Operation information

peak operating efficiency. An outside air temperature and relative humidity sensor are provided for field installation to monitor reference enthalpy. Economizer operation enables when the outside air enthalpy is less than 25 BTu/lb (adjustable 19-28 BTu/lb.). During occupied mode, the outside air damper opens to 15% (adjustable 0-100%) for ventilation purposes. Also, the ability to alter the outside air damper position to compensate forVAV supply air modulation is inherent in the unit controls, and can be enabled by the operator. An analog 2-10 VDC output (adjustable (0-10 VDC) is provided to modulate the field- provided 30 second damper actuators (adjustable 1-255 seconds).

Airside Economizer Interface with Comparative Enthalpy

temperature and relative humidity sensors, are provided for monitoring outside and return air.The sensors are field installed. Economizer operation enables when the outside air enthalpy is 3 BTU’s/lb. less than the return air enthalpy. During occupied mode, the outside air damper opens to 15% (adjustable 0-100%) for ventilation purposes. Also, the ability to alter the outside air damper position to compensate forVAV supply air modulation is inherent in the unit controls, and can be enabled by the operator. An analog 2-10VDC output (adjustable (0-10 VDC) is provided to modulate the field-provided 30-second damper actuators (adjustable 1-255 seconds).

Air-Cooled Condensers

Model SXRF units are designed for use with the remote air-cooled condenser, model CXRC. For more information, see the air-cooled condenser Installation, Owner, and Diagnostic Manual, CXRC- SVX01A-EN.

Condenser fans will stage per a user- defined setting. If the condenser is equipped with head pressure control (air modulation on last stage of condenser capacity), the condenser airflow will modulate to maintain condensing temperature setpoint. Condensing temperature is determined by sensors located at each condenser coil.

Units with airside economizer interface and comparative enthalpy are equipped with the necessary control sequences to allow using outside air for the first stage of cooling, in occupied or unoccupied mode and when ambient conditions are favorable for economizing. Inherent in the unit controller is the ability to suppress the setpoint below the normal unit setpoint. This allows the building to improve comfort levels when possible, and at the same time, optimize building mechanical cooling operation for peak operating efficiency. A factory-installed control board, with outside and return air

