315AAV
Caution!! For the following applications, use the minimum vertical heights as specified below.
For all other applications, follow exclusively the National Fuel Gas Code.
FURNACE | VENT ORIENTATION | FURNACE INPUT | MIN. VENT | MIN. VERTICAL VENT | |
DIAMETER | HEIGHT | ||||
ORIENTATION |
| (BTUH/HR) | |||
| IN. (mm)* | FT. (M)** | |||
|
|
| |||
|
|
|
|
| |
Downflow | Vent elbow left, then up | 154,000 132,000 110,000 | 5 (127) | 12 (3.6) | |
Fig. 36 | |||||
|
|
|
| ||
|
|
|
|
| |
Horizontal Left | Vent elbow right, then up | 154,000 132,000 | 5 (127) | 7 (2.1) | |
Fig. 39 | |||||
|
|
|
| ||
|
|
|
|
| |
Horizontal Left | Vent Elbow up | 154,000 132,000 | 5 (127) | 7 (2.1) | |
Fig. 40 | |||||
|
|
|
| ||
Horizontal Left | Vent elbow right | 154,000 | 5 (127) | 7 (2.1) | |
Fig. 41 | |||||
|
|
|
| ||
|
|
|
|
| |
Downflow | Vent elbow up then left | 110,000 | 5 (127) | 10 (3.0) | |
Fig. 34 | |||||
|
|
|
| ||
Downflow | Vent elbow up, then right | 110,000 | 5 (127) | 10 (3.0) | |
Fig. 37 | |||||
|
|
|
| ||
NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC. |
|
| |||
|
|
| |||
**Including 4 in. (102 mm) vent section(s) |
|
|
|
The horizontal portion of the venting system shall slope upwards not less than
Sidewall Venting
This furnace is not approved for direct sidewall horizontal venting.
Per section 12.4.3 of the NFPA 54/ANSI
Select the listed mechanical venter to match the Btuh input of the furnace being vented. Follow all manufacturer’s installation requirements for venting and termination included with the listed mechanical venter.
START-UP, ADJUSTMENT, AND SAFETY
CHECK
General
!WARNING
3.Gas supply pressure to the furnace must be greater than
4.Check all
5.Replace blower compartment door. Door must be in place to operate furnace.
6.Setup switch descriptions The variable speed furnace con- trol has DIP switches to select thermostat staging, blower off delay timings, air flow selection and other operational or service related functions. (See Fig. 26, 53 and Table 10.)
!CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicing furnaces.
FIRE HAZARD
Failure to follow this warning could result in personal injury, death or property damage.
This furnace is equipped with manual reset limit switches in the gas control area. The switches open and shut off power to the gas valve, if a flame rollout or overheating condition occurs in the gas control area. DO NOT bypass the switches. Correct problem before resetting the switches.
1. | Maintain |
| result in rapid flashing LED and no furnace operation. |
2. | Make thermostat wire connections at the |
| block on the furnace control. Failure to make proper con- |
| nections will result in improper operation. (See Fig. 25 - |
ON/OFF SWITCH
1/2˝ NPT INLET
INLET
PRESSURE TAP
1/2˝ NPT OUTLET
REGULATOR COVER SCREW
PLASTIC ADJUST SCREW
REGULATOR SPRING
HIGH STAGE GAS
PRESSURE REGULATOR
ADJUSTMENT
LOW STAGE
GAS PRESSURE
REGULATOR ADJUSTMENT
MANIFOLD
PRESSURE TAP
34.) |
A04167
Fig. 49 - Redundant Automatic Gas Control Valve
34