Bryant 340MAV instruction manual Ð5Ð, Condensate Trap Location Alternate Upflow Orientation

Page 5

BLOWER SHELF

FURNACE

 

CONDENSATE

 

 

DOOR

 

 

 

 

TRAP

 

CONDENSATE

 

 

FURNACE

 

 

 

TRAP (INSIDE)

 

 

FURNACE

DOOR

 

 

 

 

 

 

 

SIDE

 

 

 

 

4 78

4

 

 

 

 

5 3 4

 

 

 

 

4

 

 

26 1 4

11 2

26 1 4

 

FIELD

FIELD

 

DRAIN

 

 

DRAIN

ALTERNATE DRAIN

CONN

 

 

CONN

TUBE LOCATION

 

 

 

 

FURNACE SIDE

5 3 4

3 4

CONDENSATE TRAP

 

 

 

 

 

 

 

 

 

 

 

 

SIDE VIEW

 

 

 

 

 

FRONT VIEW

END VIEW

FRONT VIEW

DRAIN TUBE LOCATION

 

 

 

 

 

 

 

 

 

 

 

DOWNFLOW AND ALTERNATE

HORIZONTAL

 

 

 

 

 

 

 

 

 

 

 

 

UPFLOW APPLICATIONS

 

 

 

 

 

 

 

 

 

EXTERNAL UPFLOW APPLICATIONS

APPLICATIONS

 

SLOT FOR SCREW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HORIZONTAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

APPLICATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14 OD

 

 

 

 

 

 

 

 

(OPTIONAL)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COLLECTOR BOX TO

 

 

11 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRAP RELIEF PORT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12 OD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INDUCER HOUSING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRAIN CONNECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

58 OD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COLLECTOR BOX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

71 8

 

 

 

 

 

 

 

 

 

 

DRAIN CONNECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SCREW HOLE FOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPFLOW OR DOWN-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7 8

 

 

 

 

 

 

 

 

 

 

 

 

 

FLOW APPLICATIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WIRE TIE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(OPTIONAL)

 

 

 

 

 

 

 

 

21 4

 

 

 

 

 

 

 

 

GUIDES

 

 

 

 

 

 

 

 

 

 

 

12-IN. PVC OR CPVC

 

 

 

 

 

 

 

 

 

 

 

 

 

(WHEN USED)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FRONT VIEW

 

SIDE VIEW

 

 

A93026

Fig. 4ÐCondensate Trap

and also by a color label on each tube. These tubes are identified as follows: collector box drain tube (blue label), inducer housing drain tube (violet label or molded), relief port tube (green label), and pressure switch tube (pink label).

2.Condensate Trap Drain Tube

The condensate trap drain connection must be extended for field attachment by doing the following:

a.Determine location of field drain connection. (See Fig. 2 or 5.)

NOTE: If internal filter is used, drain tube should be located to opposite side of casing of return duct attachment to assist in filter removal.

b.Remove and discard casing drain hole plug button from desired side.

c.Install drain tube coupling grommet (factory-supplied in loose parts bag) in selected casing hole.

d.Slide drain tube coupling (factory-supplied in loose parts bag) through grommet ensuring long end of coupling faces blower.

e.Cement 2 factory-supplied 1/2-in. street CPVC elbows to the rigid drain tube connection on the condensate trap. (See Fig. 5.) These elbows must be cemented together and cemented to condensate trap drain connection.

NOTE: Failure to use CPVC elbows may allow drain to kink and prevent draining.

Ð5Ð

f.Connect larger diameter drain tube and clamp (factory- supplied in loose parts bag) to condensate trap and clamp securely.

g.Route tube to coupling and cut to appropriate length.

h.Attach tube to coupling and clamp securely.

C.Condensate Trap Location (Alternate Upflow Orientation)

An alternate location for the condensate trap is the left-hand side of casing. (See Fig. 2 and 6.)

NOTE: If the alternate left-hand side of casing location is used, the factory-connected drain and relief port tubes must be discon- nected and modified for attachment. See Condensate Trap Tubing (Alternate Upflow Orientation) section for tubing attachment.

To relocate condensate trap to the left-hand side, perform the following:

1.Remove 3 tubes connected to condensate trap.

2.Remove trap from blower shelf by gently pushing tabs inward and rotating trap.

3.Remove casing hole filler cap from casing hole. (See Fig. 2 or 6.)

4.Install casing hole filler cap into blower shelf hole where trap was removed.

5.Install condensate trap into left-hand side casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.

