SS38 Direct Vent Gas Stove | clearances |
Clearances to combustibles
| The dimensions shown in Figures 4 and 5 are minimum clearances to maintain | |
| in installing this heater. Left and right clearances are determined when facing the | |
WARNING | front of the heater. | |
Follow these instructions carefully to ensure safe installation. Failure to follow | ||
| ||
| instructions exactly can create a fire hazard. | |
| The appliance cannot be installed on a carpet, tile or other combustible material | |
| other than wood flooring. If installed on carpet or vinyl flooring, the appliance | |
| shall be installed on a metal, wood or noncombustible material panel extending | |
| full width and depth of the appliance. | |
|
|
Maintain the following minimum clearances for service and maintenance.
•Stove must be at least 6" from the back wall. Figure 4
•Stove must be at least 9" from either side wall. See Figure 4
•Stove must be at least 6" from the corner. Figure 4
•No clearance is necessary to the floor. Stove may sit on the floor. Figure 5
•The minimum ceiling height from the floor must be 72".
| Back Wall |
|
|
| |
| 6" Min. |
|
|
| |
Wall | Minimum |
|
|
| |
Side |
|
|
| ||
| 9" |
|
|
| |
| to Either |
|
|
| |
| Side Wall | 6" Minimum |
|
| |
|
| Clearance to |
|
| |
Figure 4 - | Corner |
| 0" | ||
|
| ||||
Clearances to Side, Back and Adjacent Walls | Figure 5 - | ||||
|
Clearance to Floor