Bryant 340MAV instruction manual Combustion-Air and Vent Pipe Diameter, Example

Page 22

NOTE: Select 1 vent pipe connection and

NOTE: Select 1 vent pipe connection and

1 combustion-air pipe connection.

1 combustion-air pipe connection.

AIR

 

 

 

 

COMBUSTION- FLOW COMBUSTION-

 

 

 

AIR

AIR

VENT

 

 

VENT

 

 

 

VENT

 

 

 

 

 

VENT

 

 

 

 

 

COMBUSTION-

COMBUSTION-

 

 

AIR

AIR

AIR

 

 

 

 

 

 

 

FLOW

 

UPFLOW

 

DOWNFLOW

 

 

 

 

COMBUSTION-

COMBUSTION-

 

 

AIR

 

 

 

 

 

AIR

 

 

VENT

 

VENT

 

 

 

AIR

 

 

 

AIR

FLOW

 

 

 

FLOW

HORIZONTAL-LEFT DISCHARGE

HORIZONTAL-RIGHT DISCHARGE

A96187

Fig. 27ÐCombustion-Air and Vent Pipe Connections

CAUTION: When combustion-air pipe is installed above a suspended ceiling, pipe must be insulated with 3/8-in. thick Armaflex-type insulation. Combustion-air pipe should also be insulated when it passes through warm, humid space.

CAUTION: When vent pipe is exposed to temperatures below freezing, such as when it passes through an unheated space or when a chimney is used as a raceway, pipe must be insulated as shown in Table 7 with Armaflex-type insulation.

CAUTION: Combustion air must not be taken from inside structure because inside air is frequently contami- nated by halogens, which include fluorides, chlorides, bromides, and iodides. These elements are found in aerosols, detergents, bleaches, cleaning solvents, salts, air fresheners, adhesives, paint, and other household prod- ucts. Locate combustion-air inlet as far as possible from swimming pool and swimming pool pump house.

Excessive exposure to contaminated combustion air will result in safety and performance related problems.

WARNING: Solvent cements are combustible. Keep away from heat, sparks, and open flame. Use only in well-ventilated areas. Avoid breathing in vapor or allow- ing contact with skin or eyes. Failure to follow this warning could result in fire, property damage, personal injury, or death.

WARNING: All combustion-air and vent pipes must be airtight and watertight. Pipes must also terminate exactly as shown in Fig. 30, 31, 32, 33, or 34. Failure to follow this warning could result in property damage, personal injury, or death.

NOTE: The minimum combustion-air and vent pipe length (each) for these furnaces is 5 ft. Short pipe lengths (5-8 ft) may discharge water droplets. These droplets may be undesirable, and a 12-in. minimum offset pipe section is recommended, as shown in Fig. 28, to reduce excessive droplets from exiting vent pipe outlet.

B.Combustion-Air and Vent Pipe Diameter

Determine combustion-air and vent pipe diameter.

1.Using Table 6, individually determine the combustion-air and vent pipe diameters. Pick the larger of these 2 pipe diameters and use this diameter for both combustion-air and vent pipes.

2.When installing vent systems of short pipe length, use the smallest allowable pipe diameter. Do not use pipe size greater than required or incomplete combustion, flame disturbance, or flame sense lockout may occur.

NOTE: Do not count elbows or pipe sections in terminations or within furnace. See shaded areas in Fig. 30, 31, 32, 33, and 34.

EXAMPLE:

An 036080 size furnace located in Indianapolis, elevation 650 ft above sea level, could be installed in an application requiring 3 elbows and 32 ft of vent pipe, along with 5 elbows and 34 ft of combustion-air pipe. Table 6 indicates this application would allow a 2-in. diameter vent pipe, but require a 2-1/2 in. diameter combustion air pipe (2-in. pipe is good for 35 ft with 3 elbows, but only 30 ft with 5 elbows). Therefore, 2-1/2 in. diameter pipe must be used for both vent and combustion-air pipes since larger required diameter must always be used for both pipes. If same installation were in Albuquerque, elevation 5250 ft above sea level, installation would require 2-1/2 in. vent pipe and combustion-air pipe. At 5001- to 6000-ft elevation, 2-in. pipe is only good for 17 ft with 5 elbows, and 2-1/2 in. pipe is good for 70 ft with 5 elbows.

C.Combustion-Air and Vent Pipe Attachment

NOTE: All pipe joints must be watertight except attachment of combustion-air pipe to inlet housing connection, since it may be necessary to remove pipe for servicing.

1.Attach combustion-air pipe as follows:

a.Determine location of combustion-air intake pipe con- nection to combustion-air intake housing as shown in Fig. 27 for application.

b.Reposition combustion-air intake housing plug fitting in appropriate unused intake housing connection.

c. If required, insert perforated disk assembly (factory- supplied in loose parts bag) in intake housing where combustion-air intake pipe will be connected. If half disk set is required, install with shoulder of disk against stop in combustion-air inlet.

d.Install pipe support (factory-supplied in loose parts bag) into selected furnace casing combustion-air pipe hole. Pipe support should be positioned at bottom of casing hole.

e.Insert 2-in. diameter pipe into intake housing.

NOTE: A 2-in. diameter pipe must be used within the furnace casing. Make all pipe diameter transitions outside furnace casing.

