Bryant 340MAV instruction manual Condensate Trap Freeze Protection, III Downflow Applications, Ð7Ð

Page 7

H. Condensate Trap Freeze Protection

 

c. Connect

LOWER collector box drain connection to

Refer to Condensate Drain Protection section for recommenda-

 

condensate trap.

 

 

 

 

tions and procedures.

 

 

(1.)

Condensate Trap Located on Left Side of Casing

 

 

 

 

III.

DOWNFLOW APPLICATIONS

 

 

 

(a.) Connect LOWER collector box

drain

tube

 

 

 

 

 

A downflow furnace application is where furnace blower is located

 

 

 

(blue and white striped label) to condensate

above combustion and controls section of furnace, and conditioned

 

 

 

trap. Tube does not need to be cut.

 

 

air is discharged downwards.

 

 

 

(b.)

Clamp tube to prevent any condensate leakage.

A.

Condensate Trap Location

 

 

 

 

 

(2.)

Condensate Trap Located on Right Side of Casing

The condensate trap must be removed from the factory-installed

 

 

 

(a.)

Install drain tube coupling (factory-supplied in

blower shelf location and relocated in selected application location

 

 

 

 

 

loose parts bag) into collector box drain tube

as shown in Fig. 2, 7, or 8.

 

 

 

 

 

 

 

 

(blue and white striped label) which was pre-

To

relocate condensate trap from the

blower shelf to desired

 

 

 

 

 

 

viously plugged.

 

 

 

location, perform the following:

 

 

 

 

 

 

 

 

 

 

(b.) Connect larger diameter drain tube (factory-

 

1. Remove 3 tubes connected to condensate trap.

 

 

 

 

 

 

supplied

in loose parts bag)

to

drain

tube

 

2. Remove trap from blower shelf

by gently pushing tabs

 

 

 

 

 

 

 

coupling,

extending collector

box

drain

tube

 

inward and rotating trap.

 

 

 

 

 

 

 

 

 

for connection to condensate trap.

 

 

 

3. Remove casing hole filler cap from casing hole. (See Fig. 2,

 

 

 

 

 

 

(c.)

Route extended collector box

drain tube di-

 

7, or 8.)

 

 

 

 

 

 

 

rectly from collector box drain to condensate

 

4. Install casing hole filler cap into blower shelf hole where

 

 

 

 

 

 

 

trap as shown in Fig. 8.

 

 

 

 

trap was removed.

 

 

 

 

 

 

 

 

 

 

 

(d.)

Determine appropriate length and cut.

 

 

5. Install condensate trap into desired casing hole by inserting

 

 

 

 

 

 

(e.)

Connect to condensate trap.

 

 

 

 

tube connection stubs through casing hole and rotating until

 

 

 

 

 

 

tabs snap into locking position.

 

 

 

(f.)

Clamp tube to prevent any condensate leakage.

 

 

 

 

 

B.Condensate Trap Tubing

NOTE: See Fig. 7 or 8 or tube routing label on main furnace door to check for proper connections.

1.Collector Box Drain Tube

a.Remove factory-installed plug from LOWER collector box drain tube (blue and white striped label).

b.Install removed clamp and plug into UPPER collector box drain tube (blue label) which was connected to condensate trap.

2.Inducer Housing Drain Tube

a.Remove factory-installed cap and clamp from LOWER inducer housing drain connection.

b.Remove and discard UPPER (molded) inducer housing drain tube which was previously connected to conden- sate trap.

c.Install cap and clamp on UPPER inducer housing drain connection where molded drain tube was removed.

COLLECTOR BOX

DRAIN TUBE (BLUE)

CAP

PLUG

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX

EXTENSION TUBE

COLLECTOR BOX

TUBE (PINK)

COLLECTOR BOX

DRAIN TUBE (BLUE

& WHITE STRIPED)

COLLECTOR BOX

EXTENSION TUBE

CONDENSATE

TRAP

INDUCER HOUSING

DRAIN TUBE (VIOLET)

A96196

Fig. 7ÐDownflow Tube Configuration

(Left-Hand Trap Installation)

Ð7Ð

PLUG

CAP

COLLECTOR BOX

DRAIN TUBE (BLUE)

COLLECTOR BOX

TUBE (PINK)

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX

EXTENSION TUBE

COLLECTOR BOX

DRAIN TUBE (BLUE

& WHITE STRIPED)

COLLECTOR BOX

EXTENSION TUBE

INDUCER HOUSING

DRAIN TUBE

(VIOLET)

CONDENSATE

TRAP

COLLECTOR BOX

EXTENSION

DRAIN TUBE

DRAIN TUBE

COUPLING

A96197

Fig. 8ÐDownflow Tube Configuration

(Right-Hand Trap Installation)

