Bryant 340MAV instruction manual → ÐHeating and Cooling Application Wiring Diagram, II -V Wiring

Page 18

FIELD 24-VOLT WIRING

FIELD 115-, 208/230-, 460-VOLT WIRING

FACTORY 24-VOLT WIRING

FACTORY 115-VOLT WIRING

 

 

 

NOTE 2

 

 

 

THERMOSTAT

 

 

 

FIVE

W

C R

G

Y

FIELD-SUPPLIED

 

 

TERMINALS

 

 

 

 

 

 

 

 

WIRE

 

 

 

 

 

FUSED DISCONNECT

 

 

THREE-WIRE

 

 

 

 

 

208/230- OR

 

 

HEATING-

 

 

 

 

 

 

 

ONLY

 

 

 

 

 

460-VOLT

 

 

 

 

 

 

 

 

THREE

BLK

BLK

 

W

 

 

 

 

PHASE

 

 

 

 

 

 

 

 

 

 

 

 

 

WHT

WHT

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-

GND

 

GND

 

 

 

 

 

VOLT

115-VOLT FUSED

AUXILIARY

G

 

 

 

 

SINGLE

 

 

 

 

 

PHASE

DISCONNECT

J-BOX

C

NOTE 1

 

 

 

GND

SWITCH

 

CONTROL

Y

 

 

CONDENSING

(WHEN

 

BOX

 

 

 

UNIT

 

 

 

 

 

 

 

REQUIRED)

 

24-VOLT

 

 

 

TWO

 

 

 

 

 

 

 

 

 

TERMINAL

 

 

 

WIRE

 

 

 

 

BLOCK

NOTES: 1.

Connect Y-terminal as shown for proper operation.

 

 

FURNACE

 

 

 

2.￿ Some thermostats require a "C" terminal connection as shown.

 

 

 

 

 

3.If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.

A96415

Fig. 22ÐHeating and Cooling Application Wiring Diagram

ELECTRIC

DISCONNECT

SWITCH

COPPER

WIRE ONLY

ALUMINUM

WIRE

A93033

CAUTION: Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire.

NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control center LED status indicator light will flash rapidly and furnace will NOT operate.

FACTORY INSTALLED LOCATION

ALTERNATE

FIELD

LOCATION

A93051

Fig. 23ÐRelocating J-Box

WARNING: The cabinet MUST have an uninterrupted or unbroken ground according to NEC ANSI/NFPA 70-1996 and Canadian Electrical Code CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire or conduit approved for electrical ground when installed in accordance with existing electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in electrical shock, fire, or death.

J-BOX RELOCATION

1.Remove 2 screws holding auxiliary J-box. (See Fig. 23.)

2.Rotate J-box 180° and attach box to right side, using holes provided.

Ð18Ð

CAUTION: If manual disconnect switch is to be mounted on furnace, select a location where a drill or fastener will not contact electrical or gas components.

II.24-V WIRING

Make field 24-v thermostat connections at 24-v terminal block on control center. For proper cooling operation, Y wire from thermo- stat MUST be connected to Y terminal on control center, as shown in Fig. 22. The 24-v terminal board is marked for easy connection of field wiring. (See Fig. 24.) The 24-v circuit contains a 3-amp, automotive-type fuse located on control center. (See Fig. 25.) Any electrical shorts of 24-v wiring during installation, service, or maintenance may cause fuse to blow. If fuse replacement is required, use only a fuse of identical size (3 amp).

NOTE: Use AWG No. 18 color-coded copper thermostat wire for lengths up to 100 ft. For wire lengths over 100 ft, use AWG No. 16 wire.

Image 18 Contents
Ð1Ð ÐMultipoise OrientationsDimensions Ð2ÐUnit Size Minimum Inches Clearance to Combustible Construction Safety ConsiderationsElectrostatic Discharge ESD Precautions → ÐClearances to CombustiblesII. Upflow Applications IntroductionApplications General Condensate Trap Location Factory-Shipped OrientationÐ5Ð Condensate Trap Location Alternate Upflow OrientationPressure Switch Tubing Ð6ÐCondensate Trap Location Condensate Trap Freeze ProtectionIII Downflow Applications Condensate Trap TubingIV. Horizontal Left SUPPLY-AIR Discharge Applications Ð8ÐÐ9Ð Construct a Working PlatformHorizontal Right SUPPLY-AIR Discharge Applications ÐAttic Location and Working Platform → ÐHorizontal Right Tube Configuration LocationII. Furnace Location Relative to Cooling Equipment III. Hazardous LocationsInstallation Leveling Legs if Desired → II. Installation in Upflow or Downflow Applications Ðopening Dimensions Furnace Plenum Opening Floor Opening Casing Width III. Installation in Horizontal Applications ÐDuct FlangesIV. Filter Arrangement Ðfilter InformationBottom Closure Panel Ðmaximum Capacity of Pipe WiringVI. GAS Piping Electrical Connections→ ÐHeating and Cooling Application Wiring Diagram II -V WiringÐWiring Diagram Amps Gage III. AccessoriesÐelectrical Data AmpsII. COMBUSTION-AIR and Vent Piping Direct VentingRemoval of Existing Furnaces from Common Vent Systems GeneralCombustion-Air and Vent Pipe Diameter ExampleCombustion-Air and Vent Pipe Attachment COMBUSTION-AIR Intake Housing Plug Fitting ÐShort Vent 5 to 8 Ft SystemÐmaximum Allowable Pipe Length FT 2001 toÐmaximum Allowable Pipe Length FT 4001 to 5000³Vent Extension Pipe 8001 to 9000³Extended Exposed Sidewall Pipes Two-Pipe Termination KitÐRoof Termination Preferred Condensate Drain General Concentric Vent/Air Termination KitIV. Multiventing and Vent Terminations II. ApplicationÐConcentric Vent and Combustion-Air Heating Mode Sequence of OperationIII. Condensate Drain Protection IV. Heat Pump Mode II. Cooling ModeIII. Continuous Blower Mode Component TestSTART-UP Procedures General II. Prime Condensate Trap with WaterIV. Adjustments III. Purge GAS LinesSet Gas Input Rate BTU/CU FT Ð36Ð Ð37Ð Ð38Ð Ð39Ð Ðaltitude Derate Multiplier for U.S.A Set Temperature RiseUnited States CanadaChecklist Check Safety Controls Check Primary Limit ControlII. Check Pressure Switch Ðspeed SelectorLoad Calculation ChecklistðinstallationCHECKLISTÐSTART-UP Combustion and Vent PipingÐ43Ð Service Training
Related manuals
Manual 12 pages 2.16 Kb Manual 48 pages 30.25 Kb