Emerson 3000 Balancing the Air Distribution, Under-Floor Discharge Systems, Ducted Applications

Page 27

Installation (Applicable to all Models)

2.8Balancing the Air Distribution

2.8.1Under-Floor Discharge Systems

The systems are designed for constant air delivery, therefore any unusual restrictions within the air circuit must be avoided. For under-floor air distribution, observe the following guidelines:

Select the air supply grilles and perforated panels for the raised floor to ensure minimum loss of pressure in the circuit. Air volume dampers on grilles, which extend several inches below the sur- face of the raised floor, are usually detrimental to airflow.

Consideration of the height of the damper on the grille in conjunction with the floor height will determine whether this type of grille may be used.

The grilles used in raised floors vary in size, the largest being approximately 18" x 6"

(457 x 152 mm). A larger grille size would be detrimental to the structural capacity of the raised floor panel. An 18" x 6" (457 x 152 mm) heavy duty, pencil-proof type grille typically has 56 square inches (0.036 m2) of free area.

Perforated panels are available from various manufacturers of raised floors. These panels are usually 2' x 2' (610 x 610 mm) square and have a nominal free area of approximately 108 to 144 square inches (0.07 to 0.09 m2). Use caution in selecting perforated panels as some manufacturers have only 36 to 40 square inches (0.023 to 0.026 m2) of free area, requiring four times as many panels.

Avoid floor elevations below 7-1/2" (190.5 mm), loosely installed flooring systems, and below-floor obstructions such as: electrical wiring chases, unusually long electronic system cables, or piping clusters.

Always check specifications of the floor supplier before specifying the total number of perforated panels and grilles required to handle the air flow. The proper specifications for grilles and perfo- rated panels should indicate the total free area required for air delivery rather than the number of panels and grilles. (See Table 3 for recommended free area required for each model.) This table indicates the recommended free area based on having the supply air grilles and perforated panels sized to handle approximately 75% of the total cubic feet per minute (CFM) of the units at a veloc- ity of 550 to 600 ft./min. (2.8 - 3.1 m/s). The remaining 25% of the air flow in the raised floor passes through cable cutouts, cracks between the panels, and other leakage areas.

Table 3 Recommended free area ft2 (m2) for grilles or perforated panels at output velocities of 550 and 600 fpm (2.8 and 3.1 m/s)

 

 

50 Hz Units

 

 

 

 

 

60 Hz Units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

550

 

2.8

 

600

3.1

 

 

550

 

2.8

 

600

3.1

Model

FPM

 

m/s

 

FPM

m/s

 

Model

FPM

 

m/s

 

FPM

m/s

3-ton

2.5

 

(0.01)

 

2.3

(0.01)

 

3-ton

2.5

 

(0.01)

 

2.3

(0.01)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5-ton

3.5

 

(0.02)

 

3.3

(0.02)

 

5-ton

3.8

 

(0.02)

 

3.5

(0.02)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.8.2Ducted Applications

For ducted supply applications on upflow units, the duct work should be attached to the blower dis- charge flanges of the unit. For ducted return air applications, the duct work should be attached to the filter box flanges on upflow rear return units and on the unit top flange for downflow units. Refer to Figure 2 for information on upflow units and to Figure 3 for downflow units.

The duct work on upflow units must allow access to the motors/blowers for maintenance. The duct work on upflow units must be designed within the capacity of the unit, otherwise air flow and perfor- mance will be compromised.

2.8.3Plenum Installation

A solid plenum or plenum with discharge grille(s) may be installed. The plenum and instructions for its installation ship separately from the unit.

