Bryant 315AAV instruction manual

Page 39

for Low Speed or High Speed cooling. See Table 5-Air Delivery - CFM (With Filter ). Depending on the model size, the cooling airflow can be adjusted from 1. tons nom- inal cooling to 3 ., to 4 or to 6 tons of nominal cooling based on 350 cfm ton.

The cooling airflow is adjusted by turning Setup switches SW2-1, SW2-2 and SW2-3 either ON or OFF. Select the required airflow from Fig. 57. Fig. 57 is based on 350 CFM per ton. For airflow at 400 CFM per ton, turn Setup SW1-5 ON (See Table 10 and Fig. 26 and 53.)

NOTE: 6 ton airflow will truncate at 2200 cfm on applicable models. For a complete explanation of cooling airflow, refer to the section titled “Sequence of Operation.”

10.Set Airflow For Continuous Fan/Low Speed Cooling Air- flow The ECM blower motor can be adjusted for continu-

ous fan speeds different than heating or cooling fan speed. See Table 5 - Air Delivery - CFM (With Filter). Select the required continuous fan airflow from Fig. 57.

The continuous fan speed is also the fan speed for low speed cooling when furnace is used with a 2-speed cool- ing unit. Adjust the Continuous Fan CFM to match the airflow required for low speed cooling. Select the required airflow from Fig. 55. For airflow at 400 CFM per ton, turn Setup SW1-5 ON (See Fig. 57.) The airflow selected for low speed cooling will also be the airflow used for con- tinuous fan.

The continuous fan speed can be further adjusted at the thermostat using the “Comfort Fan” select function. Changing the continuous fan speed at the thermostat DOES NOT change the low speed cooling airflow selec- ted at the control board.

315AAV

39

Image 39
Contents Electrostatic Discharge ESD Precautions Safety Considerations Furnace Reliability HazardCUT Hazard Clearances to Combustibles Electrostatic Discharge ESD Precautions Procedure IntroductionCodes and Standards Location Dimensional Drawing Dimensions In. mmFIRE, Injury or Death Hazard Carbon Monoxide Poisoning / Component Damage HazardFire Hazard Location Relative to Cooling EquipmentPersonal Injury AND/OR Property Damage Hazard AIR for Combustion Ventilation Furnace Corrosion HazardCarbon Monoxide Poisoning Hazard Standard Method Air for Combustion, Ventilation, and Dilution for OutdoorsBottom Return Air Inlet InstallationUpflow Installation Combination of Indoor and Outdoor AirDownflow Installation Suspended Furnace SupportPlatform Furnace Support Floor and Plenum Opening Dimensions Roll-Out Protection General Requirements Opening Dimensions In. mmFilter Arrangement AIR DuctsSupply Air Connections Upflow and Horizontal FurnacesDownflow Furnaces Horizontal Unit Suspension Typical Attic Installation Downflow Return Air Configurations and Restrictions CFM Air Delivery CFM With FilterFurnace Damage Hazard Return Air ConnectionsGAS Piping Fire or Explosion Hazard Maximum Capacity of PipeFurnace MAY not Operate Hazard WiringElectrical Connections Electrical Shock Hazard Electrical Shock and Fire HazardElectrical Data Box RelocationFire or Electrical Shock Hazard BX Cable Installation in Furnace J-Box AccessoriesVenting Field Wiring Diagram Two-Stage Furnace with Single-Speed Air Conditioner General Venting RequirementsTwo-Stage Furnace with Two-Speed Air Condi Tioner See notes 1 and 2 on the page following these figures 315AAV Chimney Inspection Chart Masonry Chimney Requirement Appliance Application RequirementsBurn Hazard Vent Height Additional Venting RequirementsUpflow Application Vent Elbow Up Horizontal Left Application Vent Elbow Left Horizontal Left Application Vent Elbow Up Venting Notes forFurnace Vent Orientation Furnace Input MIN. Vent START-UP, ADJUSTMENT, and Safety CheckSidewall Venting GeneralFire and Explosion Hazard Orifice HoleSetup Switch Switch Name Normal Description of USE Position Furnace Setup Switch DescriptionAltitude Derate Multiplier for U.S.A Altitude Percent Derate MultiplierDerate Factor Furnace Overheating Hazard Unit Damage Hazard315AAV Wiring Diagram Seconds G Size of Test Dial Gas Rate CU ft./hrSpecific Gravity of Natural GAS Altitude Range Altitude RangeBTUH/CU FT BTUH/CU Altitude RangeAT Altitude Electrical Operation Hazard Service and Maintenance ProceduresEnvironmental Hazard Electrical SHOCK, Fire or Explosion HazardComponent Self-Test Electrical Controls and WiringCarbon Monoxide Poisoning and Fire Hazard Care and Maintenance Fire or Explosion HazardCleaning and/or Replacing Air Filter Media cabinet filter proceduresFollowing steps should be performed by a qualified Cleaning Heat ExchangerService agency Filter Size Information In. mmIgniter Position Side View Sequence of Operation Inducer Prepurge Period Cooling A/C or Continuous-Fan CF Airflow Selection ChartSingle-Speed Cooling Single-Stage Thermostat and Two-Speed Cooling Adaptive ModeThermidistat Mode Super-Dehumidify ModeContinuous Blower Mode Troubleshooting Heat pumpComponent test Troubleshooting Guide Adapter Kit Werblo Modelinvalid Orselection Description Part Number Accessory ListParts Replacement Information Guide