Emerson 3000 installation manual Facility Fluid and Piping Maintenance, Electrical Connections

Page 24

Installation (Applicable to all Models)

2.5.2Humidifier Supply Water—Optional Infrared

1/4" supply line; maximum water pressure is 150 psi (1034kPa)

Size humidifier supply line for 1 gpm (3.8 l/m), with a minimum water pressure of 20 psi (138kPa)

Do not supply de-ionized water to the humidifier

2.6Facility Fluid and Piping Maintenance

Facility water and glycol quality remain a requirement throughout the life of the piping system. Fluid and piping system maintenance schedules must be established and performed. A local fluid mainte- nance program must be established that will evaluate fluid chemistry and apply necessary treatment. A periodic leak inspection of facility and unit fluid piping is recommended. Refer to 5.4 - Glycol Pip- ing.

2.7Electrical Connections

Three-phase electrical service is required for all models in either 208, 230, 460, or 575 V, 60 Hz; or 200, 230, or 380/415 V, 50 Hz. Electrical service shall conform to national and local electrical codes. Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to elec- trical schematic when making connections.

A manual electrical disconnect switch should be installed within 5 feet (1.6 m) of the unit in accor- dance with codes, or a factory-supplied disconnect switch may be factory mounted within the unit accessible from the exterior.

! WARNING

Risk of electric shock. Can cause injury or death.

Potentially lethal voltages exist within this equipment during operation. Observe all cautions and warnings on unit and in this manual.

The Liebert iCOM microprocessor does not isolate power from the unit, even in the “Unit Off” mode. The only way to ensure that there is NO voltage inside the unit is to install and open a remote disconnect switch. Refer to unit electrical schematic.

NOTICE

Risk of improper scroll compressor installation. Could cause poor performance and compressor damage.

Three-phase power must be connected to the unit line voltage terminals in the proper sequence so that the scroll compressor rotates in the proper direction. Rotation in the wrong direction will result in poor performance and compressor damage. Use a phase sequence and motor rotation sensor to ensure that the three-phase power is correctly connected and the compressor is rotating properly.

