Jotul GF 200 DV manual Co-linear Hearthmount Installation, These guidelines must be followed

Page 10

Co-linear Hearthmount Installation

The Jøtul GF 200 DV Lillehammer may be vented through a masonry fireplace using Simpson Dura- Vent Chimney Liner Conversion Kit 923GK. When installed in the manner described below, this system can improve the performance of the appliance in cold climate situations, as well as simplify the vent installation.

These guidelines must be followed:

Exhaust Gases

#923GK

Maximum Co- Top Kit Linear Height

- 35 FT

#991

High

Wind Cap

Intake Air

1.

Prior to the installation, the chimney flue must be

 

thoroughly cleaned and inspected by a qualified

 

chimney service person.

2.

In a masonry chimney, a fireclay liner or listed

 

steel liner, must be present the entire length of

 

the chimney.

3.

No appliance can be installed into a chimney flue

 

serving any other appliance of any kind.

4.

The minimum length of the AIR INTAKE FLEX is 6

Minimum Co-

Linear Height

-10 FT

feet- measured off of the back of the appliance

and IT MUST EXTEND PAST THE DAMPER AREA OF

THE FIREPLACE.

5. If the intake flex does not extend the full length

of the chimney and connect to both the unit and

the termination cap, A METAL BLOCK OFF PLATE

MUST BE CONSTRUCTED AND INSTALLED ABOVE

THE UNIT PRIOR TO THE END OF THE INTAKE FLEX

AND MUST COMPLETELY SEAL THE CHIMNEY FLUE

FROM THE ROOM.

Consult with the local code authority having jurisdiction before proceeding with this type of installation.

Refer to the vent manufacturer’s instructions for specific installation requirements.

Air Intake flex pipe must extend a minimum of 6 ft. and through the damper area.

Chimney must be sealed off from the room by a steel plate at the damper area.

Dual 3” Flex Liners

WARNING: FAILURE TO POSITION THE PARTS AND STOVE IN ACCORDANCE WITH THESE DIAGRAMS OR FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED FOR USE WITH THIS APPLIANCE MAY RESULT IN PROPERTY DAMAGE OR PERSONAL INJURY. BE SURE TO MAINTAIN THE PROPER CLEARANCES TO COMBUSTIBLES AS DEFINED IN THIS MANUAL AND INM THE INSTRUCTIONS PROVIDED WITH EACH VENT

COMPONENT.

IMPORTANT NOTICE

THE USE OF AN EXISTING CHIMNEY AS AN AIR INTAKE IS NOT COVERED UNDER THE ANSI Z21.88-1999-CSA 2.33-M99

TEST METHODS AND RESULTING ITS/WHI PRODUCT CERTIFICATION. THE CODE AUTHORITY HAVING JURISDICTION MUST BE CONSULTED PRIOR TO PRO- CEEDING WITH THIS INSTALLATION

#923GCL Co- Linear Appliance Adaptor

Figure 8. Co-Linear Vent System installed in a masonry fireplace.

21 1/2”

(546mm)

18”

(457 mm)

Figure 9. Co-Linear Adaptor dimensions with Plinth legs.

10

Image 10
Contents GF 200 DV Lillehammer Gas Heater Welcome to Jøtul Table of Contents GF 200 DV Lillehammer Options Input RatesGeneral Information Glass PanelHearth Requirements Safety InformationLocating the Stove MinimumClearance to Combustibles Venting Requirements Install the Exhaust Restrictor PlateInstall the Air Inlet Restrictor Plate Vent RestrictionSimpson Dura-Vent Ceiling Firestop #943 is required Vertical Venting RequirementsMinimum Vertical Rise =1 ft For a Co-linear Hearthmount Installation These guidelines must be followedMasonry or Prefabricated Chimney Conversion Not Vent TWO Appliances Into a Single ChimneyHorizontal Venting Horizontal Termination Wall Shield Installation Horizontal vent with two elbowsVent Termination Requirements Vent Terminal Clearances National Fuel Gas CodeGas Conversion Mobile Home InstallationFuel Conversion Kit Contents Canadian RequirementsGas Conversion Procedure Air Shutter adjustment and Burner OrificeRegulator Assembly Connect the Gas SupplyRequired Inlet Gas Pressures in. W.C Gas PressureLeak Test Required Manifold Pressure in. W.CRequirements High Altitude AdjustmentDerating Procedure Canadian RequirementsInstall the Log Set Air Shutter Settings See FigureRemote Control Checking the SystemOperation of Appliance Correct flame pictureGlass and Gasket Replacement MaintenanceGlass Front Maintenance Record ModelIllustrated Parts List GF 200 DV LillehammerPainted & Enamelled Cast Iron Parts Matte Black Blue Black Ivory Forest GreenNormal service Access the lower controlsToOFF. Do not force Jøtul ASA Jøtul North America