FUEL TANKS AND FUEL LINES

Installation

FUEL TANKS AND FUEL LINES

Fuel tanks and fuel lines must be installed in accordance with requirements of NFPA 31.

If fuel lines are under 30 feet in length, it is satisfactory to use 3/8" O.D. copper tube. Never use tube smaller than 3/8" O.D. If the lines are over 30 feet in length, we recommend 1/2" O.D. tube. Use good flare connections on the fuel lines and, whenever possible, avoid splicing the tube. Never make a splice or joint underground. Whenever possible, avoid overhead lines; avoid kinks and traps in the lines. Do not fasten fuel lines directly

to floor joists, sills, or girders. Whenever possible, support fuel lines with sound-absorbing devices.

SINGLE LINE SYSTEM

 

When fuel does not have to be lifted from tank to

 

burner use a single line hookup. A single line system

FIG. 18

can be used when outlet on fuel tank is higher than

inlet on burner.

 

TWO LINE SYSTEM
FUEL LINE

 

To lift fuel from tank to burner use a two-line system.

 

On outside buried tanks, install a supply line from tank

 

to burner and return line from burner back to tank. The

 

supply line is called the suction line. The suction line

 

should extend down within a few inches of the bottom

 

of fuel tank.

 

OIL FILTER

 

A fuel filter should be used with either an outside or

 

inside fuel tank. In all cases install the filter in

 

accordance with local codes. The filter should always

 

be installed inside, near the furnace. An inside tank and

 

any internal or external fire or flame appliance being

 

served by the tank must be at least 5 feet away from

 

the furnace. New oil replacement cartridges should be

 

installed annually or as required. Always use the new

 

gasket that is supplied with the replacement cartridge.

 

Tighten the top of the filter carefully and check the

 

gasket for proper fit.

 

FILL AND VENT PIPES

 

Fuel tanks must be equipped with a fill pipe and a vent

 

pipe. Fill pipes should be terminated in a convenient place

 

for filling. They should be equipped with a watertight cap.

 

It is recommended that 1-1/4" pipe be used for the vent.

 

The vent should extend outdoors served by the tank and

 

