Bryant 340MAV instruction manual Installation Leveling Legs if Desired

Page 13

INSTALLATION

I.LEVELING LEGS (IF DESIRED)

When furnace is used in upflow position with side inlet(s), leveling legs may be desired. (See Fig. 12.) Install field-supplied, corrosion-resistant 5/16-in. machine bolts and nuts.

516

516

1 34

1 34

516

516

1 34 1 34

A89014

Fig. 12ÐLeveling Legs

NOTE: The maximum length of bolt should not exceed 1-1/2 in.

1.Position furnace on its back. Locate and drill a 5/16-in. diameter hole in each bottom corner of furnace. (See Fig. 12.) Holes in bottom closure panel may be used as guide locations.

2.For each hole, install nut on bolt and then install bolt and nut in hole. (Install flat washer if desired.)

3.Install another nut on other side of furnace base. (Install flat washer if desired.)

4.Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement.

NOTE: Bottom closure must be used when leveling legs are used. See Bottom Closure Panel section.

II. INSTALLATION IN UPFLOW OR DOWNFLOW APPLICATIONS

NOTE: For downflow applications, this furnace is approved for use on combustible flooring when special base (available from manufacturer) Part No. KGASB0201ALL is used. Special base in not required when this furnace is installed on manufacturer's Coil Assembly Part No. CD5 or CK5, or Coil Box Part No. KCAKC is used.

1.Determine application being installed from Table 1.

2.Construct hole in floor per dimensions specified in Table 1 and Fig. 13.

3.Construct plenum to dimensions specified in Table 1 and Fig. 13.

4.If downflow subbase (KGASB) is used, install as shown in Fig. 14.

If coil assembly CD5 or CK5 or Coil Box KCAKC is used, install as shown in Fig. 15.

NOTE: Remove furnace perforated, discharge duct flanges when they interfere with mating flanges on coil on downflow subbase. To remove furnace perforated, discharge duct flange, use wide duct pliers or duct flange tool to bend flange back and forth until it breaks off. Be careful of sharp edges. (See Fig. 16.)

WARNING: Do not bend duct flanges inward as shown in Fig. 16. This will affect airflow across heat exchangers and may cause limit cycling or premature heat exchanger failure. Remove duct flange completely or bend it inward a minimum of 210° as shown in Fig. 16.

NOTE: For 140 size unit when installed in downflow orientation, cut the white jumper wire off between terminals PL1-6 and PL1-9. Refer to Fig. 24 for location of jumper. Cut jumper close to connector and remove wire to avoid a short circuit.

Ð13Ð

Image 13 Contents
ÐMultipoise Orientations Ð1ÐÐ2Ð DimensionsUnit Size Electrostatic Discharge ESD Precautions Safety ConsiderationsMinimum Inches Clearance to Combustible Construction → ÐClearances to CombustiblesApplications General IntroductionII. Upflow Applications Condensate Trap Location Factory-Shipped OrientationCondensate Trap Location Alternate Upflow Orientation Ð5ÐÐ6Ð Pressure Switch TubingIII Downflow Applications Condensate Trap Freeze ProtectionCondensate Trap Location Condensate Trap TubingÐ8Ð IV. Horizontal Left SUPPLY-AIR Discharge Applications Construct a Working Platform Ð9Ð Horizontal Right SUPPLY-AIR Discharge Applications ÐAttic Location and Working Platform Location → ÐHorizontal Right Tube ConfigurationIII. Hazardous Locations II. Furnace Location Relative to Cooling Equipment→ II. Installation in Upflow or Downflow Applications Installation Leveling Legs if DesiredFurnace Plenum Opening Floor Opening Casing Ðopening DimensionsWidth ÐDuct Flanges III. Installation in Horizontal ApplicationsÐfilter Information IV. Filter ArrangementBottom Closure Panel VI. GAS Piping WiringÐmaximum Capacity of Pipe Electrical ConnectionsII -V Wiring → ÐHeating and Cooling Application Wiring DiagramÐWiring Diagram Ðelectrical Data III. AccessoriesAmps Gage AmpsRemoval of Existing Furnaces from Common Vent Systems Direct VentingII. COMBUSTION-AIR and Vent Piping GeneralExample Combustion-Air and Vent Pipe DiameterCombustion-Air and Vent Pipe Attachment ÐShort Vent 5 to 8 Ft System COMBUSTION-AIR Intake Housing Plug Fitting2001 to Ðmaximum Allowable Pipe Length FT4001 to 5000³ Ðmaximum Allowable Pipe Length FT8001 to 9000³ Vent Extension PipeTwo-Pipe Termination Kit Extended Exposed Sidewall PipesÐRoof Termination Preferred IV. Multiventing and Vent Terminations Concentric Vent/Air Termination KitCondensate Drain General II. ApplicationÐConcentric Vent and Combustion-Air Sequence of Operation Heating ModeIII. Condensate Drain Protection III. Continuous Blower Mode II. Cooling ModeIV. Heat Pump Mode Component TestII. Prime Condensate Trap with Water START-UP Procedures GeneralIII. Purge GAS Lines IV. AdjustmentsSet Gas Input Rate BTU/CU FT Ð36Ð Ð37Ð Ð38Ð Ð39Ð United States Set Temperature RiseÐaltitude Derate Multiplier for U.S.A CanadaII. Check Pressure Switch Check Safety Controls Check Primary Limit ControlChecklist Ðspeed SelectorCHECKLISTÐSTART-UP ChecklistðinstallationLoad Calculation Combustion and Vent PipingÐ43Ð Service Training
Related manuals
Manual 12 pages 2.16 Kb Manual 48 pages 30.25 Kb