Bryant 340MAV instruction manual Ð39Ð

Page 39

 

 

TABLE 9ÐMODEL 340MAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT

Continued

 

 

 

 

 

 

FOR USE WITH 140 SIZE FURNACES ONLY

 

 

 

 

 

 

 

(TABULATED DATA BASED ON 23,000 BTUH PER BURNER, DERATED 2% FOR EACH 1000 FT ABOVE SEA LEVEL)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALTITUDE

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

 

HEAT VALUE

 

0.58

 

0.60

 

0.62

0.64

 

0.66

 

 

RANGE

 

 

 

 

 

 

(FT)

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

(BTU/CU FT)

 

 

 

 

 

 

 

 

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

 

 

 

725

41

 

3.6

41

 

3.7

41

 

3.8

40

 

3.6

40

 

3.8

 

 

 

750

42

 

3.7

42

 

3.8

41

 

3.6

41

 

3.7

41

 

3.8

Only

 

4001

775

42

 

3.5

42

 

3.6

42

 

3.7

42

 

3.8

41

 

3.6

 

 

800

42

 

3.3

42

 

3.4

42

 

3.5

42

 

3.6

42

 

3.7

 

 

 

 

 

 

 

 

U.S.A.

 

to

825

43

 

3.7

42

 

3.2

42

 

3.3

42

 

3.4

42

 

3.5

 

5000

875

43

 

3.3

43

 

3.4

43

 

3.6

43

 

3.7

43

 

3.8

 

 

 

850

43

 

3.5

43

 

3.6

43

 

3.8

42

 

3.2

42

 

3.3

 

 

 

900

43

 

3.1

43

 

3.3

43

 

3.4

43

 

3.5

43

 

3.6

 

 

 

925

43

 

3.0

43

 

3.1

43

 

3.2

43

 

3.3

43

 

3.4

 

 

 

950

43

 

2.8

43

 

2.9

43

 

3.0

43

 

3.1

43

 

3.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALTITUDE

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

 

HEAT VALUE

 

0.58

 

0.60

 

0.62

0.64

 

0.66

 

 

RANGE

 

 

 

 

 

 

(FT)

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

(BTU/CU FT)

 

 

 

 

 

 

 

 

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

 

 

 

700

41

 

3.5

41

 

3.7

41

 

3.8

40

 

3.6

40

 

3.7

 

 

 

725

42

 

3.7

42

 

3.8

41

 

3.5

41

 

3.6

41

 

3.8

 

 

 

750

42

 

3.4

42

 

3.5

42

 

3.7

42

 

3.8

41

 

3.5

 

 

 

775

42

 

3.2

42

 

3.3

42

 

3.4

42

 

3.5

42

 

3.7

Only

 

5001

800

43

 

3.7

43

 

3.8

42

 

3.2

42

 

3.3

42

 

3.4

 

 

825

43

 

3.5

43

 

3.6

43

 

3.7

43

 

3.8

42

 

3.2

 

 

 

 

 

 

 

 

U.S.A.

 

to

850

43

 

3.3

43

 

3.4

43

 

3.5

43

 

3.6

43

 

3.7

 

 

875

43

 

3.1

43

 

3.2

43

 

3.3

43

 

3.4

43

 

3.5

 

 

 

 

 

 

 

 

 

 

6000

900

43

 

2.9

43

 

3.0

43

 

3.1

43

 

3.2

43

 

3.3

 

 

 

925

43

 

2.7

43

 

2.8

43

 

2.9

43

 

3.0

43

 

3.1

 

 

 

950

43

 

2.6

43

 

2.7

43

 

2.8

43

 

2.9

43

 

3.0

 

 

 

975

43

 

2.5

43

 

2.6

43

 

2.6

43

 

2.7

43

 

2.8

 

 

 

1000

43

 

2.3

43

 

2.4

43

 

2.5

43

 

2.6

43

 

2.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALTITUDE

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

 

HEAT VALUE

 

0.58

 

0.60

 

0.62

0.64

 

0.66

 

 

RANGE

 

 

 

 

 

 

(FT)

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

(BTU/CU FT)

 

 

 

 

 

 

 

 

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

 

 

 

650

41

 

3.8

40

 

3.6

40

 

3.7

40

 

3.8

39

 

3.7

 

 

 

675

41

 

3.5

41

 

3.6

41

 

3.7

40

 

3.6

40

 

3.7

Only

 

6001

700

42

 

3.6

42

 

3.7

41

 

3.5

41

 

3.6

41

 

3.7

 

 

725

42

 

3.4

42

 

3.5

42

 

3.6

42

 

3.7

42

 

3.8

 

 

 

 

 

 

 

 

U.S.A.

