Page 45

Table 15 - Orifice Size and Manifold Pressure (In. W.C.) for Gas Input Rate (Con’t.)

(Tabulated Data Based on 21,000 Btuh High-Heat/14,500 Btuh for Low-Heat Per Burner, Derated 4 Percent for Each 1000 Ft.

(305 M) Above Sea level)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVG. GAS

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

 

 

HEAT VALUE

 

 

 

 

 

 

 

 

 

 

 

 

ALTITUDE RANGE

 

0.58

 

0.60

 

0.62

 

0.64

 

FT. (M)

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

(BTUH/CU

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

 

 

No.

 

No.

 

No.

 

No.

 

 

 

 

FT.)

 

High/Low

 

High/Low

 

High/Low

 

High/Low

 

 

 

 

 

 

 

 

 

 

 

 

 

 

725

44

 

3.5/1.7

43

 

3.2/1.5

43

 

3.3/1.6

43

 

3.4/1.6

 

 

5001 to

750

44

 

3.3/1.6

44

 

3.4/1.6

44

 

3.5/1.7

43

 

3.2/1.5

 

 

775

45

 

3.7/1.8

44

 

3.2/1.5

44

 

3.3/1.6

44

 

3.4/1.6

 

 

6000

 

 

 

 

 

 

 

 

 

 

 

 

 

USA

800

46

 

3.7/1.8

46

 

3.8/1.8

45

 

3.8/1.8

44

 

3.2/1.5

 

(1524 to

825

46

 

3.5/1.7

46

 

3.6/1.7

46

 

3.7/1.8

46

 

3.8/1.8

 

 

 

 

 

 

 

 

1829)

850

47

 

3.7/1.8

47

 

3.8/1.8

46

 

3.5/1.7

46

 

3.6/1.7

 

 

 

875

47

 

3.5/1.7

47

 

3.6/1.7

47

 

3.7/1.8

46

 

3.4/1.6

 

 

 

900

48

 

3.8/1.8

47

 

3.4/1.6

47

 

3.5/1.7

47

 

3.7/1.7

 

 

 

AVG. GAS

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

ALTITUDE RANGE

HEAT VALUE

 

0.58

 

0.60

 

0.62

 

0.64

 

FT. (M)

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

 

 

(BTUH/CU FT.)

No.

 

No.

 

No.

 

No.

 

 

 

 

 

High/Low

 

High/Low

 

High/Low

 

High/Low

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

675

44

 

3.5/1.7

43

 

3.2/1.5

43

 

3.3/1.6

43

 

3.4/1.6

 

 

6001 to

700

44

 

3.3/1.6

44

 

3.4/1.6

44

 

3.5/1.7

43

 

3.2/1.5

 

 

725

45

 

3.7/1.8

45

 

3.8/1.8

44

 

3.3/1.6

44

 

3.4/1.6

USA

 

7000

750

46

 

3.6/1.7

46

 

3.8/1.8

45

 

3.7/1.8

45

 

3.8/1.8

 

(1829 to

775

46

 

3.4/1.6

46

 

3.5/1.7

46

 

3.6/1.7

46

 

3.8/1.8

 

 

 

 

 

 

 

 

2134)

800

47

 

3.6/1.7

47

 

3.8/1.8

46

 

3.4/1.6

46

 

3.5/1.7

 

 

 

825

47

 

3.4/1.6

47

 

3.5/1.7

47

 

3.6/1.7

47

 

3.8/1.8

 

 

 

850

48

 

3.7/1.7

48

 

3.8/1.8

47

 

3.4/1.6

47

 

3.5/1.7

 

 

 

AVG. GAS

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

ALTITUDE RANGE

HEAT VALUE

 

0.58

 

0.60

 

0.62

 

0.64

 

FT. (M)

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

 

 

(BTUH/CU FT.)

No.

 

No.

 

No.

 

No.

 

 

 

 

 

High/Low

 

High/Low

 

High/Low

 

High/Low

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

650

44

 

3.3/1.6

44

 

3.4/1.6

44

 

3.5/1.7

43

 

3.2/1.5

 

 

7001 to

675

45

 

3.7/1.8

45

 

3.8/1.8

44

 

3.3/1.6

44

 

3.4/1.6

 

 

700

46

 

3.6/1.7

46

 

3.7/1.8

46

 

3.8/1.8

45

 

3.8/1.8

 

 

8000

 

 

 

 

 

 

 

 

 

 

 

 

 

USA

725

47

 

3.8/1.8

46

 

3.5/1.7

46

 

3.6/1.7

46

 

3.7/1.8

 

(2134 to

750

47

 

3.5/1.7

47

 

3.7/1.8

47

 

3.8/1.8

46

 

3.5/1.6

 

 

 

 

 

 

 

 

2438)

775

48

 

3.8/1.8

47

 

3.4/1.6

47

 

3.6/1.7

47

 

3.7/1.7

 

 

 

800

48

 

3.6/1.7

48

 

3.7/1.8

48

 

3.8/1.8

47

 

3.4/1.6

 

 

 

825

48

 

3.3/1.6

48

 

3.5/1.6

48

 

3.6/1.7

48

 

3.7/1.8

 

 

 

AVG. GAS

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

ALTITUDE RANGE

 

0.58

 

0.60

 

0.62

 

0.64

HEAT VALUE

 

 

 

 

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

FT. (M)

AT ALTITUDE

 

 

 

 

 

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

 

 

(BTUH/CU FT.)

No.

 

No.

 

No.

 

No.

