Leak Test:

Mix a 50-50 solution of water and dish soap.

Light appliance- see lighting instructions on page 21 of this manual or on the stove’s rating plate.

Brush or spray all joints and connections with the soapy water solution.

If bubbles appear at any connection or seam or a gas odor is detected immediately turn gas control knob to the OFF position.

Tighten or reconnect the leaking joint and retest for any gas leaks.

Gas Pressure

Correct gas pressure is essential for efficient and safe operation of this appliance. It is important that the correct pressure is established at the time of the installation. Proper gas pressure provides a consis- tent flow of gas to the appliance and is instrumental in checking for gas leaks.

The gas control valve on the stove is equipped with pressure test points for gauge connections. It is possible then to test SUPPLY/INLET pressure and manifold pressure at the appliance.

Testing the available gas pressure should be done by attaching a manometer to the appropriate test point on the valve. The gauge connections are located on the front of the valve under the On/Off/ Pilot- knob. Gauge connections are identified by:

E - for Inlet or supply pressure (the amount of gas coming to the valve.)

A - for Manifold pressure (the amount of gas that is coming out of the valve to the burner.) See fig. 20.

ALWAYS TEST PRESSURES WITH REGULA- TOR CONTROL KNOB SET ON HIGH.

Required Inlet Gas Pressures (in. W.C.)

 

MIN.

MAX.

 

 

 

NATURAL GAS

5.0

7.0

PROPANE

11.0

13.5

 

 

 

The appliance and its main gas valve must be disconnected from the gas supply piping system during any pressure testing on that system at test pressures in excess of 1/2 psig (3.5kPa).

The appliance must be isolated from the gas

supply line by closing its individual manual gas shut- off valve (gas cock) during any pressure testing of the gas supply piping system that is equal to or exceeds pressures of 1/2 psig (3.5kPa).

Required Manifold Pressure (in. W.C.)

 

MIN.

MAX.

 

 

 

NATURAL GAS

2.2

3.5

 

 

 

PROPANE

5.5

10.0

 

 

 

EA

Figure 20. Supply and Manifold pressure test points.

18

Image 18
Contents GF 200 DV Lillehammer Gas Heater Welcome to Jøtul Table of Contents GF 200 DV Lillehammer Options Input RatesGeneral Information Glass PanelHearth Requirements Safety InformationLocating the Stove MinimumClearance to Combustibles Venting Requirements Install the Exhaust Restrictor PlateInstall the Air Inlet Restrictor Plate Vent RestrictionVertical Venting Requirements Simpson Dura-Vent Ceiling Firestop #943 is requiredMinimum Vertical Rise =1 ft For a Co-linear Hearthmount Installation These guidelines must be followedMasonry or Prefabricated Chimney Conversion Not Vent TWO Appliances Into a Single ChimneyHorizontal Venting Horizontal Termination Wall Shield Installation Horizontal vent with two elbowsVent Termination Requirements Vent Terminal Clearances National Fuel Gas CodeGas Conversion Mobile Home InstallationFuel Conversion Kit Contents Canadian RequirementsGas Conversion Procedure Air Shutter adjustment and Burner OrificeRegulator Assembly Connect the Gas SupplyRequired Inlet Gas Pressures in. W.C Gas PressureLeak Test Required Manifold Pressure in. W.CRequirements High Altitude AdjustmentDerating Procedure Canadian RequirementsInstall the Log Set Air Shutter Settings See FigureRemote Control Checking the SystemOperation of Appliance Correct flame pictureMaintenance Glass and Gasket ReplacementGlass Front Maintenance Record ModelIllustrated Parts List GF 200 DV LillehammerPainted & Enamelled Cast Iron Parts Matte Black Blue Black Ivory Forest GreenAccess the lower controls Normal serviceToOFF. Do not force Jøtul ASA Jøtul North America