Bryant 315AAV instruction manual Orifice Hole, Fire and Explosion Hazard

Page 35

BURNER

ORIFICE

A93059

Fig. 50 - Orifice Hole

THERMOSTAT SUBBASE TERMINALS WITH THERMOSTAT REMOVED (ANITICIPATOR, CLOCK, ETC.,

MUST BE OUT OF CIRCUIT.)

HOOK-AROUND AMMETER

R Y W G

10 TURNS

FROM UNIT 24-V

CONTROL TERMINALS

EXAMPLE:

5.0 AMPS ON AMMETER

=

0.5 AMPS FOR THERMOSTAT

10 TURNS AROUND JAWS

ANTICIPATOR SETTING

 

 

 

 

 

A96316

Fig. 51 - Amp. Draw Check with Ammeter

Start-Up Procedures

!WARNING

FIRE AND EXPLOSION HAZARD

Failure to follow this warning could cause personal injury, death or property damage.

Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for detection of leaks to check all connections.

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury, or death.

Blower access door switch opens 115-v power to control. No component operation can occur unless switch is closed. Caution must be taken when manually closing this switch for service purposes.

1.Purge gas lines after all connections have been made.

2.Check gas lines for leaks.

3.To Begin Component Self-Test:

Remove Blower Access Door. Disconnect the thermostat R lead from furnace control board. Manually close blower door switch. Turn Setup DIP switch SW1-6 ON. (See Fig. 26, 53 and Table 10.)

NOTE: The furnace control allows all components, except the gas valve, to be run for short period of time. This feature helps diagnose a system problem in case of a component failure. Component test feature will not operate if any thermostat signal is present at the control.

Refer to service label attached to furnace or See Fig. 52. Component test sequence is as follows:

a.Inducer motor starts on high-speed and continues to run until Step d. of component test sequence.

b.Hot surface igniter is energized for 15 sec., then off.

c.Blower motor operates for 15 sec.

d.Inducer motor goes to low-speed for 10 sec., then stops.

e.After component test is completed, one or more status codes (11, 25, or 41) will flash. See component test section of service label (Fig. 52) in furnace for explan- ation of status codes.

NOTE: To repeat component test, turn setup switch SW1-6 OFF, then back ON.

4.Turn setup DIP switch SW1-6 OFF. Reconnect R lead to furnace control board, release blower door switch and re- install blower access door.

5.Operate furnace per instruction on inner door.

6.Verify furnace shut down by lowering thermostat setting below room temperature.

7.Verify furnace restarts by raising thermostat setting above room temperature.

315AAV

35

Image 35
Contents Electrostatic Discharge ESD Precautions CUT Hazard Safety ConsiderationsFurnace Reliability Hazard Clearances to Combustibles Codes and Standards Electrostatic Discharge ESD Precautions ProcedureIntroduction Location Dimensional Drawing Dimensions In. mmFIRE, Injury or Death Hazard Carbon Monoxide Poisoning / Component Damage HazardPersonal Injury AND/OR Property Damage Hazard Fire HazardLocation Relative to Cooling Equipment Carbon Monoxide Poisoning Hazard AIR for Combustion VentilationFurnace Corrosion Hazard Standard Method Air for Combustion, Ventilation, and Dilution for OutdoorsBottom Return Air Inlet InstallationUpflow Installation Combination of Indoor and Outdoor AirPlatform Furnace Support Downflow InstallationSuspended Furnace Support Floor and Plenum Opening Dimensions Roll-Out Protection General Requirements Opening Dimensions In. mmFilter Arrangement AIR DuctsDownflow Furnaces Supply Air ConnectionsUpflow and Horizontal Furnaces Horizontal Unit Suspension Typical Attic Installation Downflow Return Air Configurations and Restrictions CFM Air Delivery CFM With FilterFurnace Damage Hazard Return Air ConnectionsGAS Piping Fire or Explosion Hazard Maximum Capacity of PipeFurnace MAY not Operate Hazard WiringElectrical Connections Electrical Shock Hazard Electrical Shock and Fire HazardFire or Electrical Shock Hazard Electrical DataBox Relocation Venting BX Cable Installation in Furnace J-BoxAccessories Field Wiring Diagram Two-Stage Furnace with Single-Speed Air Conditioner General Venting RequirementsTwo-Stage Furnace with Two-Speed Air Condi Tioner See notes 1 and 2 on the page following these figures 315AAV Chimney Inspection Chart Burn Hazard Masonry Chimney RequirementAppliance Application Requirements Vent Height Additional Venting RequirementsUpflow Application Vent Elbow Up Horizontal Left Application Vent Elbow Left Horizontal Left Application Vent Elbow Up Venting Notes forFurnace Vent Orientation Furnace Input MIN. Vent START-UP, ADJUSTMENT, and Safety CheckSidewall Venting GeneralFire and Explosion Hazard Orifice HoleSetup Switch Switch Name Normal Description of USE Position Furnace Setup Switch DescriptionDerate Factor Altitude Derate Multiplier for U.S.AAltitude Percent Derate Multiplier Furnace Overheating Hazard Unit Damage Hazard315AAV Wiring Diagram Seconds G Size of Test Dial Gas Rate CU ft./hrSpecific Gravity of Natural GAS Altitude Range BTUH/CU FT AltitudeRange BTUH/CU Altitude RangeAT Altitude Electrical Operation Hazard Service and Maintenance ProceduresEnvironmental Hazard Electrical SHOCK, Fire or Explosion HazardComponent Self-Test Electrical Controls and WiringCarbon Monoxide Poisoning and Fire Hazard Care and Maintenance Fire or Explosion HazardCleaning and/or Replacing Air Filter Media cabinet filter proceduresFollowing steps should be performed by a qualified Cleaning Heat ExchangerService agency Filter Size Information In. mmIgniter Position Side View Sequence of Operation Inducer Prepurge Period Cooling A/C or Continuous-Fan CF Airflow Selection ChartSingle-Speed Cooling Single-Stage Thermostat and Two-Speed Cooling Adaptive ModeContinuous Blower Mode Thermidistat ModeSuper-Dehumidify Mode Component test TroubleshootingHeat pump Troubleshooting Guide Adapter Kit Werblo Modelinvalid Orselection Description Part Number Accessory ListParts Replacement Information Guide