NOTES FOR FIGURES 27 - 34
1.Heat pump MUST have a high pressure switch for dual fuel applications.
2.Refer to outdoor equipment Installation Instructions for additional information and setup procedure.
3.If the heat pump date code is 1501E or earlier, select the “ZONE” position on the
4.Outdoor Air Temperature Sensor must be attached in all dual fuel applications.
5.Dip switch No. 1 on Thermidistat should be set in OFF position for air conditioner installations. This is factory default.
6.Dip switch No. 1 on Thermidistat should be set in ON position for heat pump installations.
7.Dip switch No. 2 on Thermidistat should be set in OFF position for
8.Dip switch No. 2 on Thermidistat should be set in ON position for
9.Configuration Option No. 10 “Dual Fuel Selection” must be turned ON in all dual fuel applications.
10.NO connection should be made to the furnace HUM terminal when using a Thermidistat.
11.Optional connection: If wire is connected, dip switch
12.Optional connection: If wire is connected, ACRDJ jumper on furnace control should be removed to allow Thermidistat/Thermostat to control outdoor unit staging.
13.Furnace must control its own
14.The RVS Sensing terminal “L” should not be connected. This is internally used to sense defrost operation.
15.DO NOT SELECT the “FURNACE INTERFACE” or “BALANCE POINT” option on the
16.Dip switch D on Dual Fuel Thermostat should be set in OFF position for
17.Dip switch D on Dual Fuel Thermostat should be set in ON position for