure Testing Gas Supply

Piping System

Test Pressures In Excess Of 1/2 PSIG

(3.5 kPa)

1. Disconnect appliance with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage heater regulator.

Propane/LP Supply Tank

Equipment

Shutoff Valve

Thermostat Gas

Valve or Control

Valve Location

Figure 16 - Checking Gas Joints

(Propane/LP Only)

119162-01A

www.desatech.com

15

Image 15
Contents Remote-Ready Models VGC18NR/PR VGC24NR/PR and VGC30NR/PR Patent PendingAlso Design-Certified As Vented Decorative Appliances Safety Information Table of ContentsSafety Information Safety Information Unpacking Product FeaturesProduct Identification Local CodesAir For Combustion Ventilation Providing Adequate VentilationDetermining FRESH-AIR Flow for Heater Location Ventilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors InstallationMinimum Firebox Size Installation and ClearancesCheck GAS Type For Vent-Free OperationMaterial Requirements for Distance a Safe Installation Determining Minimum Mantel Clearance When Using a HoodMantel Clearances Log Set Floor ClearancesChimney Minimum Permanent Installing Damper Clamp Accessory for Vented OperationInstalling Heater Base Assembly Area of Various Standard Round Flues DiameterInstallation Items Needed Connecting to GAS SupplyNatural Dealer. See Accessories,Test Pressures Equal To or Less Than 1/2 Psig 3.5 kPa Checking GAS ConnectionsInstalling optional remote accessories Pressure Testing Heater Gas ConnectionsInstalling Remote Receiver Installing LOGS, Embers and Lava Rock Installing SwitchInstalling Log #1 For Your Safety Read Before Lighting Operating HeaterLighting Instructions Control Knob, Ignitor Button AUTO/OFF/ON Switch Remote Operation Manual Lighting ProcedureTo Turn OFF GAS To Appliance Optional Hand-HeldThermostat Series Model HRC200 Front Burner Flame Pattern Wiring DiagramInspecting Burners Pilot Flame PatternMain burner Cleaning MaintenanceBurner Injector Holder Pilot Air Inlet Hole LogsObserved Problem Possible Cause Remedy TroubleshootingMaintenance, Slight smoke or odor during See Checking Gas Connec Gas leak. See WarningReplacement Parts SpecificationsService Hints Technical ServiceIllustrated Parts Breakdown Remote-Ready Variable Control ModelsVGC18NR, VGC18PR, VGC24NR, VGC24PR, VGC30NR, VGC30PR Parts List Illustrated Parts Breakdown and Parts List Accessories Fire Crackle CF6-A Cleaning KIT GCKLava Rock GA6060 Information video119162-01A Warranty Information Keep this WarrantyLimited Warranty VENT-FREE GAS LOG Heaters