21

Image 27
Contents Liebert Challenger 3000 with iCOM Page Table of Contents Chilled Water Models Split System ModelsR407C Refrigerant Figures Tables Important Safety Instructions Page System Descriptions Water-Cooled Split SystemsProp Fan Air-Cooled Centrifugal Fan Air-CooledEquipment Handling Room PreparationEquipment Inspection Location ConsiderationsModel Lb kg Unit net weightHandling With Skid Removal of SkidUpflow BU cabinet dimensions Floor Cutout Dimensions Piping Considerations Drain LinePiping connection size Piping Outlet Locations Piping connections for air-cooled units Upflow models Installation Applicable to all Models Installation Applicable to all Models Installation Applicable to all Models Installation Applicable to all Models Installation Applicable to all Models Installation Applicable to all Models Facility Fluid and Piping Maintenance Electrical ConnectionsHumidifier Supply Water-Optional Infrared Terminal Block for customer connections Downflow Models with Liebert iCOM Upflow Models with Liebert iCOMDucted Applications Plenum InstallationBalancing the Air Distribution Under-Floor Discharge SystemsChecklist for Completed Installation Condenser Location Line VoltageLow Voltage Air-cooled condenser statistics Recommended line sizes OD copper inches Refrigerant PipingIndoor unit refrigerant charge lb kg Fan Speed Control SystemsVariable Fan Speed Control Piping Equivalent lengths feet for various pipe fittingsVariable Fan Speed Control Materials Supplied Variable Fan Speed Charging Fan speed suction pressure transducer settingsFactory Piping Field Piping Factory Piping Lee-Temp Leak Check and Evacuation Procedure Liebert Lee-Temp PipingLiebert Lee-Temp Controlled Materials Supplied 407C Lee-Temp suction pressure transducer settingsLee-Temp Charging Lee-Temp Receiver Refrigerant LevelFactory Piping Optional Piping Pressure Relief Condenser Factory Piping Field Piping Factory Piping Field Piping Water Regulating Valve AdjustmentControl Refrigerant control settings psi kPaMotorized Ball Valve-Digital Scroll Compressors Manual FlushingStartup LocationManual Control Drycooler Installation Drycooler LocationPump and Drycooler General Guidelines Glycol PipingDry Bulb Wet Bulb Relative Dew Point Humidity Room dew point temperaturesPreparing the System for Filling Volume in standard Type L copper pipingFilling Instructions Expansion Tanks, Fluid Relief Valves and Other DevicesGlycol Solutions Filling the System Ethylene glycol concentrations@ 50F 10C 483mm 1097mm For expansion tank dimensions, see on43-3/16 43-9/16 110 5mm See Note 30-1/4Pump Pump Suction Pump Discharge Connection Mounting hole dimensional dataDrycooler data Glycol pump dataField Piping General arrangement-Glycol-cooled models with digital scroll Field Piping Factorypiping Field Piping Testing Valve Function Glycol Regulating ValveMotor Ball Valve-Digital Scroll Compressors Chilled Water Models WAY Valve Water/Glycol-Cooled Condensing Units Air-Cooled Condensing UnitsRefrigerant Loop Unit refrigerant charge Line charges refrigerant per 100 ft m of Type L copper tubeRecommended refrigerant lines R407C sizes OD copper Quick Connect Fittings Line coupling sizesModel Line Size Coupling Torque Tons OD Cu, Lb-ft Outdoor Air-Cooled Condensing Units Unit Dimensions See TablePFCZ42A-L PFCZ41A-L See Table Outdoor air-cooled condensing unit-top air discharge modelsPiping and electrical connections top air discharge 36-1/4 38-1/2152 Ton High Ambient Ton Quiet-Line Field-supplied unit disconnect switchIndoor centrifugal condensing unit Installing the Indoor Condensing UnitModel Net Weight 60 Hz 50 Hz Lb kg MC40A MC39A Centrifugal Air-Cooled Condensing UnitsAirflow CFM CMH DuctingPiping Connections Mod Wire connections from evaporatorDPN000207 Rev0Ton centrifugal air-cooled condensing unit dimensional data AIR Cooled Water Cooled Regulating Valve Water and Glycol-Cooled Condensing UnitsPiping Considerations Condenser Water RequirementsTon water/glycol-cooled condensing unit Glycol Systems24V GND Ton water/glycol-cooled condensing unit dimensional data WATER/GLYCOL R407C Refrigerant Temperature Gauge Pressure Psig KPaTemperature Pressure Gauge Psig KPa Calculating SubcoolingExample R407C Refrigerant R407C Refrigerant Page Te r Ys t Ne tIti Ti n That
Related manuals
Manual 88 pages 63.05 Kb Manual 60 pages 24.1 Kb Manual 32 pages 13.16 Kb Manual 22 pages 3.64 Kb Manual 76 pages 17.32 Kb Manual 184 pages 52.9 Kb

3000 specifications

The Emerson 3000 is a cutting-edge control system designed to enhance the efficiency, reliability, and precision of industrial operations. Employed across various sectors such as oil and gas, pharmaceutical, food and beverage, and power generation, the Emerson 3000 has gained recognition for its robustness and versatility.

One of the main features of the Emerson 3000 is its advanced process control capability. With integrated control algorithms, it can optimize complex processes in real-time, resulting in significant improvements in production rates and reduced operational costs. The system's predictive analytics capabilities enable operators to anticipate equipment failures and maintenance needs, allowing for proactive management and minimizing downtime.

The Emerson 3000 features a modular architecture, providing flexibility for scaling and customization. Operators can easily tailor the system to fit specific application needs, whether it requires additional control loops or integration with other systems. This adaptability is particularly beneficial for facilities planning for future expansions or modifications.

Another technology highlight of the Emerson 3000 is its seamless integration with the latest Internet of Things (IoT) advancements. The system is designed to communicate effectively with a variety of smart devices and sensors, harnessing data to create insightful analytics that drive operational excellence. This connectivity empowers businesses to leverage big data for improved decision-making and increased agility.

Additionally, the Emerson 3000 incorporates state-of-the-art cybersecurity measures to safeguard critical data and operations. With built-in security protocols and regular updates, the system protects against emerging cyber threats, ensuring the integrity of the control network.

User experience is also a focal point of the Emerson 3000. The intuitive graphical user interface presents complex data in a user-friendly format, making it easier for operators to monitor system performance and respond to alerts quickly. This ease of use contributes to enhanced safety and operational efficiency.

In summary, the Emerson 3000 represents a fusion of advanced process control, modular design, IoT connectivity, robust cybersecurity, and user-centric interface, making it an ideal choice for industries seeking to enhance their operational performance while adapting to ever-evolving technological landscapes.