Bryant 315AAV instruction manual Air Delivery CFM With Filter, Cfm

Page 18

315AAV

Table 5 – Air Delivery - CFM (With Filter)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External

 

 

External Static Pressure (ESP) (IN. W.C.)

 

 

 

 

 

 

 

 

CFM

Static

 

 

 

 

Unit Size

 

Operating Mode

Airflow

Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting

Range*

0.1

0.2

0.3

0.4

 

0.5

0.6

 

0.7

0.8

0.9

1

 

 

 

 

 

 

 

(In. W.C.)

 

 

 

 

 

 

 

 

 

 

 

 

070---

12

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

(CFM)

 

 

 

 

 

††

 

 

 

 

Low Heat

735 (615)†

0---

0.50

735

735

735

735

 

725

 

 

 

 

 

 

 

 

 

 

 

High Heat

1180

0---

1.0

1160

1165

1175

1180

 

1180

1180

 

1180

1180

1180

1175

 

 

 

 

 

(1060)†

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

††

 

 

1---

1/2 Ton Cooling---

525

0---

0.50‡

515

500

500

490

 

485

 

 

 

 

 

 

††

 

 

2---

Ton A/C Cooling

700

0---

0.50‡

690

680

675

680

 

675

 

 

 

 

 

 

 

 

2

--- 1/2

--- Ton A/C Cooling

875

0---

1.0‡

875

875

875

870

 

865

855

 

850

835

825

820

 

 

 

3---

Ton A/C Cooling

1050

0---

1.0‡

1050

1050

1050

1050

 

1050

1050

 

1045

1035

1020

1000

 

 

3

--- 1/2

--- Ton A/C Cooling

1225

0---

1.0

1220

1225

1225

1225

 

1225

1220

 

1205

1190

1185

1170

 

 

 

 

 

Maximum

1400

0---

1.0

1395

1400

1400

1400

 

1395

1385

 

1370

1340

1300

1245

090---

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Heat

985 (825)†

0---

1.0

950

970

985

985

 

985

985

 

985

985

985

980

 

 

 

 

 

High Heat

1210

0---

1.0

1190

1205

1210

1210

 

1210

1210

 

1210

1210

1210

1200

 

 

 

 

 

(1090)†

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

††

 

1

--- 1/2

--- Ton A/C Cooling

525

0---

0.50‡

525

520

525

495

 

475

 

 

 

 

 

 

††

 

 

2---

Ton A/C Cooling

700

0---

0.50‡

680

680

680

675

 

670

 

 

 

 

 

 

 

 

2

--- 1/2

--- Ton A/C Cooling

875

0---

1.0‡

815

845

845

855

 

850

850

 

845

835

820

805

 

 

 

3---

Ton A/C Cooling

1050

0---

1.0‡

1005

1005

1015

1035

 

1040

1040

 

1035

1030

1025

1010

 

 

3

--- 1/2

--- Ton A/C Cooling

1225

0---

1.0

1190

1200

1200

1205

 

1205

1215

 

1205

1200

1185

1170

 

 

 

4---

Ton A/C Cooling

1400

0---

1.0

1350

1370

1390

1390

 

1400

1390

 

1380

1380

1360

1340

 

 

 

 

 

Maximum

1600

0---

1.0

1595

1600

1600

1600

 

1595

1555

 

1505

1465

1430

1390

110--- 20***

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Heat

1320

0---

1.0

1275

1295

1315

1320

 

1320

1320

 

1320

1320

1320

1315

 

 

 

 

 

(1110)†

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Heat

1475

0---

1.0

1460

1465

1475

1475

 

1475

1475

 

1475

1475

1465

1465

 

 

 

 

 

(1330)†

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

††

 

 

2---

Ton A/C Cooling

700

0---

0.50‡

700

700

700

700

 

700

 

 

 

 

 

 

††

 

2

--- 1/2

--- Ton A/C Cooling

875

0---

0.50‡

875

875

875

875

 

875

 

 

 

 

 

 

††

 

 

3---

Ton A/C Cooling

1050

0---

0.50‡

1050

1050

1050

1050

 

1050

 

 

 

 

 

 

 

 

3

--- 1/2

--- Ton A/C Cooling

1225

0---

1.0‡

1225

1225

1225

1225

 

