Lodge Manufacturing GMD1-80N manual Inspecting the Venting System, GASKETS/SEALING Materials

Page 40

All installations and services must be performed by qualified service personnel.

D. INSPECTING THE VENTING SYSTEM

The venting system should be inspected during the annual maintenance check-up or during each subsequent service call.

Check all vent pipes for restrictions due to soot, or carbon build-up, as well as foreign matter, or any materials, that cause the venting system to restrict the proper venting of combustion products. If a restriction is found, the flue vent must be cleaned or replaced to ensure proper venting.

Vent pipes should also be inspected for any signs of corrosion, deterioration, or leakage that may cause combustion by-products to infiltrate the home or indoor environment.

If signs of corrosion, deterioration, or leakage are evident, the vent pipe must be replaced with a properly sized, agency-approved, vent pipe.

E. GASKETS/SEALING MATERIALS

Inspect all visible gaskets for signs of degradation, especially any seals which were removed as part of the inspection. Replace any suspect gaskets.

F. HEAT EXCHANGER

Inspect for corrosion, pitting, warpage, deterioration, carbon build-up, and loose gaskets in the flue pipe, burner box, and accessible areas of the heat exchanger.

G. HOUSE AIR BLOWER

Check and clean the blower wheel, housing, and compartment with a vacuum. Check the motor nameplate and follow the motor manufacturers instructions for lubrication, if required.

IMPORTANT: Some motors are permanently lubricated and should not be oiled. See motor nameplate for specific instructions.

H. EXTENDED SHUTDOWN

If this furnace is shut down or off for an extended period of time, several steps can be taken to help insure a smooth and reliable start.

ON SHUT DOWN:

1.Close the gas supply shutoff valve(s).

2.Turn the furnace power switch “off” and disconnect electrical power to the unit.

39

Image 40
Contents GAS-FIRED Furnace Safety Section Page Page Page Table of Contents Section Beginning Page Models GMD1-80N III. Furnace Specifications Model GMD1-80Blower Data Standard Chimney IV. Installation Roof JackFurnace Location Page Base Installation Page Alcove Installation Closet Installation ? Warning Hazard Combustion AIR Page GAS Piping Electrical Wiring AWG Contents Quantity NAT. to Propane ConversionManifold Removal and Orifice Change Page Initial Start UP Adjustment of Heat Input RateOperating Instructions GAS Pressure Chart for ALL GMD1-80 Model Furnaces Burner Adjustment Setting Temperature Rise Furnace Checkout ProcedurePage Installers Instructions to User VI. Starting the Unit Refer to the Troubleshooting Section of this Manual Page Diagnostic Features Power must be disconnected before servicingTurn Tstat Setting Above Room Temp Yes After GAS Valve OPENS, do the Burners IGNITE? Check ALL VIII. Dealer Maintenance Inducer Blower AssemblyElectrical BurnersInspecting the Venting System GASKETS/SEALING MaterialsHeat Exchanger House AIR BlowerOn START-UP IX. User Information Section Component Locations Inspection AreasFilter Location and Cleaning Appendix A. Replacement Parts List Page Appendix B Wiring Diagram