Image 7
Contents ÐMultipoise Orientations Ð1ÐÐ2Ð DimensionsUnit Size → ÐClearances to Combustibles Safety ConsiderationsElectrostatic Discharge ESD Precautions Minimum Inches Clearance to Combustible ConstructionCondensate Trap Location Factory-Shipped Orientation IntroductionApplications General II. Upflow ApplicationsCondensate Trap Location Alternate Upflow Orientation Ð5ÐÐ6Ð Pressure Switch TubingCondensate Trap Tubing Condensate Trap Freeze ProtectionIII Downflow Applications Condensate Trap LocationÐ8Ð IV. Horizontal Left SUPPLY-AIR Discharge ApplicationsConstruct a Working Platform Ð9ÐHorizontal Right SUPPLY-AIR Discharge Applications ÐAttic Location and Working Platform Location → ÐHorizontal Right Tube ConfigurationIII. Hazardous Locations II. Furnace Location Relative to Cooling Equipment→ II. Installation in Upflow or Downflow Applications Installation Leveling Legs if DesiredFurnace Plenum Opening Floor Opening Casing Ðopening DimensionsWidth ÐDuct Flanges III. Installation in Horizontal ApplicationsÐfilter Information IV. Filter ArrangementBottom Closure Panel Electrical Connections WiringVI. GAS Piping Ðmaximum Capacity of PipeII -V Wiring → ÐHeating and Cooling Application Wiring DiagramÐWiring Diagram Amps III. AccessoriesÐelectrical Data Amps GageGeneral Direct VentingRemoval of Existing Furnaces from Common Vent Systems II. COMBUSTION-AIR and Vent PipingExample Combustion-Air and Vent Pipe DiameterCombustion-Air and Vent Pipe Attachment ÐShort Vent 5 to 8 Ft System COMBUSTION-AIR Intake Housing Plug Fitting2001 to Ðmaximum Allowable Pipe Length FT4001 to 5000³ Ðmaximum Allowable Pipe Length FT8001 to 9000³ Vent Extension PipeTwo-Pipe Termination Kit Extended Exposed Sidewall PipesÐRoof Termination Preferred II. Application Concentric Vent/Air Termination KitIV. Multiventing and Vent Terminations Condensate Drain GeneralÐConcentric Vent and Combustion-Air Sequence of Operation Heating ModeIII. Condensate Drain Protection Component Test II. Cooling ModeIII. Continuous Blower Mode IV. Heat Pump ModeII. Prime Condensate Trap with Water START-UP Procedures GeneralIII. Purge GAS Lines IV. AdjustmentsSet Gas Input Rate BTU/CU FT Ð36Ð Ð37Ð Ð38Ð Ð39Ð Canada Set Temperature RiseUnited States Ðaltitude Derate Multiplier for U.S.AÐspeed Selector Check Safety Controls Check Primary Limit ControlII. Check Pressure Switch ChecklistCombustion and Vent Piping ChecklistðinstallationCHECKLISTÐSTART-UP Load CalculationÐ43Ð Service Training
Related manuals
Manual 12 pages 2.16 Kb Manual 48 pages 30.25 Kb

340MAV specifications

The Bryant 340MAV is a standout model in the Bryant lineup, designed to provide exceptional comfort, efficiency, and performance for residential heating and cooling needs. This unit offers a perfect blend of innovative technology and user-friendly features, making it an ideal choice for homeowners seeking reliability and quality.

One of the defining characteristics of the Bryant 340MAV is its impressive efficiency rating. With a SEER (Seasonal Energy Efficiency Ratio) of up to 18, this model ensures that homeowners can enjoy effective cooling during the summer months while minimizing energy consumption. Similarly, the heating efficiency is notable, with a high AFUE (Annual Fuel Utilization Efficiency) rating. This makes the 340MAV an environmentally friendly option that also promotes cost savings on energy bills.

The 340MAV incorporates advanced technologies that enhance its performance. One such technology is the variable-speed compressor, which allows the system to adjust its output based on the demands of the home. This means that the unit operates more quietly and reduces energy usage by matching the cooling or heating output required. Additionally, the two-stage heating capability provides more consistent temperatures and improved comfort throughout the space.

Operating noise is a crucial factor in residential HVAC systems, and the Bryant 340MAV is designed with this in mind. Engineered for quiet operation, the unit features a sound-dampening design, including an insulated cabinet and a specially designed compressor that minimizes noise levels. Homeowners can enjoy a comfortable indoor climate without the disruptive racket often associated with traditional systems.

Furthermore, the Bryant 340MAV is equipped with a durable all-aluminum coil, which improves heat transfer efficiency while also being resistant to corrosion. This characteristic contributes to the longevity of the unit, ensuring that it can withstand various environmental factors without compromising performance.

Another key feature is the advanced control options that the Bryant 340MAV offers. Integration with smart thermostats allows homeowners to monitor and adjust their HVAC system remotely, ensuring optimal comfort at all times. Additionally, the system is compatible with Bryant's Perfect Air™ filtration system, enhancing indoor air quality by reducing pollutants and allergens.

In summary, the Bryant 340MAV is a high-efficiency heating and cooling solution that brings together cutting-edge technology, quiet operation, and user-friendly features. With its focus on comfort and energy savings, it stands out as a prime choice for homeowners looking to invest in a reliable HVAC system.