SS38 Direct Vent Gas Stove | VENTING INSTALLATION INFORMATION |
termination clearances for buildings with combustible and noncombustible exteriors
G G=6" (152mm)
V
Inside Corner
G
V
G = Combustible 24"(610mm) Noncombustible 18"(457mm)
V
F F=6" (152mm)
Outside Corner
H |
V |
J |
Combustible & |
Noncombustible |
H = 24" (610mm) |
J = 20" (508mm) |
| D |
C | C |
|
V
E
C = Maximum depth of 48" (1219mm) for alcove location
D = Minimum width for back wall of alcove location Combustible - 38" (965mm) Noncombustible - 24" (610mm)
E = Clearance from corner in alcove location
Combustible - 6" (152mm) Noncombustible - 2" (51mm)
Balcony with No Side Wall
Balcony with Perpendicular
Side Wall
Alcove Location
FP1951
| 40 |
|
|
|
|
|
|
|
|
|
| 38 |
|
|
|
|
|
|
|
|
|
| 36 |
|
|
|
|
|
|
|
|
|
Max. | 34 |
|
|
|
|
|
|
|
|
|
32 |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
m) | 30 |
|
|
|
|
|
|
|
|
|
28 |
|
|
|
|
|
|
|
|
| |
(12.2 |
|
|
|
|
|
|
|
|
| |
26 |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
40' | 24 |
|
|
|
|
|
|
|
|
|
22 |
|
|
|
|
|
|
|
|
| |
Height |
|
|
|
|
|
|
|
|
| |
20 |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
| 18 |
|
|
|
|
|
|
|
|
|
Vertical | 16 |
|
|
|
|
|
|
|
|
|
14 |
|
|
|
|
|
|
|
| NOTE: Any vent | |
| 12 |
|
|
|
|
|
|
|
| configuration within |
| 10 |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| the shaded areas is | |
| 8 |
|
|
|
|
|
|
|
| acceptable. |
| 6 |
|
|
|
|
|
|
|
|
|
47.5" | 4 |
|
|
|
|
|
|
|
|
|
(121cm) 2 |
|
|
|
|
|
|
|
|
| |
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 11 12 13 14 15 16 17 18 19 20 |
Figure 7 - | Horizontal run 20' (6 m) Max. |
| |
Allowable Venting Chart | ST1102 |
|
12 | 46D0232 |