 

 

 

 

 

High/Low

 

High/Low

 

High/Low

 

High/Low

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

625

45

3.7/1.8

45

3.8/1.8

44

3.3/1.6

44

3.4/1.6

 

 

8001 to

650

46

3.6/1.7

46

3.7/1.8

46

3.8/1.8

45

3.8/1.8

 

 

675

47

3.8/1.8

46

3.4/1.6

46

3.5/1.7

46

3.7/1.7

 

9000

USA

700

47

3.5/1.7

47

3.6/1.7

47

3.7/1.8

46

3.4/1.6

 

(2438 to

 

 

725

48

3.7/1.8

48

3.8/1.8

47

3.5/1.7

47

3.6/1.7

 

2743)

 

750

48

3.5/1.7

48

3.6/1.7

48

3.7/1.8

48

3.8/1.8

 

 

 

775

49

3.8/1.8

48

3.4/1.6

48

3.5/1.7

48

3.6/1.7

 

 

9001 to

600

46

3.6/1.7

46

3.7/1.8

46

3.8/1.8

45

3.7/1.8

 

 

625

47

3.7/1.8

47

3.8/1.8

46

3.5/1.7

46

3.6/1.7

 

10,000

 

 

 

 

 

 

 

 

 

USA

650

47

3.4/1.6

47

3.6/1.7

47

3.7/1.8

47

3.8/1.8

 

(2743 to

675

48

3.6/1.7

48

3.8/1.8

47

3.4/1.6

47

3.5/1.7

 

 

 

3048)

700

48

3.4/1.6

48

3.5/1.7

48

3.6/1.7

48

3.7/1.8

 

 

 

725

49

3.7/1.8

49

3.8/1.8

48

3.4/1.6

48

3.5/1.7

* Orifice numbers 43 are factory installed

315AAV

45

Image 45
Contents Electrostatic Discharge ESD Precautions Safety Considerations Furnace Reliability HazardCUT Hazard Clearances to Combustibles Electrostatic Discharge ESD Precautions Procedure IntroductionCodes and Standards Location Dimensional Drawing Dimensions In. mmFIRE, Injury or Death Hazard Carbon Monoxide Poisoning / Component Damage HazardFire Hazard Location Relative to Cooling EquipmentPersonal Injury AND/OR Property Damage Hazard AIR for Combustion Ventilation Furnace Corrosion HazardCarbon Monoxide Poisoning Hazard Standard Method Air for Combustion, Ventilation, and Dilution for OutdoorsUpflow Installation InstallationCombination of Indoor and Outdoor Air Bottom Return Air InletDownflow Installation Suspended Furnace SupportPlatform Furnace Support Floor and Plenum Opening Dimensions Roll-Out Protection Filter Arrangement Opening Dimensions In. mmAIR Ducts General RequirementsSupply Air Connections Upflow and Horizontal FurnacesDownflow Furnaces Horizontal Unit Suspension Typical Attic Installation Downflow Return Air Configurations and Restrictions CFM Air Delivery CFM With FilterGAS Piping Fire or Explosion Hazard Return Air ConnectionsMaximum Capacity of Pipe Furnace Damage HazardElectrical Connections Electrical Shock Hazard WiringElectrical Shock and Fire Hazard Furnace MAY not Operate HazardElectrical Data Box RelocationFire or Electrical Shock Hazard BX Cable Installation in Furnace J-Box AccessoriesVenting Field Wiring Diagram Two-Stage Furnace with Single-Speed Air Conditioner General Venting RequirementsTwo-Stage Furnace with Two-Speed Air Condi Tioner See notes 1 and 2 on the page following these figures 315AAV Chimney Inspection Chart Masonry Chimney Requirement Appliance Application RequirementsBurn Hazard Vent Height Additional Venting RequirementsUpflow Application Vent Elbow Up Horizontal Left Application Vent Elbow Left Horizontal Left Application Vent Elbow Up Venting Notes forSidewall Venting START-UP, ADJUSTMENT, and Safety CheckGeneral Furnace Vent Orientation Furnace Input MIN. VentFire and Explosion Hazard Orifice HoleSetup Switch Switch Name Normal Description of USE Position Furnace Setup Switch DescriptionAltitude Derate Multiplier for U.S.A Altitude Percent Derate MultiplierDerate Factor Furnace Overheating Hazard Unit Damage Hazard315AAV Wiring Diagram Seconds G Size of Test Dial Gas Rate CU ft./hrSpecific Gravity of Natural GAS Altitude Range Altitude RangeBTUH/CU FT BTUH/CU Altitude RangeAT Altitude Environmental Hazard Service and Maintenance ProceduresElectrical SHOCK, Fire or Explosion Hazard Electrical Operation HazardComponent Self-Test Electrical Controls and WiringCleaning and/or Replacing Air Filter Care and Maintenance Fire or Explosion HazardMedia cabinet filter procedures Carbon Monoxide Poisoning and Fire HazardService agency Cleaning Heat ExchangerFilter Size Information In. mm Following steps should be performed by a qualifiedIgniter Position Side View Sequence of Operation Inducer Prepurge Period Cooling A/C or Continuous-Fan CF Airflow Selection ChartSingle-Speed Cooling Single-Stage Thermostat and Two-Speed Cooling Adaptive ModeThermidistat Mode Super-Dehumidify ModeContinuous Blower Mode Troubleshooting Heat pumpComponent test Troubleshooting Guide Adapter Kit Werblo Modelinvalid Orselection Description Part Number Accessory ListParts Replacement Information Guide