Page 19

All installations and services must be performed by qualified service personnel.

H. GAS PIPING

: Because of the potential of the odorant to fade, a gas leak may not be detected by smell. If this furnace is installed below grade, contact your gas supplier for a gas detector.

: With the gas piping pressurized, all gas piping connections must be leak tested using a strong soap and water solution. Any leaks must be repaired immediately after turning off the gas supply. A final test for gas leakage must be made after purging the gas line.

: DO NOT wet electronic components during the leak test. Wetting electronic components may damage circuitry and cause a hazardous situation. Dry moisture from all leads and terminals if wetting occurs. Wait at least 24 hours for the circuit to fully dry before energizing the system.

: The furnace and its gas valve must be disconnected from the gas supply during pressure testing of the gas supply system at pressures in excess of 1/2 PSIG (13.9 inches W.G.). The furnace can be isolated from the gas supply by closing the manual gas shutoff valve serving the appliance at test pressures equal to, or less than, 1/2 PSIG or (13.9 inches W.G.).

: Copper and brass tubing and fittings (except tin lined) shall not be used if the gas contains more than a trace (0.3 grains per 100 cubic ft.) of hydrogen sulfide gas. Check with your gas supplier.

Sizing and installation of fuel lines must be in accordance with federal, state, and local regulations.

A qualified installer or service person must install all gas piping and perform all required testing.

Piping from the natural gas meter to the furnace shall be in accordance with requirements of the local gas utility. Piping from the propane tank to the furnace must follow the recommendations of the gas supplier. In the absence of local codes governing gas piping selection and installation, follow the National Fuel Gas Code, ANSI Z223.1 / NFPA 54-1999, or latest edition.

A readily accessible, manual gas shutoff valve (design-certified for the applicable gas) with a non-displaceable rotor member shall be installed within six (6) feet of the furnace.

A pipe union, or flanged connection, shall be provided directly up stream of the burner to allow burner removal. Unions must be of a ground joint type or flange-jointed type using a gasket resistant to the corrosive effects of LP gases. Pipe dope or sealant

18

Image 19
Contents GAS-FIRED Furnace Safety Section Page Page Page Table of Contents Section Beginning Page Models GMD1-80N GMD1-80 III. Furnace Specifications ModelBlower Data Standard Chimney IV. Installation Roof JackFurnace Location Page Base Installation Page Alcove Installation Closet Installation ? Warning Hazard Combustion AIR Page GAS Piping Electrical Wiring AWG Propane Conversion Contents Quantity NAT. toManifold Removal and Orifice Change Page Initial Start UP Adjustment of Heat Input RateOperating Instructions GAS Pressure Chart for ALL GMD1-80 Model Furnaces Burner Adjustment Furnace Checkout Procedure Setting Temperature RisePage Installers Instructions to User VI. Starting the Unit Refer to the Troubleshooting Section of this Manual Page Power must be disconnected before servicing Diagnostic FeaturesTurn Tstat Setting Above Room Temp Yes After GAS Valve OPENS, do the Burners IGNITE? Check ALL Burners VIII. Dealer MaintenanceInducer Blower Assembly ElectricalHouse AIR Blower Inspecting the Venting SystemGASKETS/SEALING Materials Heat ExchangerOn START-UP IX. User Information Section Inspection Areas Component LocationsFilter Location and Cleaning Appendix A. Replacement Parts List Page Appendix B Wiring Diagram