Lodge Manufacturing GMD1-80N manual Check ALL

Page 38

All installations and services must be performed by qualified service personnel.

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CHECK ALL

 

 

 

IS LED LIGHT

 

 

 

 

 

 

 

DOES SYSTEM RUN UNTIL

No

No

WIRING FOR

ON INTEGRATED

THERMOSTAT IS SATISFIED?

 

 

 

LOOSE

 

CONTROL FLASHING?

 

 

 

 

 

 

 

CONNECTIONS

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CHECK FOR SHORT IN

DOES BURNER SHUT OFF

 

No

WIRE TO THERMOSTAT

WHEN THERMOSTAT IS

 

AND CORRECT IF

SATISFIED?

 

 

NECESSARY.

 

 

 

 

 

 

IF LED FLASHES:

 

Yes

1 FLASH, THEN PAUSE SYSTEM LOCKOUT

 

 

2 FLASHES, THEN PAUSE

PRESSURE SWITCH STUCK CLOSED

 

3 FLASHES, THEN PAUSE

PRESSURE SWITCH STUCK OPEN

 

4 FLASHES, THEN PAUSE

OPEN LIMIT SWITCH OR ROLLOUT SWITCH

 

 

 

DOES THE CIRCULATING

6 FLASHES, THEN PAUSE

115 VOLT AC POWER REVERSED

AIR BLOWER TURN OFF

 

 

AFTER THERMOSTAT IS

7 FLASHES, THEN PAUSE

LOW FLAME SENSE SIGNAL

SATISFIED WITHIN

 

 

120 SECONDS?

8 FLASHES, THEN PAUSE

CHECK IGNITOR OR IMPROPER GROUNDING

 

CONTINUOUS FLASHING

FLAME HAS BEEN SENSED WHEN NO FLAME

 

(NO PAUSE)

SHOULD BE PRESENT (NO CALL FOR HEAT)

 

THE LED WILL ALSO FLASH ONCE AT POWER-UP.

Yes

CHECK COMPLETE SYSTEM OUT.

 

 

 

LED LIGHT STAYS ON CONTINUOUSLY,

 

COMPLETE FAILURE - REPLACE INTEGRATED CONTROL.

TROUBLESHOOTING COMPLETE.

 

 

37

Image 38
Contents GAS-FIRED Furnace Safety Section Page Page Page Table of Contents Section Beginning Page Models GMD1-80N III. Furnace Specifications Model GMD1-80Blower Data Furnace Location IV. Installation Roof JackStandard Chimney Page Base Installation Page Alcove Installation Closet Installation ? Warning Hazard Combustion AIR Page GAS Piping Electrical Wiring AWG Contents Quantity NAT. to Propane ConversionManifold Removal and Orifice Change Page Operating Instructions Adjustment of Heat Input RateInitial Start UP GAS Pressure Chart for ALL GMD1-80 Model Furnaces Burner Adjustment Setting Temperature Rise Furnace Checkout ProcedurePage Installers Instructions to User VI. Starting the Unit Refer to the Troubleshooting Section of this Manual Page Diagnostic Features Power must be disconnected before servicing Turn Tstat Setting Above Room Temp Yes After GAS Valve OPENS, do the Burners IGNITE? Check ALL Electrical VIII. Dealer MaintenanceInducer Blower Assembly BurnersHeat Exchanger Inspecting the Venting SystemGASKETS/SEALING Materials House AIR BlowerOn START-UP IX. User Information Section Component Locations Inspection AreasFilter Location and Cleaning Appendix A. Replacement Parts List Page Appendix B Wiring Diagram