Bryant Essential Information on 340MAV Furnace Features

Page 6

PLUG

 

CAP

 

COLLECTOR BOX

 

DRAIN TUBE (BLUE

 

& WHITE STRIPED)

 

COLLECTOR BOX

 

TUBE (PINK)

 

COLLECTOR BOX

 

TUBE (GREEN)

 

INDUCER HOUSING

 

(MOLDED) DRAIN

 

TUBE (BEHIND

 

COLLECTOR BOX

 

DRAIN TUBE)

 

COLLECTOR BOX

 

DRAIN TUBE (BLUE)

CONDENSATE

 

 

TRAP

FIELD-INSTALLED

 

FACTORY-SUPPLIED

 

DRAIN TUBE

 

COUPLING (LEFT

 

DRAIN OPTION)

 

FIELD-INSTALLED

FACTORY-SUPPLIED

DRAIN TUBE

FIELD-INSTALLED

FIELD-INSTALLED

FACTORY-SUPPLIED

FACTORY-SUPPLIED

12-IN. CPVC STREET

DRAIN TUBE

ELBOWS (2) FOR

COUPLING (RIGHT

LEFT DRAIN OPTION

DRAIN OPTION)

A96194

Fig. 5ÐFactory-Shipped Upflow Tube Configuration

(Shown With Blower Access Panel Removed)

D.Condensate Trap Tubing (Alternate Upflow Orientation)

NOTE: See Fig. 6 or tube routing label on main furnace door to confirm location of these tubes.

1. Collector Box Drain Tube

Connect collector box drain tube (blue label) to condensate trap.

NOTE: On 17-1/2-in. wide furnaces ONLY, cut tube between corrugated sections to prevent kinks from occurring.

2.Inducer Housing Drain Tube

a.Remove and discard LOWER (molded) inducer housing drain tube which was previously connected to conden- sate trap.

b.Use inducer housing drain extension tube (violet label and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to the con- densate trap.

c.Determine appropriate length, cut, and connect tube.

d.Clamp tube to prevent any condensate leakage.

3.Relief Port Tube

a.Connect relief port tube (green label) to condensate trap.

b. Extend this tube (if required) by splicing to small diameter tube (factory-supplied in loose parts bag).

c.Determine appropriate length, cut, and connect tube.

Ð6Ð

PLUG

CAP

COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED)

COLLECTOR BOX

TUBE (PINK)

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX

DRAIN TUBE (BLUE)

CONDENSATE

TRAP

INDUCER HOUSING DRAIN TUBE (VIOLET)

A96195

Fig. 6ÐAlternate Upflow Tube Configuration and

Trap Location

E.Condensate Trap Field Drain Attachment

Refer to Condensate Drain section for recommendations and procedures.

F. Pressure Switch Tubing

The LOWER collector box pressure tube (pink label) is factory connected to the pressure switch and should not require any modification.

NOTE: See Fig. 5 or 6 or tube routing label on main furnace door to check for proper connections.

G.Upper Collector Box and Inducer Housing (Unused) Drain Connections

UPPER COLLECTOR BOX DRAIN CONNECTION

Attached to the UPPER collector box drain connection is a factory-installed corrugated, plugged tube (blue and white striped label). This tube is plugged to prevent condensate leakage in this application. Ensure this tube is plugged.

NOTE: See Fig. 5 or 6 or tube routing label on main furnace door to check for proper connections.

UPPER INDUCER HOUSING DRAIN CONNECTION

Attached to the UPPER (unused) inducer housing drain connection is a cap and clamp. This cap is used to prevent condensate leakage in this application. Ensure this connection is capped.

NOTE: See Fig. 5 or 6 or tube routing label on main furnace door to check for proper connections.

