Bryant 315AAV Electrical Connections Electrical Shock Hazard, Electrical Shock and Fire Hazard

Page 20

should extend below level of furnace gas controls. Place a ground joint union between furnace gas control valve and exterior manual equipment gas shutoff valve.

A 1/8-in. (3 mm) NPT plugged tapping, accessible for test gauge connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual equipment shutoff valve.

Piping should be pressure and leak tested in accordance with the current addition of the NFGC in the United States, local, and national plumbing and gas codes before the furnace has been connected. After all connections have been made, purge lines and check for leakage at furnace prior to operating furnace.

 

If pressure exceeds 0.5 psig (14-In. W.C.), gas supply pipe must

 

be disconnected from furnace and capped before and during

 

supply pipe pressure test. If test pressure is equal to or less than

 

0.5 psig (14-In. W.C.), turn off electric shutoff switch located on

 

furnace gas control valve and accessible manual equipment

315AAV

shutoff valve before and during supply pipe pressure test. After

all connections have been made, purge lines and check for

 

 

leakage at furnace prior to operating furnace.

 

The gas supply pressure shall be within the maximum and

 

minimum inlet supply pressures marked on the rating plate with

 

the furnace burners ON and OFF.

2” (51mm)

Street Elbow

A08551

Fig. 21 - Burner and Manifold

GAS

SUPPLY

MANUAL

SHUTOFF

VALVE (REQUIRED)

SEDIMENT TRAP

UNION

A02035

Fig. 22 - Typical Gas Pipe Arrangement

ELECTRICAL CONNECTIONS

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Blower access panel door switch opens 115-v power to control. No component operation can occur. Do not bypass or close switch with panel removed.

See Fig. 25 for field wiring diagram showing typical field 115-v wiring. Check all factory and field electrical connections for tightness.

Field-supplied wiring shall conform with the limitations of 63_F (33_C) rise.

!WARNING

ELECTRICAL SHOCK AND FIRE HAZARD

Failure to follow this warning could result in personal injury, death, or property damage.

The cabinet MUST have an uninterrupted or unbroken ground according to NEC ANSI/NFPA 70-2008 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire, conduit approved for electrical ground or a listed, grounded power cord (where permitted by local code) when installed in accordance with existing electrical codes. Refer to the power cord manufacturer’s ratings for proper wire gauge. Do not use gas piping as an electrical ground.

!CAUTION

FURNACE MAY NOT OPERATE HAZARD

Failure to follow this caution may result in intermittent furnace operation.

Furnace control must be grounded for proper operation or else control will lock out. Control must remain grounded through green/yellow wire routed to gas valve and manifold bracket screw.

115-V Wiring

Verify that the voltage, frequency, and phase correspond to that specified on unit rating plate. Also, check to be sure that service provided by utility is sufficient to handle load imposed by this equipment. Refer to rating plate or Table 7 for equipment electrical specifications.

U.S. Installations: Make all electrical connections in accordance with National Electrical Code (NEC) ANSI/NFPA 70-2008 and any local codes or ordinances that might apply.

20

Image 20
Contents Electrostatic Discharge ESD Precautions CUT Hazard Safety ConsiderationsFurnace Reliability Hazard Clearances to Combustibles Codes and Standards Electrostatic Discharge ESD Precautions ProcedureIntroduction Dimensional Drawing Dimensions In. mm LocationCarbon Monoxide Poisoning / Component Damage Hazard FIRE, Injury or Death HazardPersonal Injury AND/OR Property Damage Hazard Fire HazardLocation Relative to Cooling Equipment Carbon Monoxide Poisoning Hazard AIR for Combustion VentilationFurnace Corrosion Hazard Air for Combustion, Ventilation, and Dilution for Outdoors Standard MethodInstallation Upflow InstallationCombination of Indoor and Outdoor Air Bottom Return Air InletPlatform Furnace Support Downflow InstallationSuspended Furnace Support Floor and Plenum Opening Dimensions Roll-Out Protection Opening Dimensions In. mm Filter ArrangementAIR Ducts General RequirementsDownflow Furnaces Supply Air ConnectionsUpflow and Horizontal Furnaces Horizontal Unit Suspension Typical Attic Installation Downflow Return Air Configurations and Restrictions Air Delivery CFM With Filter CFMReturn Air Connections GAS Piping Fire or Explosion HazardMaximum Capacity of Pipe Furnace Damage HazardWiring Electrical Connections Electrical Shock HazardElectrical Shock and Fire Hazard Furnace MAY not Operate HazardFire or Electrical Shock Hazard Electrical DataBox Relocation Venting BX Cable Installation in Furnace J-BoxAccessories Field Wiring Diagram General Venting Requirements Two-Stage Furnace with Single-Speed Air ConditionerTwo-Stage Furnace with Two-Speed Air Condi Tioner See notes 1 and 2 on the page following these figures 315AAV Chimney Inspection Chart Burn Hazard Masonry Chimney RequirementAppliance Application Requirements Additional Venting Requirements Vent HeightUpflow Application Vent Elbow Up Horizontal Left Application Vent Elbow Left Venting Notes for Horizontal Left Application Vent Elbow UpSTART-UP, ADJUSTMENT, and Safety Check Sidewall VentingGeneral Furnace Vent Orientation Furnace Input MIN. VentOrifice Hole Fire and Explosion HazardFurnace Setup Switch Description Setup Switch Switch Name Normal Description of USE PositionDerate Factor Altitude Derate Multiplier for U.S.AAltitude Percent Derate Multiplier Unit Damage Hazard Furnace Overheating Hazard315AAV Wiring Diagram Gas Rate CU ft./hr Seconds G Size of Test DialSpecific Gravity of Natural GAS Altitude Range BTUH/CU FT AltitudeRange Altitude Range BTUH/CUAT Altitude Service and Maintenance Procedures Environmental HazardElectrical SHOCK, Fire or Explosion Hazard Electrical Operation HazardElectrical Controls and Wiring Component Self-TestCare and Maintenance Fire or Explosion Hazard Cleaning and/or Replacing Air FilterMedia cabinet filter procedures Carbon Monoxide Poisoning and Fire HazardCleaning Heat Exchanger Service agencyFilter Size Information In. mm Following steps should be performed by a qualifiedIgniter Position Side View Sequence of Operation Cooling A/C or Continuous-Fan CF Airflow Selection Chart Inducer Prepurge PeriodSingle-Stage Thermostat and Two-Speed Cooling Adaptive Mode Single-Speed CoolingContinuous Blower Mode Thermidistat ModeSuper-Dehumidify Mode Component test TroubleshootingHeat pump Troubleshooting Guide Adapter Kit Werblo Modelinvalid Orselection Accessory List Description Part NumberParts Replacement Information Guide