Bryant 340MAV instruction manual Extended Exposed Sidewall Pipes, Two-Pipe Termination Kit

Page 27

9.While cement is still wet, twist pipe into socket with 1/4 turn. Be sure pipe is fully inserted into fitting socket.

10.Wipe excess cement from joint. A continuous bead of cement will be visible around perimeter of a properly made joint.

11.Handle pipe joints carefully until cement sets.

12.Support combustion-air and vent piping a minimum of every 5 ft (3 ft for SDR-21 or -26 PVC) using perforated metal hanging strap.

13.Slope combustion-air and vent pipes toward furnace a minimum of 1/4 in. per linear ft with no sags between hangers.

14.Use appropriate methods to seal openings where vent and combustion-air pipes pass through roof or side wall.

III.CONCENTRIC VENT AND COMBUSTION-AIR TERMINATION KIT INSTALLATION

NOTE: If these instructions differ from those packaged with termination kit, follow kit instructions.

Combustion-air and vent pipes must terminate outside structure. A factory accessory termination kit must be installed in 1 of the installations shown in Fig. 30, 31, 32, 33, or 34. Four termination kits are available.

1.The 2-in. termination bracket kit is for 1-in., 1-1/2 in., and 2-in. diameter 2-pipe termination systems.

2. The 3-in. termination bracket kit is for 2-1/2 in., 3-in., and 4-in. diameter 2-pipe termination systems.

3.The 2-in. concentric vent/air termination kit is for 1-in., 1-1/2 in., 2-in., and 2-1/2 in. diameter pipe systems when single penetration of wall or roof is desired.

4. The 3-in. concentric vent/air termination kit is for 2-1/2 in., 3-in., and 4-in. diameter pipe systems when single penetra- tion of wall or roof is desired.

NOTE: Shaded parts in Fig. 30, 31, 32, 33, and 34 are considered to be termination. These components should NOT be counted when determining pipe diameter. Roof termination is preferred since it is less susceptible to damage, has reduced chances to take

in contaminants, and has less visible vent vapors. (See Fig. 30 or 31.) Sidewall termination may require sealing or shielding of building surfaces with a corrosive resistance material due to corrosive combustion products of vent system.

A. Extended Exposed Sidewall Pipes

Sidewall combustion-air and vent pipe terminations may be extended beyond area shown in Fig. 33 or 34 in outside ambient by insulating pipes as indicated in Table 7.

1.Determine combustion-air and vent pipe diameters, as stated above, using total pipe length and number of elbows.

2.Using winter design temperature (used in load calculations), find appropriate temperature for your application and fur- nace model.

3.Determine required insulation thickness for exposed pipe lengths.

NOTE: Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces cannot exceed total allowable pipe length as specified in Table 6.

B.Two-Pipe Termination Kit

1.Determine location for termination.

Consideration of the following should be made when determining an appropriate location for termination kit.

a.Comply with all clearance requirements as stated in Table 5.

b.Termination kit should be positioned where vent vapors will not damage plants/shrubs or air conditioning equip- ment.

c.Termination kit should be positioned so that it will not be affected by wind eddy (such as inside building corners) or allow recirculation of flue gases, airborne leaves, or light snow.

d.Termination kit should be positioned where it will not be damaged by or subjected to foreign objects, such as stones, balls, etc.

e.Termination kit should be positioned where vent vapors are not objectionable.

TABLE 7ÐMAXIMUM ALLOWABLE EXPOSED VENT PIPE LENGTH (FT) WITH AND WITHOUT INSULATION IN WINTER DESIGN TEMPERATURE AMBIENT*

UNIT

WINTER DESIGN

MAX PIPE

WITHOUT

WITH 3/8-IN. OR

TEMPERATURE

DIAMETER

SIZE

INSULATION

THICKER INSULATION²

(°F)

(IN.)

 

 

 

 

20

1-1/2

51

70

040

 

 

 

 

0

1-1/2

28

70

 

-20

1-1/2

16

70

 

20

2

65

70

060

 

 

 

 

0

2

35

70

 

-20

2

20

70

 

20

2-1/2

70

70

080

 

 

 

 

0

2-1/2

47

70

 

-20

2-1/2

28

70

 

20

3

70

70

100

0

3

50

70

 

-20

3

28

70

 

20

4

70

70

120

0

4

48

70

 

-20

4

23

70

 

20

4

70

70

140

0

4

57

70

 

-20

4

30

70

 

 

 

 

 

*Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe length as specified in Table 6.

² Insulation thickness based on R value of 3.5 per in.