Image 5
Contents ÐMultipoise Orientations Ð1ÐUnit Size DimensionsÐ2Ð Electrostatic Discharge ESD Precautions Safety ConsiderationsMinimum Inches Clearance to Combustible Construction → ÐClearances to CombustiblesApplications General IntroductionII. Upflow Applications Condensate Trap Location Factory-Shipped OrientationCondensate Trap Location Alternate Upflow Orientation Ð5ÐÐ6Ð Pressure Switch TubingIII Downflow Applications Condensate Trap Freeze ProtectionCondensate Trap Location Condensate Trap TubingÐ8Ð IV. Horizontal Left SUPPLY-AIR Discharge ApplicationsHorizontal Right SUPPLY-AIR Discharge Applications Ð9ÐConstruct a Working Platform ÐAttic Location and Working Platform Location → ÐHorizontal Right Tube ConfigurationIII. Hazardous Locations II. Furnace Location Relative to Cooling Equipment→ II. Installation in Upflow or Downflow Applications Installation Leveling Legs if DesiredWidth Ðopening DimensionsFurnace Plenum Opening Floor Opening Casing ÐDuct Flanges III. Installation in Horizontal ApplicationsBottom Closure Panel IV. Filter ArrangementÐfilter Information VI. GAS Piping WiringÐmaximum Capacity of Pipe Electrical ConnectionsII -V Wiring → ÐHeating and Cooling Application Wiring DiagramÐWiring Diagram Ðelectrical Data III. AccessoriesAmps Gage AmpsRemoval of Existing Furnaces from Common Vent Systems Direct VentingII. COMBUSTION-AIR and Vent Piping GeneralCombustion-Air and Vent Pipe Attachment Combustion-Air and Vent Pipe DiameterExample ÐShort Vent 5 to 8 Ft System COMBUSTION-AIR Intake Housing Plug Fitting2001 to Ðmaximum Allowable Pipe Length FT4001 to 5000³ Ðmaximum Allowable Pipe Length FT8001 to 9000³ Vent Extension PipeTwo-Pipe Termination Kit Extended Exposed Sidewall PipesÐRoof Termination Preferred IV. Multiventing and Vent Terminations Concentric Vent/Air Termination KitCondensate Drain General II. ApplicationÐConcentric Vent and Combustion-Air III. Condensate Drain Protection Heating ModeSequence of Operation III. Continuous Blower Mode II. Cooling ModeIV. Heat Pump Mode Component TestII. Prime Condensate Trap with Water START-UP Procedures GeneralSet Gas Input Rate IV. AdjustmentsIII. Purge GAS Lines BTU/CU FT Ð36Ð Ð37Ð Ð38Ð Ð39Ð United States Set Temperature RiseÐaltitude Derate Multiplier for U.S.A CanadaII. Check Pressure Switch Check Safety Controls Check Primary Limit ControlChecklist Ðspeed SelectorCHECKLISTÐSTART-UP ChecklistðinstallationLoad Calculation Combustion and Vent PipingÐ43Ð Service Training
Related manuals
Manual 12 pages 2.16 Kb Manual 48 pages 30.25 Kb

340MAV specifications

The Bryant 340MAV is a standout model in the Bryant lineup, designed to provide exceptional comfort, efficiency, and performance for residential heating and cooling needs. This unit offers a perfect blend of innovative technology and user-friendly features, making it an ideal choice for homeowners seeking reliability and quality.

One of the defining characteristics of the Bryant 340MAV is its impressive efficiency rating. With a SEER (Seasonal Energy Efficiency Ratio) of up to 18, this model ensures that homeowners can enjoy effective cooling during the summer months while minimizing energy consumption. Similarly, the heating efficiency is notable, with a high AFUE (Annual Fuel Utilization Efficiency) rating. This makes the 340MAV an environmentally friendly option that also promotes cost savings on energy bills.

The 340MAV incorporates advanced technologies that enhance its performance. One such technology is the variable-speed compressor, which allows the system to adjust its output based on the demands of the home. This means that the unit operates more quietly and reduces energy usage by matching the cooling or heating output required. Additionally, the two-stage heating capability provides more consistent temperatures and improved comfort throughout the space.

Operating noise is a crucial factor in residential HVAC systems, and the Bryant 340MAV is designed with this in mind. Engineered for quiet operation, the unit features a sound-dampening design, including an insulated cabinet and a specially designed compressor that minimizes noise levels. Homeowners can enjoy a comfortable indoor climate without the disruptive racket often associated with traditional systems.

Furthermore, the Bryant 340MAV is equipped with a durable all-aluminum coil, which improves heat transfer efficiency while also being resistant to corrosion. This characteristic contributes to the longevity of the unit, ensuring that it can withstand various environmental factors without compromising performance.

Another key feature is the advanced control options that the Bryant 340MAV offers. Integration with smart thermostats allows homeowners to monitor and adjust their HVAC system remotely, ensuring optimal comfort at all times. Additionally, the system is compatible with Bryant's Perfect Air™ filtration system, enhancing indoor air quality by reducing pollutants and allergens.

In summary, the Bryant 340MAV is a high-efficiency heating and cooling solution that brings together cutting-edge technology, quiet operation, and user-friendly features. With its focus on comfort and energy savings, it stands out as a prime choice for homeowners looking to invest in a reliable HVAC system.