1225

1225

 

1225

1225

1225

1225

 

 

 

4---

Ton A/C Cooling

1400

0---

1.0‡

1400

1400

1400

1400

 

1400

1400

 

1400

1400

1400

1400

 

 

 

5---

Ton A/C Cooling

1750

0---

1.0‡

1750

1750

1750

1750

 

1750

1750

 

1750

1750

1740

1725

 

 

 

6---

Ton A/C Cooling

2100

0---

1.0

2100

2100

2100

2100

 

2090

2075

 

2055

2040

2005

1970

 

 

 

 

 

Maximum

2200

0---

1.0

2200

2190

2190

2180

 

2155

2145

 

2125

2100

2080

2020

135---

22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Heat

1700

0---

1.0

1700

1700

1700

1700

 

1700

1695

 

1700

1695

1685

1670

 

 

 

 

 

(1430)†

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Heat

1915

0---

1.0

1900

1905

1915

1915

 

1915

1915

 

1915

1915

1915

1915

 

 

 

 

 

(1725)†

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

††

 

 

2---

Ton A/C Cooling

700

0---

0.50‡

700

700

700

700

 

665

 

 

 

 

 

 

††

 

2

--- 1/2

--- Ton A/C Cooling

875

0---

0.50‡

870

870

865

865

 

865

 

 

 

 

 

 

††

 

 

3---

Ton A/C Cooling

1050

0---

0.50‡

1010

1030

1050

1050

 

1050

 

 

 

 

 

 

 

 

3

--- 1/2

--- Ton A/C Cooling

1225

0---

1.0‡

1155

1180

1200

1210

 

1220

1225

 

1225

1225

1225

1225

 

 

 

4---

Ton A/C Cooling

1400

0---

1.0‡

1395

1400

1400

1400

 

1400

1400

 

1400

1390

1375

1355

 

 

 

5---

Ton A/C Cooling

1750

0---

1.0‡

1740

1750

1750

1750

 

1735

1740

 

1735

1730

1715

1700

 

 

 

6---

Ton A/C Cooling

2100

0---

1.0

2075

2085

2090

2100

 

2100

2100

 

2090

2080

2055

2025

 

 

 

 

 

Maximum

2200

0---

1.0

2180

2195

2200

2200

 

2200

2200

 

2185

2165

2140

2095

155---

22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Heat

1715

0---

1.0

1715

1715

1715

1715

 

1715

1705

 

1710

1705

1705

1695

 

 

 

 

 

(1440)†

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Heat

1970

0---

1.0

1955

1965

1965

1970

 

1970

1970

 

1970

1970

1970

1960

 

 

 

 

 

(1775)†

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

††

 

 

2---

Ton A/C Cooling

700

0---

0.50‡

700

700

700

700

 

680

 

 

 

 

 

 

††

 

2

--- 1/2

--- Ton A/C Cooling

875

0---

0.50‡

865

875

875

865

 

865

 

 

 

 

 

 

††

 

 

3---

Ton A/C Cooling

1050

0---

0.50‡

1015

1020

1035

1045

 

1050

 

 

 

 

 

 

 

 

3

--- 1/2

--- Ton A/C Cooling

1225

0---

1.0‡

1160

1185

1215

1225

 

1225

1225

 

1225

1225

1225

1225

 

 

 

4---

Ton A/C Cooling

1400

0---

1.0‡

1385

1400

1400

1400

 

1400

1400

 

1395

1395

1380

1360

 

 

 

5---

Ton A/C Cooling

1750

0---

1.0‡

1745

1750

1750

1750

 

1745

1740

 

1745

1745

1740

1735

 

 

 

6---

Ton A/C Cooling

2100

0---

1.0

2055

2070

2080

2085

 

2095

2100

 

2100

2100

2090

2065

 

 

 

 

 

Maximum

2200

0---

1.0

2175

2190

2200

2200

 

2200

2200

 

2200

2200

2180

2160

*Actual external static pressure (ESP) can be determined by using the fan laws (CFM 2 proportional to ESP); such as, a system with 1180 CFM at 0.5 ESP would operate at cooling airflow of 1050 CFM at 0.4 ESP and low--- heating airflow of 735 CFM at 0.19 ESP.

