Bryant 340MAV Ðspeed Selector, Check Safety Controls Check Primary Limit Control, Checklist

Page 41

3.Adjust temperature rise by adjusting blower speed. Increase blower speed to reduce temperature rise. Decrease blower speed to increase temperature rise.

WARNING: Disconnect 115-v electrical power before changing speed tap. Failure to follow this warning could result in personal injury.

4.To change blower motor speed selections for heating mode, remove blower motor lead from control center HEAT terminal. (See Fig. 25.) Select desired blower motor speed lead from 1 of the other terminals and relocate it to HEAT terminal. See Table 12 for lead color identification. Recon- nect original lead on SPARE terminal.

Follow this same procedure for proper selection of COOL speed selection.

TABLE 12ÐSPEED SELECTOR

 

 

FACTORY-

COLOR

SPEED

SHIPPED

 

 

CONNECTION

Black

High

Cool

Yellow (When Present)

Medium High

Spare

Blue

Medium Low

Heat

Red

Low

Spare

White

Common

Com

 

 

 

C.Blower Off Delay (Heat Mode)

The main blower off time delay period is factory-set at 135 sec and is not field-adjustable.

D.Set Thermostat Heat Anticipator

Thermostat heat anticipator must be set to match amp draw of components in R-W circuit. Accurate amp draw measurements can be obtained at thermostat subbase terminals R and W.

Fig. 46 illustrates an easy method of obtaining these measure- ments. Amp reading should be taken after blower motor has started. See thermostat manufacturer's instructions for adjusting heat anticipator and for varying heating cycle length.

CHECK SAFETY CONTROLS

I.CHECK PRIMARY LIMIT CONTROL

This control shuts off combustion control system and energizes air-circulating blower motor if furnace overheats. Recommended method of checking this limit control is to gradually block off return air after furnace has been operating for a period of at least 5 minutes. As soon as limit control has shut off burners, return-air opening should be unblocked to permit normal air circulation. By using this method to check limit control, it can be established that limit is functioning properly and operates if there is a restricted return-air supply or motor failure. If limit control does not function during this test, cause must be determined and corrected.

II.CHECK PRESSURE SWITCH

This control proves operation of draft inducer. Check switch operation as follows:

1. Turn off 115-v power to furnace.

THERMOSTAT SUBBASE

TERMINALS WITH

THERMOSTAT REMOVED

HOOK-AROUND

VOLT/AMMETER

R Y W G

10 TURNS

FROM UNIT 24-VOLT

TERMINAL BLOCK

EXAMPLE:

5.0 AMPS ON AMMETER

= 0.5 AMPS FOR THERMOSTAT SETTING

 

10 TURNS AROUND JAWS

A80201

Fig. 46ÐAmp Draw Check with Ammeter

2.Remove main furnace door and disconnect inducer motor lead wires from wire harness.

3.Turn on 115-v power to furnace.

4.Set thermostat to call for heat and wait 1 minute. When pressure switch is functioning properly, hot surface ignitor should NOT glow, and control center diagnostic light flashes a Status Code 31. If hot surface ignitor glows when inducer motor is disconnected, shut furnace down immedi- ately. Determine reason pressure switch did not function properly and correct condition.

5.Turn off 115-v power to furnace.

6.Reconnect inducer motor leads, reinstall main furnace door, and turn on 115-v power supply.

CHECKLIST

1.Put away tools and instruments. Clean up debris.

2.Verify manual reset switch has continuity.

3.Verify that blower and control access doors are properly installed.

4.Cycle test furnace with room thermostat.

5.Check operation of accessories per manufacturer's instruc- tions.

6.Review User's Guide with owner.

7.Leave literature packet near furnace.

