Bryant 315AAV instruction manual START-UP, ADJUSTMENT, and Safety Check, Sidewall Venting, General

Page 34

315AAV

Caution!! For the following applications, use the minimum vertical heights as specified below.

For all other applications, follow exclusively the National Fuel Gas Code.

FURNACE

VENT ORIENTATION

FURNACE INPUT

MIN. VENT

MIN. VERTICAL VENT

DIAMETER

HEIGHT

ORIENTATION

 

(BTUH/HR)

 

IN. (mm)*

FT. (M)**

 

 

 

 

 

 

 

 

Downflow

Vent elbow left, then up

154,000 132,000 110,000

5 (127)

12 (3.6)

Fig. 36

 

 

 

 

 

 

 

 

 

Horizontal Left

Vent elbow right, then up

154,000 132,000

5 (127)

7 (2.1)

Fig. 39

 

 

 

 

 

 

 

 

 

Horizontal Left

Vent Elbow up

154,000 132,000

5 (127)

7 (2.1)

Fig. 40

 

 

 

 

Horizontal Left

Vent elbow right

154,000

5 (127)

7 (2.1)

Fig. 41

 

 

 

 

 

 

 

 

 

Downflow

Vent elbow up then left

110,000

5 (127)

10 (3.0)

Fig. 34

 

 

 

 

Downflow

Vent elbow up, then right

110,000

5 (127)

10 (3.0)

Fig. 37

 

 

 

 

NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC.

 

 

*4---in. (102 mm) inside casing or vent guard

 

 

 

**Including 4 in. (102 mm) vent section(s)

 

 

 

The horizontal portion of the venting system shall slope upwards not less than 1/4-in. per linear ft. (21 mm/m) from the furnace to the vent and shall be rigidly supported every 5 ft. (1.5 M) or less with metal hangers or straps to ensure there is no movement after installation.

Sidewall Venting

This furnace is not approved for direct sidewall horizontal venting.

Per section 12.4.3 of the NFPA 54/ANSI Z223.1-2009, any listed mechanical venter may be used, when approved by the authority having jurisdiction.

Select the listed mechanical venter to match the Btuh input of the furnace being vented. Follow all manufacturer’s installation requirements for venting and termination included with the listed mechanical venter.

START-UP, ADJUSTMENT, AND SAFETY

CHECK

General

!WARNING

3.Gas supply pressure to the furnace must be greater than 4.5-In. W.C. (0.16 psig ) but not exceed 14-In. W.C. (0.5 psig).

4.Check all manual-reset switches for continuity.

5.Replace blower compartment door. Door must be in place to operate furnace.

6.Setup switch descriptions The variable speed furnace con- trol has DIP switches to select thermostat staging, blower off delay timings, air flow selection and other operational or service related functions. (See Fig. 26, 53 and Table 10.)

!CAUTION

CUT HAZARD

Failure to follow this caution may result in personal injury.

Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicing furnaces.

FIRE HAZARD

Failure to follow this warning could result in personal injury, death or property damage.

This furnace is equipped with manual reset limit switches in the gas control area. The switches open and shut off power to the gas valve, if a flame rollout or overheating condition occurs in the gas control area. DO NOT bypass the switches. Correct problem before resetting the switches.

1.

Maintain 115-v wiring and ground. Improper polarity will

 

result in rapid flashing LED and no furnace operation.

2.

Make thermostat wire connections at the 24-v terminal

 

block on the furnace control. Failure to make proper con-

 

nections will result in improper operation. (See Fig. 25 -

ON/OFF SWITCH

1/2˝ NPT INLET

INLET

PRESSURE TAP

1/2˝ NPT OUTLET

REGULATOR COVER SCREW

PLASTIC ADJUST SCREW

REGULATOR SPRING

HIGH STAGE GAS

PRESSURE REGULATOR

ADJUSTMENT

LOW STAGE

GAS PRESSURE

REGULATOR ADJUSTMENT

MANIFOLD

PRESSURE TAP

34.)

