Page 22

315AAV

A10141

Fig. 24 - Field-Supplied Electrical Box on Furnace Casing

Power Cord Installation in Furnace J-Box

NOTE: Power cords must be able to handle the electrical requirements listed in Table 6. Refer to power cord manufacturer’s listings.

1.Remove cover from J-Box.

2.Route listed power cord through 7/8-in. (22 mm) diameter hole in J-Box.

3.Secure power cord to J-Box bracket with a strain relief bushing or a connector approved for the type of cord used.

4.Secure field ground wire to green ground screw on J-Box bracket.

5.Connect line voltage leads as shown in Fig. 25.

6.Reinstall cover to J-Box. Do not pinch wires between cover and bracket.

BX Cable Installation in Furnace J-Box

1. Remove cover from J-Box.

2.Route BX cable into 7/8-in. (22 mm) diameter hole in J-Box.

3.Secure BX cable to J-Box bracket with connectors ap- proved for the type of cable used.

4.Secure field ground wire to green ground screw on J-Box bracket.

5.Connect line voltage leads as shown in Fig. 25.

6.Reinstall cover to J-Box. Do not pinch wires between cover and bracket.

24-V Wiring

Make field 24-v connections at the 24-v terminal strip. (See Fig.

25- 34.) Connect terminal Y/Y2 as shown in Fig. 27-34 for proper cooling operation. Use only AWG No. 18, color-coded, copper thermostat wire.

The 24-v circuit contains an automotive-type, 3-amp. fuse located on the control. Any direct shorts during installation, service, or maintenance could cause this fuse to blow. If fuse replacement is required, use ONLY a 3-amp. fuse of identical size.

ACCESSORIES

1.Electronic Air Cleaner (EAC)

Connect an accessory Electronic Air Cleaner (if used) us- ing 1/4-in female quick connect terminals to the two male 1/4-in quick-connect terminals on the control board marked EAC-1 and EAC-2. The terminals are rated for 115VAC, 1.0 amps maximum and are energized during blower motor operation. (See Fig. 26.)

2.Humidifier (HUM)

Connect an accessory 24 VAC, 0.5 amp. maximum hu- midifier (if used) to the 1/4-in male quick-connect HUM terminal and COM-24V screw terminal on the control board thermostat strip. The HUM terminal is energized when blower is energized in heating. (See Fig. 26.)

NOTE: DO NOT connect furnace control HUM terminal to HUM (humidifier) terminal on Thermidistat, Zone Controller or similar device. See ThermidistatE, Zone Controller, thermostat, or controller manufacturer’s instructions for proper connection.

VENTING

The furnace shall be connected to a listed factory built chimney or vent, or a clay-tile lined masonry or concrete chimney. Venting into an unlined masonry chimney or concrete chimney is prohibited.

When an existing Category I furnace is removed or replaced, the original venting system, may no longer be sized to properly vent the attached appliances. An improperly sized Category I venting system could cause the formation of condensate in the furnace and vent, leakage of condensate and combustion products, and spillage of combustion products into the living space.

22

Image 22
Contents Electrostatic Discharge ESD Precautions Furnace Reliability Hazard Safety ConsiderationsCUT Hazard Clearances to Combustibles Introduction Electrostatic Discharge ESD Precautions ProcedureCodes and Standards Dimensional Drawing Dimensions In. mm LocationCarbon Monoxide Poisoning / Component Damage Hazard FIRE, Injury or Death HazardLocation Relative to Cooling Equipment Fire HazardPersonal Injury AND/OR Property Damage Hazard Furnace Corrosion Hazard AIR for Combustion VentilationCarbon Monoxide Poisoning Hazard Air for Combustion, Ventilation, and Dilution for Outdoors Standard MethodCombination of Indoor and Outdoor Air InstallationUpflow Installation Bottom Return Air InletSuspended Furnace Support Downflow InstallationPlatform Furnace Support Floor and Plenum Opening Dimensions Roll-Out Protection AIR Ducts Opening Dimensions In. mmFilter Arrangement General RequirementsUpflow and Horizontal Furnaces Supply Air ConnectionsDownflow Furnaces Horizontal Unit Suspension Typical Attic Installation Downflow Return Air Configurations and Restrictions Air Delivery CFM With Filter CFMMaximum Capacity of Pipe Return Air ConnectionsGAS Piping Fire or Explosion Hazard Furnace Damage HazardElectrical Shock and Fire Hazard WiringElectrical Connections Electrical Shock Hazard Furnace MAY not Operate HazardBox Relocation Electrical DataFire or Electrical Shock Hazard Accessories BX Cable Installation in Furnace J-BoxVenting Field Wiring Diagram General Venting Requirements Two-Stage Furnace with Single-Speed Air ConditionerTwo-Stage Furnace with Two-Speed Air Condi Tioner See notes 1 and 2 on the page following these figures 315AAV Chimney Inspection Chart Appliance Application Requirements Masonry Chimney RequirementBurn Hazard Additional Venting Requirements Vent HeightUpflow Application Vent Elbow Up Horizontal Left Application Vent Elbow Left Venting Notes for Horizontal Left Application Vent Elbow UpGeneral START-UP, ADJUSTMENT, and Safety CheckSidewall Venting Furnace Vent Orientation Furnace Input MIN. VentOrifice Hole Fire and Explosion HazardFurnace Setup Switch Description Setup Switch Switch Name Normal Description of USE PositionAltitude Percent Derate Multiplier Altitude Derate Multiplier for U.S.ADerate Factor Unit Damage Hazard Furnace Overheating Hazard315AAV Wiring Diagram Gas Rate CU ft./hr Seconds G Size of Test DialSpecific Gravity of Natural GAS Altitude Range Range AltitudeBTUH/CU FT Altitude Range BTUH/CUAT Altitude Electrical SHOCK, Fire or Explosion Hazard Service and Maintenance ProceduresEnvironmental Hazard Electrical Operation HazardElectrical Controls and Wiring Component Self-TestMedia cabinet filter procedures Care and Maintenance Fire or Explosion HazardCleaning and/or Replacing Air Filter Carbon Monoxide Poisoning and Fire HazardFilter Size Information In. mm Cleaning Heat ExchangerService agency Following steps should be performed by a qualifiedIgniter Position Side View Sequence of Operation Cooling A/C or Continuous-Fan CF Airflow Selection Chart Inducer Prepurge PeriodSingle-Stage Thermostat and Two-Speed Cooling Adaptive Mode Single-Speed CoolingSuper-Dehumidify Mode Thermidistat ModeContinuous Blower Mode Heat pump TroubleshootingComponent test Troubleshooting Guide Adapter Kit Werblo Modelinvalid Orselection Accessory List Description Part NumberParts Replacement Information Guide