Bryant 340MAV instruction manual ÐAttic Location and Working Platform

Page 10

COMBUSTION – AIR

INTAKE

VENT

5 34

MANUAL

SHUTOFF

GAS VALVE

SEDIMENT

TRAP

CONDENSATE

TRAP

A 12-IN. MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH SHORT (5 TO 8 FT) VENT SYSTEMS TO REDUCE EXCESSIVE CONDENSATE DROPLETS FROM

30MIN EXITING THE VENT PIPE. WORK AREA

ACCESS OPENING

FOR TRAP

DRAIN

NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE

FURNACE AND CONDENSATE TRAP WHEN A CONDENSING

FURNACE IS INSTALLED ABOVE FINISHED CEILINGS.

A93031

Fig. 10ÐAttic Location and Working Platform

1.Remove 3 tubes connected to condensate trap.

2.Remove trap from blower shelf by gently pushing tabs inward and rotating trap.

3.Remove casing hole filler cap from casing hole. (See Fig. 2 or 11.)

4.Install casing hole filler cap into blower shelf hole where trap was removed.

5.Install condensate trap into casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.

B.Condensate Trap Tubing

NOTE: See Fig. 11 or tube routing label on main furnace door to check for proper connections.

c.Install cap and clamp on UPPER inducer housing drain connection where molded drain tube was removed.

d.Use inducer housing drain extension tube (violet label and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to conden- sate trap.

e.Determine appropriate length, cut, and connect tube to condensate trap.

f.Clamp tube to prevent any condensate leakage.

3.Relief Port Tube

Refer to Pressure Switch Tubing section for connection procedure.

1.Collector Box Drain Tube

a.Remove factory-installed plug from LOWER collector box drain tube (blue and white striped label).

b.Install removed clamp and plug into UPPER collector box drain tube (blue label) which was previously con- nected to condensate trap.

c.Connect LOWER collector box drain tube (blue and white striped label) to condensate trap. Tube does not need to be cut.

d.Clamp tube to prevent any condensate leakage.

2.Inducer Housing Drain Tube

a.Remove factory-installed cap and clamp from LOWER inducer housing drain connection.

b.Remove and discard UPPER (molded) inducer housing drain tube which was previously connected to conden- sate trap.

Ð10Ð

C. Condensate Trap Field Drain Attachment

Refer to Condensate Drain section for recommendations and procedures.

D. Pressure Switch Tubing

One collector box pressure tube (pink label) is factory connected to the pressure switch for use when furnace is installed in UPFLOW applications. This tube MUST be disconnected and used for the condensate trap relief port tube. The other collector box pressure tube (green label) which was factory connected to the condensate trap relief port connection MUST be connected to the pressure switch in DOWNFLOW or HORIZONTAL RIGHT applications.

NOTE: See Fig. 11 or tube routing label on main furnace door to check for proper connections.

Relocate tubes as described below.

1.Disconnect collector box pressure tube (pink label) attached to pressure switch.

Image 10 Contents
Ð1Ð ÐMultipoise OrientationsÐ2Ð DimensionsUnit Size Minimum Inches Clearance to Combustible Construction Safety ConsiderationsElectrostatic Discharge ESD Precautions → ÐClearances to CombustiblesII. Upflow Applications IntroductionApplications General Condensate Trap Location Factory-Shipped OrientationÐ5Ð Condensate Trap Location Alternate Upflow Orientation Pressure Switch Tubing Ð6ÐCondensate Trap Location Condensate Trap Freeze ProtectionIII Downflow Applications Condensate Trap TubingIV. Horizontal Left SUPPLY-AIR Discharge Applications Ð8ÐConstruct a Working Platform Ð9ÐHorizontal Right SUPPLY-AIR Discharge Applications ÐAttic Location and Working Platform → ÐHorizontal Right Tube Configuration LocationII. Furnace Location Relative to Cooling Equipment III. Hazardous LocationsInstallation Leveling Legs if Desired → II. Installation in Upflow or Downflow ApplicationsFurnace Plenum Opening Floor Opening Casing Ðopening DimensionsWidth III. Installation in Horizontal Applications ÐDuct FlangesÐfilter Information IV. Filter ArrangementBottom Closure Panel Ðmaximum Capacity of Pipe WiringVI. GAS Piping Electrical Connections→ ÐHeating and Cooling Application Wiring Diagram II -V WiringÐWiring Diagram Amps Gage III. AccessoriesÐelectrical Data AmpsII. COMBUSTION-AIR and Vent Piping Direct VentingRemoval of Existing Furnaces from Common Vent Systems GeneralExample Combustion-Air and Vent Pipe DiameterCombustion-Air and Vent Pipe Attachment COMBUSTION-AIR Intake Housing Plug Fitting ÐShort Vent 5 to 8 Ft SystemÐmaximum Allowable Pipe Length FT 2001 toÐmaximum Allowable Pipe Length FT 4001 to 5000³Vent Extension Pipe 8001 to 9000³Extended Exposed Sidewall Pipes Two-Pipe Termination KitÐRoof Termination Preferred Condensate Drain General Concentric Vent/Air Termination KitIV. Multiventing and Vent Terminations II. ApplicationÐConcentric Vent and Combustion-Air Sequence of Operation Heating ModeIII. Condensate Drain Protection IV. Heat Pump Mode II. Cooling ModeIII. Continuous Blower Mode Component TestSTART-UP Procedures General II. Prime Condensate Trap with WaterIII. Purge GAS Lines IV. AdjustmentsSet Gas Input Rate BTU/CU FT Ð36Ð Ð37Ð Ð38Ð Ð39Ð Ðaltitude Derate Multiplier for U.S.A Set Temperature RiseUnited States CanadaChecklist Check Safety Controls Check Primary Limit ControlII. Check Pressure Switch Ðspeed SelectorLoad Calculation ChecklistðinstallationCHECKLISTÐSTART-UP Combustion and Vent PipingÐ43Ð Service Training
Related manuals
Manual 12 pages 2.16 Kb Manual 48 pages 30.25 Kb