Ð27Ð

Image 27
Contents ÐMultipoise Orientations Ð1ÐDimensions Ð2ÐUnit Size → ÐClearances to Combustibles Safety ConsiderationsElectrostatic Discharge ESD Precautions Minimum Inches Clearance to Combustible ConstructionCondensate Trap Location Factory-Shipped Orientation IntroductionApplications General II. Upflow ApplicationsCondensate Trap Location Alternate Upflow Orientation Ð5ÐÐ6Ð Pressure Switch TubingCondensate Trap Tubing Condensate Trap Freeze ProtectionIII Downflow Applications Condensate Trap LocationÐ8Ð IV. Horizontal Left SUPPLY-AIR Discharge ApplicationsÐ9Ð Construct a Working PlatformHorizontal Right SUPPLY-AIR Discharge Applications ÐAttic Location and Working Platform Location → ÐHorizontal Right Tube ConfigurationIII. Hazardous Locations II. Furnace Location Relative to Cooling Equipment→ II. Installation in Upflow or Downflow Applications Installation Leveling Legs if DesiredÐopening Dimensions Furnace Plenum Opening Floor Opening CasingWidth ÐDuct Flanges III. Installation in Horizontal ApplicationsIV. Filter Arrangement Ðfilter InformationBottom Closure Panel Electrical Connections WiringVI. GAS Piping Ðmaximum Capacity of PipeII -V Wiring → ÐHeating and Cooling Application Wiring DiagramÐWiring Diagram Amps III. AccessoriesÐelectrical Data Amps GageGeneral Direct VentingRemoval of Existing Furnaces from Common Vent Systems II. COMBUSTION-AIR and Vent PipingCombustion-Air and Vent Pipe Diameter ExampleCombustion-Air and Vent Pipe Attachment ÐShort Vent 5 to 8 Ft System COMBUSTION-AIR Intake Housing Plug Fitting2001 to Ðmaximum Allowable Pipe Length FT4001 to 5000³ Ðmaximum Allowable Pipe Length FT8001 to 9000³ Vent Extension PipeTwo-Pipe Termination Kit Extended Exposed Sidewall PipesÐRoof Termination Preferred II. Application Concentric Vent/Air Termination KitIV. Multiventing and Vent Terminations Condensate Drain GeneralÐConcentric Vent and Combustion-Air Heating Mode Sequence of OperationIII. Condensate Drain Protection Component Test II. Cooling ModeIII. Continuous Blower Mode IV. Heat Pump ModeII. Prime Condensate Trap with Water START-UP Procedures GeneralIV. Adjustments III. Purge GAS LinesSet Gas Input Rate BTU/CU FT Ð36Ð Ð37Ð Ð38Ð Ð39Ð Canada Set Temperature RiseUnited States Ðaltitude Derate Multiplier for U.S.AÐspeed Selector Check Safety Controls Check Primary Limit ControlII. Check Pressure Switch ChecklistCombustion and Vent Piping ChecklistðinstallationCHECKLISTÐSTART-UP Load CalculationÐ43Ð Service Training
Related manuals
Manual 12 pages 2.16 Kb Manual 48 pages 30.25 Kb

340MAV specifications

The Bryant 340MAV is a standout model in the Bryant lineup, designed to provide exceptional comfort, efficiency, and performance for residential heating and cooling needs. This unit offers a perfect blend of innovative technology and user-friendly features, making it an ideal choice for homeowners seeking reliability and quality.

One of the defining characteristics of the Bryant 340MAV is its impressive efficiency rating. With a SEER (Seasonal Energy Efficiency Ratio) of up to 18, this model ensures that homeowners can enjoy effective cooling during the summer months while minimizing energy consumption. Similarly, the heating efficiency is notable, with a high AFUE (Annual Fuel Utilization Efficiency) rating. This makes the 340MAV an environmentally friendly option that also promotes cost savings on energy bills.

The 340MAV incorporates advanced technologies that enhance its performance. One such technology is the variable-speed compressor, which allows the system to adjust its output based on the demands of the home. This means that the unit operates more quietly and reduces energy usage by matching the cooling or heating output required. Additionally, the two-stage heating capability provides more consistent temperatures and improved comfort throughout the space.

Operating noise is a crucial factor in residential HVAC systems, and the Bryant 340MAV is designed with this in mind. Engineered for quiet operation, the unit features a sound-dampening design, including an insulated cabinet and a specially designed compressor that minimizes noise levels. Homeowners can enjoy a comfortable indoor climate without the disruptive racket often associated with traditional systems.

Furthermore, the Bryant 340MAV is equipped with a durable all-aluminum coil, which improves heat transfer efficiency while also being resistant to corrosion. This characteristic contributes to the longevity of the unit, ensuring that it can withstand various environmental factors without compromising performance.

Another key feature is the advanced control options that the Bryant 340MAV offers. Integration with smart thermostats allows homeowners to monitor and adjust their HVAC system remotely, ensuring optimal comfort at all times. Additionally, the system is compatible with Bryant's Perfect Airâ„¢ filtration system, enhancing indoor air quality by reducing pollutants and allergens.

In summary, the Bryant 340MAV is a high-efficiency heating and cooling solution that brings together cutting-edge technology, quiet operation, and user-friendly features. With its focus on comfort and energy savings, it stands out as a prime choice for homeowners looking to invest in a reliable HVAC system.