Image 6
Contents Ð1Ð ÐMultipoise OrientationsDimensions Ð2ÐUnit Size Minimum Inches Clearance to Combustible Construction Safety ConsiderationsElectrostatic Discharge ESD Precautions → ÐClearances to CombustiblesII. Upflow Applications IntroductionApplications General Condensate Trap Location Factory-Shipped OrientationÐ5Ð Condensate Trap Location Alternate Upflow OrientationPressure Switch Tubing Ð6ÐCondensate Trap Location Condensate Trap Freeze ProtectionIII Downflow Applications Condensate Trap TubingIV. Horizontal Left SUPPLY-AIR Discharge Applications Ð8ÐÐ9Ð Construct a Working PlatformHorizontal Right SUPPLY-AIR Discharge Applications ÐAttic Location and Working Platform → ÐHorizontal Right Tube Configuration LocationII. Furnace Location Relative to Cooling Equipment III. Hazardous LocationsInstallation Leveling Legs if Desired → II. Installation in Upflow or Downflow ApplicationsÐopening Dimensions Furnace Plenum Opening Floor Opening CasingWidth III. Installation in Horizontal Applications ÐDuct FlangesIV. Filter Arrangement Ðfilter InformationBottom Closure Panel Ðmaximum Capacity of Pipe WiringVI. GAS Piping Electrical Connections→ ÐHeating and Cooling Application Wiring Diagram II -V WiringÐWiring Diagram Amps Gage III. AccessoriesÐelectrical Data AmpsII. COMBUSTION-AIR and Vent Piping Direct VentingRemoval of Existing Furnaces from Common Vent Systems GeneralCombustion-Air and Vent Pipe Diameter ExampleCombustion-Air and Vent Pipe Attachment COMBUSTION-AIR Intake Housing Plug Fitting ÐShort Vent 5 to 8 Ft SystemÐmaximum Allowable Pipe Length FT 2001 toÐmaximum Allowable Pipe Length FT 4001 to 5000³Vent Extension Pipe 8001 to 9000³Extended Exposed Sidewall Pipes Two-Pipe Termination KitÐRoof Termination Preferred Condensate Drain General Concentric Vent/Air Termination KitIV. Multiventing and Vent Terminations II. ApplicationÐConcentric Vent and Combustion-Air Heating Mode Sequence of OperationIII. Condensate Drain Protection IV. Heat Pump Mode II. Cooling ModeIII. Continuous Blower Mode Component TestSTART-UP Procedures General II. Prime Condensate Trap with WaterIV. Adjustments III. Purge GAS LinesSet Gas Input Rate BTU/CU FT Ð36Ð Ð37Ð Ð38Ð Ð39Ð Ðaltitude Derate Multiplier for U.S.A Set Temperature RiseUnited States CanadaChecklist Check Safety Controls Check Primary Limit ControlII. Check Pressure Switch Ðspeed SelectorLoad Calculation ChecklistðinstallationCHECKLISTÐSTART-UP Combustion and Vent PipingÐ43Ð Service Training
Related manuals
Manual 12 pages 2.16 Kb Manual 48 pages 30.25 Kb

340MAV specifications

The Bryant 340MAV is a standout model in the Bryant lineup, designed to provide exceptional comfort, efficiency, and performance for residential heating and cooling needs. This unit offers a perfect blend of innovative technology and user-friendly features, making it an ideal choice for homeowners seeking reliability and quality.

One of the defining characteristics of the Bryant 340MAV is its impressive efficiency rating. With a SEER (Seasonal Energy Efficiency Ratio) of up to 18, this model ensures that homeowners can enjoy effective cooling during the summer months while minimizing energy consumption. Similarly, the heating efficiency is notable, with a high AFUE (Annual Fuel Utilization Efficiency) rating. This makes the 340MAV an environmentally friendly option that also promotes cost savings on energy bills.

The 340MAV incorporates advanced technologies that enhance its performance. One such technology is the variable-speed compressor, which allows the system to adjust its output based on the demands of the home. This means that the unit operates more quietly and reduces energy usage by matching the cooling or heating output required. Additionally, the two-stage heating capability provides more consistent temperatures and improved comfort throughout the space.

Operating noise is a crucial factor in residential HVAC systems, and the Bryant 340MAV is designed with this in mind. Engineered for quiet operation, the unit features a sound-dampening design, including an insulated cabinet and a specially designed compressor that minimizes noise levels. Homeowners can enjoy a comfortable indoor climate without the disruptive racket often associated with traditional systems.

Furthermore, the Bryant 340MAV is equipped with a durable all-aluminum coil, which improves heat transfer efficiency while also being resistant to corrosion. This characteristic contributes to the longevity of the unit, ensuring that it can withstand various environmental factors without compromising performance.

Another key feature is the advanced control options that the Bryant 340MAV offers. Integration with smart thermostats allows homeowners to monitor and adjust their HVAC system remotely, ensuring optimal comfort at all times. Additionally, the system is compatible with Bryant's Perfect Airâ„¢ filtration system, enhancing indoor air quality by reducing pollutants and allergens.

In summary, the Bryant 340MAV is a high-efficiency heating and cooling solution that brings together cutting-edge technology, quiet operation, and user-friendly features. With its focus on comfort and energy savings, it stands out as a prime choice for homeowners looking to invest in a reliable HVAC system.