Questions? Visit www.yukon-eagle.com or call 1-800-358-0060

20

Image 20
Contents POLAR/EAGLE Oil/Wood - Gas/WoodWarm Air Central Heating Furnaces LWO-112Oil Fired LWG-112Gas FiredFOR YOUR SAFETY For repair or replacement partsDANGER or call 1-800-358-0060TABLE OF CONTENTS PLAN YOUR INSTALLATIONINSTALLATION MAINTENANCESafety Statements STOP FOR SAFETYREAD THROUGH THE ENTIRE MANUAL extra safety precautions should be takenUnpack and Check Your Cartons INSPECT SHIPMENTPACKING LIST FIG.Furnace Features - Eagle I - Husky vMORE HEAT EXCHANGE SURFACEMEANS LESS HEAT UP THE CHIMNEY xTHE OIL OR GAS BURNER FIRES INTOFurnace Features - Eagle I - Husky yv x~ w z u | zFIRE BRICK LINING EXTENDS Furnace Features - Eagle II - PolaruYUKONTROL SOLID-STATE w|z u Furnace Features - Eagle II - PolarSpecifications MODEL LWO-112OilInput rating 1.0 G.P.H. - 80 HPlan Your Installation Unit DimensionsPLAN YOUR INSTALLATION RULES FOR SAFE INSTALLATION AND OPERATIONBE SURE TO INSTALL DUCT WORK CLEARANCES TO COMBUSTIBLESWITH CLEARANCES SHOWN Plan Your InstallationTYPICAL INSTALLATION Plan Your InstallationBE INSTALLED WITH A METAL CONDENSATE PAN EVENT OF ELECTRIC POWER OR FURNACE FAN FAILUREInstallation DRAFT TUBE INSTALLATIONPLACE FURNACE SECONDARY AIR INTAKE COVERCUT AWAY VIEW BURNER COMBUSTION CHAMBER InstallationOIL BURNER INSTALLATION Install burner as followsInstallation Draft Tube AssemblyDRAFT DAMPER CONTROLSMOKE BAFFLES InstallationFIG. 14-A FIG. 14-B Fan Limit Control InstallationINSTALLING THE HONEYWELL FAN/LIMIT CONTROL Installation TYPICAL THERMOSTAT SETTINGSMOUNTING THE THERMOSTATS FIG.Installation FIG.FUEL TANKS AND FUEL LINES SINGLE LINE SYSTEMInstallation GAS PIPE SIZINGGAS PIPING FIG.Installation Field Controls Model WMO-1Safety SwitchFUME SENSOR GAS MODELS ONLY FIG.Installation ELECTRIC WIRINGWIRING THE FURNACE DS-103DAMPER CONTROLOIL OR GAS AND WOOD HEATING WITH AIR CONDITIONING 24 Volt Field WiringOIL OR GAS AND WOOD HEATING ONLY Installation CONNECTING SMOKE PIPEFIG. LESSER CLEARANCES TO COMBUSTIBLEACCURATELY ADJUST FLUE DRAFT A MANOMETER MUST BE USED TOInstallation MAKE THESE ADJUSTMENTS WHEN INSTALLINGCHOOSING A CHIMNEY InstallationPROPER CHIMNEYS Installation Installation COMBUSTION AIRFIG. FIG. FIGInstallation BTU Per Hour InputTo start the oil burner on a new installation Operating InstructionsOIL FIRING THE UNIT STARTING BURNER AFTER IGNITION FAILUREGas Firing the Unit To Start the Gas burner on new installationOperating Instructions FIG.Operating Instructions BEST WOOD TO BURNBTU’s EquivalentHAND FIRING WOOD Operating InstructionsSTARTING WOOD FIRE WITH GAS OR OIL BURNER HOW TO START A COAL FIRE Operating InstructionsWHAT SIZE COAL SHOULD I BURN? MAINTAINING A COAL FIREON 1/2-INCHOPENING GRATES Optional Operating InstructionsOPERATING INSTRUCTIONS FOR BURNING COAL Wiring Diagrams OIL AND WOOD HEATING ONLYOIL AND WOOD HEATING WITH A/C Wiring DiagramsGAS AND WOOD HEATING ONLY Wiring DiagramsGAS AND WOOD HEATING WITH A/C Wiring DiagramsMaintenance RECOVERING UNBURNED COALGRATE CARE -ASHREMOVAL ASH DISPOSALMaintenance CLEANING FURNACE AND CHIMNEY FLUE PIPESSMOKE PIPE, CHIMNEY AND SECONDARY HEAT EXCHANGER Secondary Heat Exchanger Eagle I - HuskyFIG. FIG. FIG. FIG. MaintenanceFURNACE BLOWER ADJUSTMENT Maintenance DUCT WORK AND BLOWER SPEED ADJUSTMENTFIG. MaintenanceTESTING INSTALLATIONS FOR EFFICIENCY Maintenance TEST PROCEDURE StepStep StepMaintenance FIREBRICK PLACEMENTFIREBRICK PLACEMENT Models LWO-112& LWG-112ONLY Fig. Lower RowMaintenance OIL BURNER MAINTENANCEMAINTENANCE AT THE END OF THE HEATING SEASON MAINTENANCE AT THE START OF THE HEATING SEASONMaintenance HOW TO PREVENT RUST AND CORROSIONDISPOSAL OF ASHES CREOSOTE-FORMATIONAND NEED FOR REMOVALMaintenance SMOKE IN THE FURNACE ROOMChimney causes FIG.Maintenance OVER HEATING WHEN BURNING SOLID FUEL ASYOUR PRIMARY SOURCE OF HEAT GAS OR OIL PART OF FURNACE TOO LARGE FOR THE HOMEExploded Views & Parts List EAGLE I - HUSKY MODELS LWO-112& LWG-112Exploded Views & Parts List Left HandRight Hand DescriptionEAGLE II - POLAR MODELS LWO-168& LWG-168 Exploded Views & Parts ListLeft Hand Shown Exploded Views & Parts ListKey No Left HandGUN ASSEMBLY WAYNE MODEL MSR OIL BURNERExploded Views & Parts List BURNER COMPONENTS WAYNE MODEL MSR Exploded Views & Parts ListMSR GUN ASSEMBLY DETAIL Part DescriptionWAYNE MODEL P250AF-DIN GAS BURNER Exploded Views & Parts ListBURNER COMPONENTS WAYNE MODEL P250AF-DIN Exploded Views & Parts ListPart Description Part NumberCIRCULATING FAN PERFORMANCE CURVE CHART CHART IS FOR DETERMINING MOTOR HORSEPOWER NEEDSMODELS LWO-112AND LWG-112 THIS CIRCULATING FAN PERFORMANCE CURVEMODELS LWO-168AND LWG-168 Exploded Views & Parts ListCIRCULATING FAN PERFORMANCE CURVE CHART CHART IS FOR DETERMINING MOTOR HORSEPOWER NEEDSTroubleshooting SERVICE HINTS- OILNotes HOW TO ORDER REPAIR PARTS Assembly Installation Operation Repair PartsYUKONEAGLE OWNERS MANUAL