A04167

Fig. 49 - Redundant Automatic Gas Control Valve

34

Image 34
Contents Electrostatic Discharge ESD Precautions Furnace Reliability Hazard Safety ConsiderationsCUT Hazard Clearances to Combustibles Introduction Electrostatic Discharge ESD Precautions ProcedureCodes and Standards Dimensional Drawing Dimensions In. mm LocationCarbon Monoxide Poisoning / Component Damage Hazard FIRE, Injury or Death HazardLocation Relative to Cooling Equipment Fire HazardPersonal Injury AND/OR Property Damage Hazard Furnace Corrosion Hazard AIR for Combustion VentilationCarbon Monoxide Poisoning Hazard Air for Combustion, Ventilation, and Dilution for Outdoors Standard MethodCombination of Indoor and Outdoor Air InstallationUpflow Installation Bottom Return Air InletSuspended Furnace Support Downflow InstallationPlatform Furnace Support Floor and Plenum Opening Dimensions Roll-Out Protection AIR Ducts Opening Dimensions In. mmFilter Arrangement General RequirementsUpflow and Horizontal Furnaces Supply Air ConnectionsDownflow Furnaces Horizontal Unit Suspension Typical Attic Installation Downflow Return Air Configurations and Restrictions Air Delivery CFM With Filter CFMMaximum Capacity of Pipe Return Air ConnectionsGAS Piping Fire or Explosion Hazard Furnace Damage HazardElectrical Shock and Fire Hazard WiringElectrical Connections Electrical Shock Hazard Furnace MAY not Operate HazardBox Relocation Electrical DataFire or Electrical Shock Hazard Accessories BX Cable Installation in Furnace J-BoxVenting Field Wiring Diagram General Venting Requirements Two-Stage Furnace with Single-Speed Air ConditionerTwo-Stage Furnace with Two-Speed Air Condi Tioner See notes 1 and 2 on the page following these figures 315AAV Chimney Inspection Chart Appliance Application Requirements Masonry Chimney RequirementBurn Hazard Additional Venting Requirements Vent HeightUpflow Application Vent Elbow Up Horizontal Left Application Vent Elbow Left Venting Notes for Horizontal Left Application Vent Elbow UpGeneral START-UP, ADJUSTMENT, and Safety CheckSidewall Venting Furnace Vent Orientation Furnace Input MIN. VentOrifice Hole Fire and Explosion HazardFurnace Setup Switch Description Setup Switch Switch Name Normal Description of USE PositionAltitude Percent Derate Multiplier Altitude Derate Multiplier for U.S.ADerate Factor Unit Damage Hazard Furnace Overheating Hazard315AAV Wiring Diagram Gas Rate CU ft./hr Seconds G Size of Test DialSpecific Gravity of Natural GAS Altitude Range Range AltitudeBTUH/CU FT Altitude Range BTUH/CUAT Altitude Electrical SHOCK, Fire or Explosion Hazard Service and Maintenance ProceduresEnvironmental Hazard Electrical Operation HazardElectrical Controls and Wiring Component Self-TestMedia cabinet filter procedures Care and Maintenance Fire or Explosion HazardCleaning and/or Replacing Air Filter Carbon Monoxide Poisoning and Fire HazardFilter Size Information In. mm Cleaning Heat ExchangerService agency Following steps should be performed by a qualifiedIgniter Position Side View Sequence of Operation Cooling A/C or Continuous-Fan CF Airflow Selection Chart Inducer Prepurge PeriodSingle-Stage Thermostat and Two-Speed Cooling Adaptive Mode Single-Speed CoolingSuper-Dehumidify Mode Thermidistat ModeContinuous Blower Mode Heat pump TroubleshootingComponent test Troubleshooting Guide Adapter Kit Werblo Modelinvalid Orselection Accessory List Description Part NumberParts Replacement Information Guide