Ð22Ð

Image 22
Contents Ð1Ð ÐMultipoise OrientationsÐ2Ð DimensionsUnit Size Minimum Inches Clearance to Combustible Construction Safety ConsiderationsElectrostatic Discharge ESD Precautions → ÐClearances to CombustiblesII. Upflow Applications IntroductionApplications General Condensate Trap Location Factory-Shipped OrientationÐ5Ð Condensate Trap Location Alternate Upflow OrientationPressure Switch Tubing Ð6ÐCondensate Trap Location Condensate Trap Freeze ProtectionIII Downflow Applications Condensate Trap TubingIV. Horizontal Left SUPPLY-AIR Discharge Applications Ð8ÐConstruct a Working Platform Ð9ÐHorizontal Right SUPPLY-AIR Discharge Applications ÐAttic Location and Working Platform → ÐHorizontal Right Tube Configuration LocationII. Furnace Location Relative to Cooling Equipment III. Hazardous LocationsInstallation Leveling Legs if Desired → II. Installation in Upflow or Downflow ApplicationsFurnace Plenum Opening Floor Opening Casing Ðopening DimensionsWidth III. Installation in Horizontal Applications ÐDuct FlangesÐfilter Information IV. Filter ArrangementBottom Closure Panel Ðmaximum Capacity of Pipe WiringVI. GAS Piping Electrical Connections→ ÐHeating and Cooling Application Wiring Diagram II -V WiringÐWiring Diagram Amps Gage III. AccessoriesÐelectrical Data AmpsII. COMBUSTION-AIR and Vent Piping Direct VentingRemoval of Existing Furnaces from Common Vent Systems GeneralExample Combustion-Air and Vent Pipe DiameterCombustion-Air and Vent Pipe Attachment COMBUSTION-AIR Intake Housing Plug Fitting ÐShort Vent 5 to 8 Ft SystemÐmaximum Allowable Pipe Length FT 2001 toÐmaximum Allowable Pipe Length FT 4001 to 5000³Vent Extension Pipe 8001 to 9000³Extended Exposed Sidewall Pipes Two-Pipe Termination KitÐRoof Termination Preferred Condensate Drain General Concentric Vent/Air Termination KitIV. Multiventing and Vent Terminations II. ApplicationÐConcentric Vent and Combustion-Air Sequence of Operation Heating ModeIII. Condensate Drain Protection IV. Heat Pump Mode II. Cooling ModeIII. Continuous Blower Mode Component TestSTART-UP Procedures General II. Prime Condensate Trap with WaterIII. Purge GAS Lines IV. AdjustmentsSet Gas Input Rate BTU/CU FT Ð36Ð Ð37Ð Ð38Ð Ð39Ð Ðaltitude Derate Multiplier for U.S.A Set Temperature RiseUnited States CanadaChecklist Check Safety Controls Check Primary Limit ControlII. Check Pressure Switch Ðspeed SelectorLoad Calculation ChecklistðinstallationCHECKLISTÐSTART-UP Combustion and Vent PipingÐ43Ð Service Training
Related manuals
Manual 12 pages 2.16 Kb Manual 48 pages 30.25 Kb

340MAV specifications

The Bryant 340MAV is a standout model in the Bryant lineup, designed to provide exceptional comfort, efficiency, and performance for residential heating and cooling needs. This unit offers a perfect blend of innovative technology and user-friendly features, making it an ideal choice for homeowners seeking reliability and quality.

One of the defining characteristics of the Bryant 340MAV is its impressive efficiency rating. With a SEER (Seasonal Energy Efficiency Ratio) of up to 18, this model ensures that homeowners can enjoy effective cooling during the summer months while minimizing energy consumption. Similarly, the heating efficiency is notable, with a high AFUE (Annual Fuel Utilization Efficiency) rating. This makes the 340MAV an environmentally friendly option that also promotes cost savings on energy bills.

The 340MAV incorporates advanced technologies that enhance its performance. One such technology is the variable-speed compressor, which allows the system to adjust its output based on the demands of the home. This means that the unit operates more quietly and reduces energy usage by matching the cooling or heating output required. Additionally, the two-stage heating capability provides more consistent temperatures and improved comfort throughout the space.

Operating noise is a crucial factor in residential HVAC systems, and the Bryant 340MAV is designed with this in mind. Engineered for quiet operation, the unit features a sound-dampening design, including an insulated cabinet and a specially designed compressor that minimizes noise levels. Homeowners can enjoy a comfortable indoor climate without the disruptive racket often associated with traditional systems.

Furthermore, the Bryant 340MAV is equipped with a durable all-aluminum coil, which improves heat transfer efficiency while also being resistant to corrosion. This characteristic contributes to the longevity of the unit, ensuring that it can withstand various environmental factors without compromising performance.

Another key feature is the advanced control options that the Bryant 340MAV offers. Integration with smart thermostats allows homeowners to monitor and adjust their HVAC system remotely, ensuring optimal comfort at all times. Additionally, the system is compatible with Bryant's Perfect Airâ„¢ filtration system, enhancing indoor air quality by reducing pollutants and allergens.

In summary, the Bryant 340MAV is a high-efficiency heating and cooling solution that brings together cutting-edge technology, quiet operation, and user-friendly features. With its focus on comfort and energy savings, it stands out as a prime choice for homeowners looking to invest in a reliable HVAC system.