period one

Fundamentals of Sound

notes

Again, a pure tone has a single frequency. If a sound in a narrow band of frequencies is significantly greater than the sound at adjacent frequencies, it would be similar to a tone. Tones that stand out enough from the background sound can be objectionable. Many of the sounds generated by HVAC equipment and systems include both broadband and tonal characteristics.

Octave Bands

octave

 

center

 

frequency

 

 

band

 

frequency (Hz)

 

range (Hz)

1

 

63

 

45 to 90

2

 

125

 

90 to 180

3

 

250

 

180 to 355

4

 

500

 

355 to 710

5

 

1,000

 

710 to 1,400

6

 

2,000

 

1,400 to 2,800

7

 

4,000

 

2,800 to 5,600

8

 

8,000

 

5,600 to 11,200

 

 

 

 

 

Figure 8

Octave Bands

Because sound occurs over a range of frequencies, it is considerably more difficult to measure than temperature or pressure. The sound must be measured at each frequency in order to understand how it will be perceived in a particular environment. The human ear can perceive sounds at frequencies ranging from 20 to 16,000 Hz, whereas, HVAC system designers generally focus on sounds in the frequencies between 45 and 11,200 Hz. Despite this reduced range, measuring a sound at each frequency would result in 11,156 data points.

For some types of analyses, it is advantageous to measure and display the sound at each frequency over the entire range of frequencies being studied. This is called a full-spectrum analysis and is displayed like the example shown in Figure 7.

To make the amount of data more manageable, this range of frequencies is typically divided into smaller ranges called octave bands. Each octave band is defined such that the highest frequency in the band is two times the lowest frequency. The octave band is identified by its center frequency, which is calculated by taking the square root of the product of the lowest and highest frequencies in the band.

center frequency = lowest frequency × highest frequency

The result is that this frequency range (45 to 11,200 Hz) is separated into eight octave bands with center frequencies of 63, 125, 250, 500, 1,000, 2,000, 4,000, and 8,000 Hz. For example, sounds that occur at the frequencies between 90 Hz and 180 Hz are grouped together in the 125 Hz octave band.

6

TRG-TRC007-EN

Image 13
Contents Air Conditioning Clinic Fundamentals of Hvac Acoustics Business Reply Mail One of the Fundamental Series Comment CardFundamentals of Hvac Acoustics Fundamentals of Hvac Acoustics PrefaceContents TRG-TRC007-EN Fundamentals of Sound Fundamentals of SoundWhat is Sound? What is Sound?Sound Wave and Frequency Wavelength Broadband Sound and Tones Broadband SoundOctave Bands Octave BandsLogarithmic sums One-Third Octave Bands Sound Power and Sound Pressure Sound Power and Sound PressureAn Analogy Decibel DB = 10 log10 ´ log Logarithmic ScaleEquation for Sound Pressure Equation for Sound Power50 dB + 44 dB = 51 dB Logarithmic Addition of DecibelsHuman Ear Sound Perception Rating MethodsHuman Ear Response Loudness Contours Single-Number Rating Methods Response to TonesSingle-Number Rating Methods Sound Perception and Rating Methods C WeightingWeighting Example Weighting Noise Criteria NC Curves NC-39 Room Criteria RC Curves MPa DB ref Pressure Sound Perception and Rating Methods RC-31 R Phon and Sone Octave-Band Rating Method Octave-Band Rating MethodAcoustical Analysis Acoustical AnalysisSetting a Design Goal Setting a Design GoalAcoustical Analysis Source-Path-Receiver Analysis Acoustical AnalysisSource-Path-Receiver Model Airborne Typical Sound PathsExample of Multiple Sound Paths Examples of a Single Sound PathIdentifying Sound Sources and Paths Sound-Path Modeling Modeling Sound PathsSupply Algorithms for Sound-Path Modeling Computerized Analysis Tools Terms Used in Sound-Path Modeling Attenuation and RegenerationSound Transmission Insertion loss IL Noise reduction NR Transmission loss TL Absorption Reflected Sound Receiver Sound Correction Equipment Sound Rating Equipment Sound RatingFields of Measurement Free FieldDistance Correction in a Free Field = L p1 20 logLot Near Field Reverberant Field Semireverberant Field Hvac Equipment Sound Rating Rating Hvac EquipmentReverberant-Room Method Free-Field Method Industry Standards Ducted Air-Handling Equipment Air Handler Test Configurations Former Methods of Sound Testing ARI Standard Sound Power by Octave Band Review-Period One ReviewNoise criteria NC Room criteria RC Review-Period TwoReview-Period Three Review-Period Four Review Questions for Period QuizOctave-band frequency, Hz Answers Glossary Glossary Room effect See receiver room correction Glossary Trane