 

to

750

43

 

3.8

42

 

3.3

42

 

3.4

42

 

3.5

42

 

3.6

 

7000

800

43

 

3.4

43

 

3.5

43

 

3.6

43

 

3.7

43

 

3.8

 

 

 

775

43

 

3.6

43

 

3.7

43

 

3.8

42

 

3.3

42

 

3.4

 

 

 

825

43

 

3.2

43

 

3.3

43

 

3.4

43

 

3.5

43

 

3.6

 

 

 

850

43

 

3.0

43

 

3.1

43

 

3.2

43

 

3.3

43

 

3.4

 

 

 

875

43

 

2.8

43

 

2.9

43

 

3.0

43

 

3.1

43

 

3.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ð39Ð

Image 39
Contents ÐMultipoise Orientations Ð1ÐDimensions Ð2ÐUnit Size → ÐClearances to Combustibles Safety ConsiderationsElectrostatic Discharge ESD Precautions Minimum Inches Clearance to Combustible ConstructionCondensate Trap Location Factory-Shipped Orientation IntroductionApplications General II. Upflow ApplicationsCondensate Trap Location Alternate Upflow Orientation Ð5ÐÐ6Ð Pressure Switch TubingCondensate Trap Tubing Condensate Trap Freeze ProtectionIII Downflow Applications Condensate Trap LocationÐ8Ð IV. Horizontal Left SUPPLY-AIR Discharge ApplicationsÐ9Ð Construct a Working PlatformHorizontal Right SUPPLY-AIR Discharge Applications ÐAttic Location and Working Platform Location → ÐHorizontal Right Tube ConfigurationIII. Hazardous Locations II. Furnace Location Relative to Cooling Equipment→ II. Installation in Upflow or Downflow Applications Installation Leveling Legs if DesiredÐopening Dimensions Furnace Plenum Opening Floor Opening CasingWidth ÐDuct Flanges III. Installation in Horizontal ApplicationsIV. Filter Arrangement Ðfilter InformationBottom Closure Panel Electrical Connections WiringVI. GAS Piping Ðmaximum Capacity of PipeII -V Wiring → ÐHeating and Cooling Application Wiring DiagramÐWiring Diagram Amps III. AccessoriesÐelectrical Data Amps GageGeneral Direct VentingRemoval of Existing Furnaces from Common Vent Systems II. COMBUSTION-AIR and Vent PipingCombustion-Air and Vent Pipe Diameter ExampleCombustion-Air and Vent Pipe Attachment ÐShort Vent 5 to 8 Ft System COMBUSTION-AIR Intake Housing Plug Fitting2001 to Ðmaximum Allowable Pipe Length FT4001 to 5000³ Ðmaximum Allowable Pipe Length FT8001 to 9000³ Vent Extension PipeTwo-Pipe Termination Kit Extended Exposed Sidewall PipesÐRoof Termination Preferred II. Application Concentric Vent/Air Termination KitIV. Multiventing and Vent Terminations Condensate Drain GeneralÐConcentric Vent and Combustion-Air Heating Mode Sequence of OperationIII. Condensate Drain Protection Component Test II. Cooling ModeIII. Continuous Blower Mode IV. Heat Pump ModeII. Prime Condensate Trap with Water START-UP Procedures GeneralIV. Adjustments III. Purge GAS LinesSet Gas Input Rate BTU/CU FT Ð36Ð Ð37Ð Ð38Ð Ð39Ð Canada Set Temperature RiseUnited States Ðaltitude Derate Multiplier for U.S.AÐspeed Selector Check Safety Controls Check Primary Limit ControlII. Check Pressure Switch ChecklistCombustion and Vent Piping ChecklistðinstallationCHECKLISTÐSTART-UP Load CalculationÐ43Ð Service Training
Related manuals
Manual 12 pages 2.16 Kb Manual 48 pages 30.25 Kb

340MAV specifications

The Bryant 340MAV is a standout model in the Bryant lineup, designed to provide exceptional comfort, efficiency, and performance for residential heating and cooling needs. This unit offers a perfect blend of innovative technology and user-friendly features, making it an ideal choice for homeowners seeking reliability and quality.

One of the defining characteristics of the Bryant 340MAV is its impressive efficiency rating. With a SEER (Seasonal Energy Efficiency Ratio) of up to 18, this model ensures that homeowners can enjoy effective cooling during the summer months while minimizing energy consumption. Similarly, the heating efficiency is notable, with a high AFUE (Annual Fuel Utilization Efficiency) rating. This makes the 340MAV an environmentally friendly option that also promotes cost savings on energy bills.

The 340MAV incorporates advanced technologies that enhance its performance. One such technology is the variable-speed compressor, which allows the system to adjust its output based on the demands of the home. This means that the unit operates more quietly and reduces energy usage by matching the cooling or heating output required. Additionally, the two-stage heating capability provides more consistent temperatures and improved comfort throughout the space.

Operating noise is a crucial factor in residential HVAC systems, and the Bryant 340MAV is designed with this in mind. Engineered for quiet operation, the unit features a sound-dampening design, including an insulated cabinet and a specially designed compressor that minimizes noise levels. Homeowners can enjoy a comfortable indoor climate without the disruptive racket often associated with traditional systems.

Furthermore, the Bryant 340MAV is equipped with a durable all-aluminum coil, which improves heat transfer efficiency while also being resistant to corrosion. This characteristic contributes to the longevity of the unit, ensuring that it can withstand various environmental factors without compromising performance.

Another key feature is the advanced control options that the Bryant 340MAV offers. Integration with smart thermostats allows homeowners to monitor and adjust their HVAC system remotely, ensuring optimal comfort at all times. Additionally, the system is compatible with Bryant's Perfect Air™ filtration system, enhancing indoor air quality by reducing pollutants and allergens.

In summary, the Bryant 340MAV is a high-efficiency heating and cooling solution that brings together cutting-edge technology, quiet operation, and user-friendly features. With its focus on comfort and energy savings, it stands out as a prime choice for homeowners looking to invest in a reliable HVAC system.