Napoleon Fireplaces GVF40P, GVF40N manual GAS Installation

Page 6

6

ROOM 2

FIGURE 1

ROOM 1

H E I G H T

L E N G T H

Room Volume = Length x Width x Height

Max BTU/hr = Room Volume x 1000 ÷ 50

EXAMPLE 1

In this example, because there is no door to the adjoining room, the volume of the adjoining room may be added to the volume of the room with the heater to get a total unconfined space.

The total unconfined space: 800 + 1200 = 2000 cubic feet.

Maximum BTU/h: 2000 x 1000 = 40,000 BTU/h 50

If there are no more fuel burning appliances within this space then the 30,000 BTU/h input of the fireplace is suit- able to be installed. This also assumes that the construc- tion of this space is not unusually tight.

If for example,

the length of the rooms is 10 feet, the width of Room 1 is 10 feet,

the width of Room 2 is 15 feet

the height of the rooms is 8 feet.

The volume of Room 1: 10 x 10 x 8 = 800 cubic feet.

The volume of Room 2: 10 x 15 x 8 = 1200 cubic feet.

EXAMPLE 2

If in this example a solid door separates Room 1 from Room 2, the volume of Room 2 could not be used. In this case the maximum BTU/h would be:

Maximum BTU/h: 800 x 1000 = 16,000 BTU/h

50

This would be considered a confined space since it can not support the 30,000BTU/h input of the heater and it would be necessary to provide adequate combustion and ventilation air to Room 1.

GAS INSTALLATION

1.Move the fireplace into position and secure to the floor through the ¼"ø holes located at the four outside corners of the base.

2.Install rigid black pipe, 1/2" type-L copper tubing or, if local codes permit, a 3/8" flex connector and shutoff valve to the gas line and the fireplace gas valve. Seal and tighten securely. An adapter fitting is required between the gas valve and the copper tubing or flex connector.

FIGURE 2 DO NOT KINK FLEX CONNECTOR.

WIRE SIZE

MAX. LENGTH

14gauge

100 feet

16gauge

60 feet

18gauge

40 feet

5.Attach the two leads to terminals 1 and 3 located on

the gas valve.

 

1

 

 

 

 

FIGURE 3

2

 

OL

 

 

 

 

N

O

 

 

 

 

F

 

 

 

HI

O

F

 

 

 

 

 

 

 

 

 

 

P

 

 

3

 

 

TOLI

 

 

P

 

 

 

 

 

TOLI

 

 

3.Check for gas leaks by brushing on a soap and water solution.

DO NOT USE OPEN FLAME.

4.For ease of accessibility, an optional remote wall switch or millivolt thermostat may be installed in a con- venient location. Route a 2 strand, solid core millivolt wire through the electrical hole located at the bottom left side of the unit. The recommended maximum lead length de- pends on wire size:

Do not connect either the wall switch, thermostat or gas valve to electricity (110 volts).

6.Mark the appropriate boxes on the rating plate label to indicate the model type.

USING DOOR OPTION:

Purge all gas lines with the glass door of the fireplace opened. Assure that a continuous gas flow is at the burner before closing the door.

W415-0319 / D / 08.03.05

Image 6
Contents Unvented Millivolt System Table of Contents Napoleon GAS Fireplace Presidents Lifetime Limited Warranty General Instructions General InformationCarbon Monoxide Poisoning MAY Lead to Death Installation Combustion and Ventilation AIR ProvisionsDetermining Confined or Unconfined Space GAS Installation Sided Peninsula Installation Procedure Countertop / BAR InstallationFraming Brick Panel Installation FacingFinishing OPEN-END Installation Procedure = 25¼ minus finishing material thickness each sideSEE-THROUGH Installation Procedure Framing FacingIsland Installation Procedure LOG Placement FinishingCharcoal Embers Mantle InstallationGlowing Embers HoodLogo Placement Gvfl InstallationL36 Louvre Installation Heat Shield STAND-OFF RemovalGVF103-KT Patented Catalytic Door Installation OptionsDoor Opening and Closing Optional Blower Installation This Blower is not Recommended for the 4 Sided InstallationOperation / Maintenance For Your Safety Read Before LightingOxygen Depletion Sensor Pilot Cleaning MaintenanceCatalytic Tile Maintenance Venturi AdjustmentReplacements AccessoriesW415-0319 / D Trouble Shooting Guide Symptom Problem Test SolutionDo not Clean Glass When HOT Fireplace Service History