18

Image 24
Contents Liebert Challenger 3000 with iCOM Page Table of Contents Chilled Water Models Split System ModelsR407C Refrigerant Figures Tables Important Safety Instructions Page System Descriptions Split Systems Prop Fan Air-CooledCentrifugal Fan Air-Cooled Water-CooledRoom Preparation Equipment InspectionLocation Considerations Equipment HandlingUnit net weight Handling With SkidRemoval of Skid Model Lb kgUpflow BU cabinet dimensions Floor Cutout Dimensions Piping Considerations Drain LinePiping connection size Piping Outlet Locations Piping connections for air-cooled units Upflow models Installation Applicable to all Models Installation Applicable to all Models Installation Applicable to all Models Installation Applicable to all Models Installation Applicable to all Models Installation Applicable to all Models Facility Fluid and Piping Maintenance Electrical ConnectionsHumidifier Supply Water-Optional Infrared Terminal Block for customer connections Upflow Models with Liebert iCOM Downflow Models with Liebert iCOMPlenum Installation Balancing the Air DistributionUnder-Floor Discharge Systems Ducted ApplicationsChecklist for Completed Installation Condenser Location Line VoltageLow Voltage Air-cooled condenser statistics Refrigerant Piping Recommended line sizes OD copper inchesFan Speed Control Systems Variable Fan Speed Control PipingEquivalent lengths feet for various pipe fittings Indoor unit refrigerant charge lb kgVariable Fan Speed Control Materials Supplied Fan speed suction pressure transducer settings Variable Fan Speed ChargingFactory Piping Field Piping Factory Piping Lee-Temp Leak Check and Evacuation Procedure Liebert Lee-Temp PipingLiebert Lee-Temp Controlled Materials Supplied Lee-Temp suction pressure transducer settings Lee-Temp ChargingLee-Temp Receiver Refrigerant Level 407CFactory Piping Optional Piping Pressure Relief Condenser Factory Piping Field Piping Factory Piping Field Piping Adjustment Water Regulating ValveRefrigerant control settings psi kPa Motorized Ball Valve-Digital Scroll CompressorsManual Flushing ControlStartup LocationManual Control Drycooler Installation Drycooler LocationPump and Drycooler Glycol Piping General GuidelinesRoom dew point temperatures Dry Bulb Wet Bulb Relative Dew Point HumidityVolume in standard Type L copper piping Filling InstructionsExpansion Tanks, Fluid Relief Valves and Other Devices Preparing the System for FillingGlycol Solutions Filling the System Ethylene glycol concentrations@ 50F 10C For expansion tank dimensions, see on 43-3/16 43-9/16 110 5mmSee Note 30-1/4 483mm 1097mmMounting hole dimensional data Drycooler dataGlycol pump data Pump Pump Suction Pump Discharge ConnectionField Piping General arrangement-Glycol-cooled models with digital scroll Field Piping Factorypiping Field Piping Testing Valve Function Glycol Regulating ValveMotor Ball Valve-Digital Scroll Compressors Chilled Water Models WAY Valve Air-Cooled Condensing Units Water/Glycol-Cooled Condensing UnitsRefrigerant Loop Unit refrigerant charge Line charges refrigerant per 100 ft m of Type L copper tubeRecommended refrigerant lines R407C sizes OD copper Quick Connect Fittings Line coupling sizesModel Line Size Coupling Torque Tons OD Cu, Lb-ft Unit Dimensions See Table Outdoor Air-Cooled Condensing UnitsPFCZ42A-L PFCZ41A-L Outdoor air-cooled condensing unit-top air discharge models See TablePiping and electrical connections top air discharge 36-1/4 38-1/2152 Field-supplied unit disconnect switch Ton High Ambient Ton Quiet-LineInstalling the Indoor Condensing Unit Model Net Weight 60 Hz 50 Hz Lb kg MC40A MC39ACentrifugal Air-Cooled Condensing Units Indoor centrifugal condensing unitDucting Airflow CFM CMHPiping Connections Wire connections from evaporator DPN000207Rev0 ModTon centrifugal air-cooled condensing unit dimensional data AIR Cooled Water Cooled Water and Glycol-Cooled Condensing Units Piping ConsiderationsCondenser Water Requirements Regulating ValveGlycol Systems Ton water/glycol-cooled condensing unit24V GND Ton water/glycol-cooled condensing unit dimensional data WATER/GLYCOL Temperature Gauge Pressure Psig KPa R407C RefrigerantTemperature Pressure Gauge Psig KPa Calculating SubcoolingExample R407C Refrigerant R407C Refrigerant Page Ne t Iti Ti nThat Te r Ys t
Related manuals
Manual 88 pages 63.05 Kb Manual 60 pages 24.1 Kb Manual 32 pages 13.16 Kb Manual 22 pages 3.64 Kb Manual 76 pages 17.32 Kb Manual 184 pages 52.9 Kb

3000 specifications

The Emerson 3000 is a cutting-edge control system designed to enhance the efficiency, reliability, and precision of industrial operations. Employed across various sectors such as oil and gas, pharmaceutical, food and beverage, and power generation, the Emerson 3000 has gained recognition for its robustness and versatility.

One of the main features of the Emerson 3000 is its advanced process control capability. With integrated control algorithms, it can optimize complex processes in real-time, resulting in significant improvements in production rates and reduced operational costs. The system's predictive analytics capabilities enable operators to anticipate equipment failures and maintenance needs, allowing for proactive management and minimizing downtime.

The Emerson 3000 features a modular architecture, providing flexibility for scaling and customization. Operators can easily tailor the system to fit specific application needs, whether it requires additional control loops or integration with other systems. This adaptability is particularly beneficial for facilities planning for future expansions or modifications.

Another technology highlight of the Emerson 3000 is its seamless integration with the latest Internet of Things (IoT) advancements. The system is designed to communicate effectively with a variety of smart devices and sensors, harnessing data to create insightful analytics that drive operational excellence. This connectivity empowers businesses to leverage big data for improved decision-making and increased agility.

Additionally, the Emerson 3000 incorporates state-of-the-art cybersecurity measures to safeguard critical data and operations. With built-in security protocols and regular updates, the system protects against emerging cyber threats, ensuring the integrity of the control network.

User experience is also a focal point of the Emerson 3000. The intuitive graphical user interface presents complex data in a user-friendly format, making it easier for operators to monitor system performance and respond to alerts quickly. This ease of use contributes to enhanced safety and operational efficiency.

In summary, the Emerson 3000 represents a fusion of advanced process control, modular design, IoT connectivity, robust cybersecurity, and user-centric interface, making it an ideal choice for industries seeking to enhance their operational performance while adapting to ever-evolving technological landscapes.