Jotul GF 200 DV manual Connect the Gas Supply, Regulator Assembly

Page 17

from the front of the valve Regulator. See fig. 18.

13.Remove the regulator tower and the gasket.

14.Install the new variable regulator parts, confiming that the gasket is properly positioned. Replace the regulator cover and tighten the three screws securely.

15.Apply the identification labels to locations as follows:

Label A - apply to back of stove.

Label B - apply to stove’s rating plate.

Small Conversion Label - apply to valve.

16.Reassemble the stove. Connect supply gas to the system and check for leaks using a soapy water solution.

WHEN RE-INSTALLING THE BURNER TUBE, BE SURE THAT THE TUBE IS PULLED FORWARD IN THE MOUNTING HOLES AND SECURED WITH THE TWO 1/ 4” SCREWS.

Mounting

 

Regulator Tower

 

Screws

 

 

Gasket

Regulator

Conversion

Label

Figure 18. Regulator Assembly.

Connect the Gas Supply

The gas supply line connection is made to the valve just inside the left rear leg. The gas supply line should be 3/8" npt with a 1/2" diameter supply, or the appropriate size to provide sufficient gas pres- sure to the valve regardless of the input setting.

The use of Flexible Gas Appliance Connectors is acceptable in many areas in the U.S. However, Canadian methods vary depending on local code.

ALL INSTALLATIONS MUST COMPLY WITH LOCAL CODE OR IN THE ABSENCE OF LOCAL CODE, MUST COMPLY WITH THE MOST RECENT EDITION OF THE NATIONAL FUEL GAS CODE ANSI Z223.1/NFPA 54 OR CAN-B149.

All codes require a gas shut-off valve (gas cock) and union, to be installed in the supply line, and in the same room as the appliance. This allows for the disconnection of the stove for servicing and mainte- nance. See Figure 19.

T-HANDLE GAS COCKS ARE REQUIRED IN MASSA- CHUSETTS IN COMPLIANCE WITH CODE 248CMR.

Secure all joints tightly using appropriate tools and sealing compounds. For propane units be sure to use compounds that are propane resistant.Turn on gas supply and test for gas leaks using a soapy water solution.

NEVER USE AN OPEN FLAME TO

CHECK FOR GAS LEAKS.

ALWAYS REFER TO THE LIGHTING

INSTRUCTIONS ON THE BACK COVER

OF THIS MANUAL WHEN LIGHTING Figure 19. Supply Line Shut-off Valve Configurations.

YOUR LILLEHAMMER.

17

Image 17
Contents GF 200 DV Lillehammer Gas Heater Welcome to Jøtul Table of Contents Input Rates GF 200 DV Lillehammer OptionsGlass Panel General InformationLocating the Stove Safety InformationHearth Requirements MinimumClearance to Combustibles Install the Air Inlet Restrictor Plate Install the Exhaust Restrictor PlateVenting Requirements Vent RestrictionMinimum Vertical Rise =1 ft For a Vertical Venting RequirementsSimpson Dura-Vent Ceiling Firestop #943 is required These guidelines must be followed Co-linear Hearthmount InstallationNot Vent TWO Appliances Into a Single Chimney Masonry or Prefabricated Chimney ConversionHorizontal Venting Horizontal Termination Horizontal vent with two elbows Wall Shield InstallationVent Terminal Clearances National Fuel Gas Code Vent Termination RequirementsFuel Conversion Kit Contents Mobile Home InstallationGas Conversion Canadian RequirementsAir Shutter adjustment and Burner Orifice Gas Conversion ProcedureConnect the Gas Supply Regulator AssemblyLeak Test Gas PressureRequired Inlet Gas Pressures in. W.C Required Manifold Pressure in. W.CDerating Procedure High Altitude AdjustmentRequirements Canadian RequirementsAir Shutter Settings See Figure Install the Log SetChecking the System Remote ControlCorrect flame picture Operation of ApplianceGlass Front MaintenanceGlass and Gasket Replacement Model Maintenance RecordGF 200 DV Lillehammer Illustrated Parts ListMatte Black Blue Black Ivory Forest Green Painted & Enamelled Cast Iron PartsToOFF. Do not force Access the lower controlsNormal service Jøtul North America Jøtul ASA