{Comfort airflow values are shown in parenthesis. Comfort airflow is selected when the low--- heat rise adjustment switch (SW1--- 3) is OFF and

the comfort/efficiency switch (SW1

--- 4) is ON.

}Ductwork must be sized for high---

heating CFM within the operational range of ESP.

{{Operation within the blank areas of the chart is not recommended because high--- heat operation will be above 1.0 ESP.

***All airflow on 110 size furnace are 5% less on side return only installations.

18

Image 18
Contents Electrostatic Discharge ESD Precautions Safety Considerations Furnace Reliability HazardCUT Hazard Clearances to Combustibles Electrostatic Discharge ESD Precautions Procedure IntroductionCodes and Standards Dimensional Drawing Dimensions In. mm LocationCarbon Monoxide Poisoning / Component Damage Hazard FIRE, Injury or Death HazardFire Hazard Location Relative to Cooling EquipmentPersonal Injury AND/OR Property Damage Hazard AIR for Combustion Ventilation Furnace Corrosion HazardCarbon Monoxide Poisoning Hazard Air for Combustion, Ventilation, and Dilution for Outdoors Standard MethodCombination of Indoor and Outdoor Air InstallationUpflow Installation Bottom Return Air InletDownflow Installation Suspended Furnace SupportPlatform Furnace Support Floor and Plenum Opening Dimensions Roll-Out Protection AIR Ducts Opening Dimensions In. mmFilter Arrangement General RequirementsSupply Air Connections Upflow and Horizontal FurnacesDownflow Furnaces Horizontal Unit Suspension Typical Attic Installation Downflow Return Air Configurations and Restrictions Air Delivery CFM With Filter CFMMaximum Capacity of Pipe Return Air ConnectionsGAS Piping Fire or Explosion Hazard Furnace Damage HazardElectrical Shock and Fire Hazard WiringElectrical Connections Electrical Shock Hazard Furnace MAY not Operate HazardElectrical Data Box RelocationFire or Electrical Shock Hazard BX Cable Installation in Furnace J-Box AccessoriesVenting Field Wiring Diagram General Venting Requirements Two-Stage Furnace with Single-Speed Air ConditionerTwo-Stage Furnace with Two-Speed Air Condi Tioner See notes 1 and 2 on the page following these figures 315AAV Chimney Inspection Chart Masonry Chimney Requirement Appliance Application RequirementsBurn Hazard Additional Venting Requirements Vent HeightUpflow Application Vent Elbow Up Horizontal Left Application Vent Elbow Left Venting Notes for Horizontal Left Application Vent Elbow UpGeneral START-UP, ADJUSTMENT, and Safety CheckSidewall Venting Furnace Vent Orientation Furnace Input MIN. VentOrifice Hole Fire and Explosion HazardFurnace Setup Switch Description Setup Switch Switch Name Normal Description of USE PositionAltitude Derate Multiplier for U.S.A Altitude Percent Derate MultiplierDerate Factor Unit Damage Hazard Furnace Overheating Hazard315AAV Wiring Diagram Gas Rate CU ft./hr Seconds G Size of Test DialSpecific Gravity of Natural GAS Altitude Range Altitude RangeBTUH/CU FT Altitude Range BTUH/CUAT Altitude Electrical SHOCK, Fire or Explosion Hazard Service and Maintenance ProceduresEnvironmental Hazard Electrical Operation HazardElectrical Controls and Wiring Component Self-TestMedia cabinet filter procedures Care and Maintenance Fire or Explosion HazardCleaning and/or Replacing Air Filter Carbon Monoxide Poisoning and Fire HazardFilter Size Information In. mm Cleaning Heat ExchangerService agency Following steps should be performed by a qualifiedIgniter Position Side View Sequence of Operation Cooling A/C or Continuous-Fan CF Airflow Selection Chart Inducer Prepurge PeriodSingle-Stage Thermostat and Two-Speed Cooling Adaptive Mode Single-Speed CoolingThermidistat Mode Super-Dehumidify ModeContinuous Blower Mode Troubleshooting Heat pumpComponent test Troubleshooting Guide Adapter Kit Werblo Modelinvalid Orselection Accessory List Description Part NumberParts Replacement Information Guide