Ð41Ð

Image 41
Contents ÐMultipoise Orientations Ð1ÐUnit Size DimensionsÐ2Ð Electrostatic Discharge ESD Precautions Safety ConsiderationsMinimum Inches Clearance to Combustible Construction → ÐClearances to CombustiblesApplications General IntroductionII. Upflow Applications Condensate Trap Location Factory-Shipped OrientationCondensate Trap Location Alternate Upflow Orientation Ð5ÐÐ6Ð Pressure Switch TubingIII Downflow Applications Condensate Trap Freeze ProtectionCondensate Trap Location Condensate Trap TubingÐ8Ð IV. Horizontal Left SUPPLY-AIR Discharge ApplicationsHorizontal Right SUPPLY-AIR Discharge Applications Ð9ÐConstruct a Working Platform ÐAttic Location and Working Platform Location → ÐHorizontal Right Tube ConfigurationIII. Hazardous Locations II. Furnace Location Relative to Cooling Equipment→ II. Installation in Upflow or Downflow Applications Installation Leveling Legs if DesiredWidth Ðopening DimensionsFurnace Plenum Opening Floor Opening Casing ÐDuct Flanges III. Installation in Horizontal ApplicationsBottom Closure Panel IV. Filter ArrangementÐfilter Information VI. GAS Piping WiringÐmaximum Capacity of Pipe Electrical ConnectionsII -V Wiring → ÐHeating and Cooling Application Wiring DiagramÐWiring Diagram Ðelectrical Data III. AccessoriesAmps Gage AmpsRemoval of Existing Furnaces from Common Vent Systems Direct VentingII. COMBUSTION-AIR and Vent Piping GeneralCombustion-Air and Vent Pipe Attachment Combustion-Air and Vent Pipe DiameterExample ÐShort Vent 5 to 8 Ft System COMBUSTION-AIR Intake Housing Plug Fitting2001 to Ðmaximum Allowable Pipe Length FT4001 to 5000³ Ðmaximum Allowable Pipe Length FT8001 to 9000³ Vent Extension PipeTwo-Pipe Termination Kit Extended Exposed Sidewall PipesÐRoof Termination Preferred IV. Multiventing and Vent Terminations Concentric Vent/Air Termination KitCondensate Drain General II. ApplicationÐConcentric Vent and Combustion-Air III. Condensate Drain Protection Heating ModeSequence of Operation III. Continuous Blower Mode II. Cooling ModeIV. Heat Pump Mode Component TestII. Prime Condensate Trap with Water START-UP Procedures GeneralSet Gas Input Rate IV. AdjustmentsIII. Purge GAS Lines BTU/CU FT Ð36Ð Ð37Ð Ð38Ð Ð39Ð United States Set Temperature RiseÐaltitude Derate Multiplier for U.S.A CanadaII. Check Pressure Switch Check Safety Controls Check Primary Limit ControlChecklist Ðspeed SelectorCHECKLISTÐSTART-UP ChecklistðinstallationLoad Calculation Combustion and Vent PipingÐ43Ð Service Training
Related manuals
Manual 12 pages 2.16 Kb Manual 48 pages 30.25 Kb

340MAV specifications

The Bryant 340MAV is a standout model in the Bryant lineup, designed to provide exceptional comfort, efficiency, and performance for residential heating and cooling needs. This unit offers a perfect blend of innovative technology and user-friendly features, making it an ideal choice for homeowners seeking reliability and quality.

One of the defining characteristics of the Bryant 340MAV is its impressive efficiency rating. With a SEER (Seasonal Energy Efficiency Ratio) of up to 18, this model ensures that homeowners can enjoy effective cooling during the summer months while minimizing energy consumption. Similarly, the heating efficiency is notable, with a high AFUE (Annual Fuel Utilization Efficiency) rating. This makes the 340MAV an environmentally friendly option that also promotes cost savings on energy bills.

The 340MAV incorporates advanced technologies that enhance its performance. One such technology is the variable-speed compressor, which allows the system to adjust its output based on the demands of the home. This means that the unit operates more quietly and reduces energy usage by matching the cooling or heating output required. Additionally, the two-stage heating capability provides more consistent temperatures and improved comfort throughout the space.

Operating noise is a crucial factor in residential HVAC systems, and the Bryant 340MAV is designed with this in mind. Engineered for quiet operation, the unit features a sound-dampening design, including an insulated cabinet and a specially designed compressor that minimizes noise levels. Homeowners can enjoy a comfortable indoor climate without the disruptive racket often associated with traditional systems.

Furthermore, the Bryant 340MAV is equipped with a durable all-aluminum coil, which improves heat transfer efficiency while also being resistant to corrosion. This characteristic contributes to the longevity of the unit, ensuring that it can withstand various environmental factors without compromising performance.

Another key feature is the advanced control options that the Bryant 340MAV offers. Integration with smart thermostats allows homeowners to monitor and adjust their HVAC system remotely, ensuring optimal comfort at all times. Additionally, the system is compatible with Bryant's Perfect Air™ filtration system, enhancing indoor air quality by reducing pollutants and allergens.

In summary, the Bryant 340MAV is a high-efficiency heating and cooling solution that brings together cutting-edge technology, quiet operation, and user-friendly features. With its focus on comfort and energy savings, it stands out as a prime choice for homeowners looking to invest in a reliable HVAC system.