Napoleon Fireplaces GVF40N, GVF40P manual SEE-THROUGH Installation Procedure, Framing Facing

Page 11

11

SEE-THROUGH INSTALLATION PROCEDURE

FRAMING

 

FACING

 

 

 

Note: In order to avoid the possibility of exposed insula- tion or vapour barrier coming in contact with the fireplace body, it is recommended that the walls of the fireplace enclosure be “finished” (ie: drywall/sheetrock), as you would finish any other outside wall of a home. This will ensure that clearance to combustibles is maintained within the cavity.

It is best to frame your fireplace after it is positioned and the vent system is installed. Use 2x4's and frame to local building codes. FIGURE 15.

See PAGE 8 for bar type / countertop installation.

FIGURE 15

Combustible materials may be installed flush with the front of the fireplace but must not cover any of the black face- areas of the fireplace. Non-combustible material (brick, stone or ceramic tile) may protrude in these areas.

It is not necessary to install a hearth extension with this fireplace system.

When roughing in the fireplace, raise the fireplace to ac- commodate for the thickness of the finished floor materi- als, i.e. tile, carpeting, hard wood, which if not planned for will interfere with the opening of the lower access door and the installation of many decorative flashing accesso- ries.

Objects placed in front of the fireplace should be kept a minimum of 48" away from the glass front faces of the fireplace.

FINISHING

Refer to pages 13-15 for complete instructions regarding mantle requirements and installations, log placement, glass door and upper and lower louvre attachments.

FIGURE 17

A

DRYWALL

DRYWALL

A = 22" minus finishing material thickness, each side.

BRICK PANEL INSTALLATION

Install the base panels as illustrated in steps 1-4 on page

9.Both side panels sit under the bracket tab. Holding the side panel in position, bend down the tab to secure. [DE-

TAIL 6].

FIGURES 16 a-c

4" MIN

RETAINER

STEP 5

RETAINER

DETAIL 5 & 6

STEP 6

W415-0319 / D / 08.03.05

Image 11
Contents Unvented Millivolt System Table of Contents Napoleon GAS Fireplace Presidents Lifetime Limited Warranty Carbon Monoxide Poisoning MAY Lead to Death General InstructionsGeneral Information Determining Confined or Unconfined Space InstallationCombustion and Ventilation AIR Provisions GAS Installation Sided Framing Peninsula Installation ProcedureCountertop / BAR Installation Finishing Brick Panel InstallationFacing = 25¼ minus finishing material thickness each side OPEN-END Installation ProcedureFraming Facing SEE-THROUGH Installation ProcedureIsland Installation Procedure Finishing LOG PlacementHood Mantle InstallationGlowing Embers Charcoal EmbersHeat Shield STAND-OFF Removal Gvfl InstallationL36 Louvre Installation Logo PlacementDoor Opening and Closing GVF103-KT Patented Catalytic Door InstallationOptions This Blower is not Recommended for the 4 Sided Installation Optional Blower InstallationFor Your Safety Read Before Lighting Operation / MaintenanceVenturi Adjustment MaintenanceCatalytic Tile Maintenance Oxygen Depletion Sensor Pilot CleaningAccessories ReplacementsW415-0319 / D Symptom Problem Test Solution Trouble Shooting GuideDo not Clean Glass When HOT Fireplace Service History