Figure O-GI-6. CO2 reset function, outside air vs. CO2

SCXG-SVX01B-EN

81

Image 81
Contents Models JO and later design sequenceHazard Identification IntroductionSpecial Note on Refrigeration Emissions HazardousVoltage w/CapacitorsContents Refrigerant Handling Procedures Features and BenefitsModular Series Self-Contained Unit Components Unit Nameplate Installation informationModel Number Description Model Number Description ScwgDigit 22 Unit Finish Digit 31 Compressor ServiceValvesDigit Digit 24 Unit ConnectionModel Number Description Pswg Self-Contained Ship-WithAccessory Model Number DescriptionAfter-ShipmentAccessory Model Number Shipping Package Receiving and HandlingInstallation Preparation Table I-PC-1. Service and code clearance requirements ServiceAccessSection TopView CCRC/CIRC 20, 29Lifting Equipment Capacity Rigging and Unit HandlingFigure I-PC-7.Assembled modular unit proper rigging Unit Handling ProcedureIntelliPak UnitsUCM Only Split-Apart Unit AssemblyRemove panels FML, FMM, and FMR Units with Thermostat OnlyFigure I-PC-9 How to assemble the split apart modular unit Pre-Installation Checklist Skid RemovalExternal Unit Isolation Weights DimensionsSCWG/SIWG Dimensions, Left-side viewSCRG/SIRG Dimensions, SCRG/SIRGWeight, lbsLeft-side View Right-side view Top view Detail Dimensions, Dimensions WeightsCCRC/CIRC -Air-Cooled Condenser CCRC/CIRC Air-cooled condenser dimensions & weight, in-lbsCCRC/CIRC Electrical connections, CCRC/CIRC Refrigerant connections,Hot Water Coil Hot water coil dimensions & weight, in-lbsSteam Coil Steam coil dimensions, in-lbsElectric heat coil dimensions & weight, in-lbs Electric Heat CoilFlexible Horizontal Discharge Plenum Waterside Economizer Waterside economizer weight, in-lbsAirside economizer dimensions & weight, in-lbs Airside EconomizerDetail a Detail B Variable Frequency Drive Option VFD Dimensions Weights VFDControl and LineVoltage Result in death or serious injury Mounting RequirementsElectrical Installation Procedure VFD with bypass dimensions,Variable Frequency Drive with Bypass Duct Connections Mechanical SpecificationsWater Piping Hazardous Voltage w/Capaci- torsTable I-MR-1. Water Connection Sizes Waterside Piping ArrangementsBrazing Procedures Refrigerant Piping Air-Cooled Units OnlyHazard of Explosion and Deadly Gases Supply PowerWiring Unit Wiring DiagramsLive Electrical Components Equipment DamageSelection Procedures Pre-Startup Procedures Installation requirementsSupply Fan Isolators Shipping bracketFigure I-PR-3. Correct plenum insulation placement Unit Installation Airside Economizer InstallationField Wiring Connections Unit HandlingStatic PressureTransducer Installation VAV units only Installing theTransducerTransducer Location Figure I-PR-7. Installing the waterside economizer Waterside Economizer Installation ProcedureTubing assemblies for waterside econo Mizer left-hand piping Waterside Economizer Ship-Separate Parts List Hydronic Coil Installation Installation ProcedureUnit Structural Integrity Electric Heat Installation Electric Heat CoilWiring ProcedureTable I-PR-2.Available Electric Heat kW Zone Sensor Options for IntelliPak Control Units Standard with All IntelliPak UnitsCV Unit Zone Sensor Options BAYSENS077* DescriptionVAV Unit Zone Sensor Option CV andVAV Unit Zone Sensor OptionsBAYSENS074 Description BAYSENS073 DescriptionWiring Zone Sensor InstallationMounting Location Mounting the SubbaseRight Mounting Directly to the Wall Mounting to Junction Box ConstantVolume Zone Sensor BAYSENS019 Description Variable AirVolume Zone Sensor BAYSENS020B DescriptionProgrammable Zone Sensors Airflows from adjacent zones or other units Programmable Zone Sensor InstallationTime Clock Installation Checklist Time Clock InstallationWiring theTimeclock Time Clock OptionHuman Interface HI Panel Remote Human Interface Panel InstallationRemote Human Interface Panel Location RecommendationsProcedure Mounting the Remote Human Interface RHI PanelWall Mounting the RHI Panel Pre-startup LowVoltage AC FieldWiring Connections Wiring the Remote Human InterfaceCommunication Link ShieldedTwisted PairWiring Interprocessor Communication Bridge ModuleWiringPre-Startup Checklist Connecting toTracer SummitProgrammable Zone Sensor Options Installation programmingDuring Programming Indicates Heat supply air Cool supply air Warmup temperatureKeypad Operation Time Button Temporary Manual OverrideKeypad Lockout Up and Down Button ArrowsFigure I-P-6.Temporary manual override menu screen Temporary Override Run ModeTable I-P-1. Zone sensor BAYSENS019 option menu settings Figure I-P-7.Temporary manual override run mode screenIntelligent Copy Remote Panel Indicator Signals From UCM to ZSMTo use Intelligent Copy Off FlashingFigure I-P-9.BAYSENS019 complete icon display Icon DescriptionsFigure I-P-10.BAYSENS020 complete icon display Programming theTime Clock Option Setting theTimeProgramming To review and change programsUnit Startup Procedures Installation startupPre-Startup Checklist Compressor DamageStartup Log EvaporatorCompressor Amp Draw Air Cooled Units Water Cooled UnitsPoints List Gbas Module Points List RTM ModulePoints List Ecem Module Points List -TracerTMLCI-I ModuleRTM Module Board Standard on all Units Unit Control ComponentsTable O-GI-2. RTM sensor resistance vs. temperature VAV Box OptionTable O-GI-3. RTM setpoint analog inputs Human Interface Module Standard on all Units Heat ModuleVentilation Override Module VOM Option Supply fan on Supply fan VFD on if equipped Purge sequence DGeneric BuildingAutomation System Module Option Table O-GI-7. Gbas input voltage corresponding setpoints Table O-GI-6. Gbas analog input setpointsWaterside Components Figure O-GI-3. Basic water piping, constant water flow UnitAirside Components General Operation information Air-Cooled Condensers Airside Economizer Interface with Comparative EnthalpyProperWaterTreatment Input Devices and System FunctionsSupply Air Temperature Sensor Return AirTemperature SensorSupply Airflow Proving Switches Filter SwitchControl Sequences Operation Operation operationUnoccupied Sequence of Operation Tracer Summit SystemMorning Warmup Cycling Capacity Morning Warmup MWUTimed Override Activation ICS Occupied Sequence Mechanical Cooling Supply Air Setpoint Reset VAV Units OnlyWater-Cooled Units Only Electric HeatCompressors Compressor Lead/Lag OperationTable O-SO-1. Compressor Stages Step Control Evaporator Coil Frost ProtectionTable O-SO-2. Pressure cutouts Operation Service Valve OptionTable M-GI-1. SCWG/SIWG/SCRG/SIRG General Maintenance Data Maintenance informationMaintenance procedures Maintenance ProceduresAir Filters Inspecting and Cleaning the Drain Pan Inspecting and Cleaning the FanRemove all standing water Supply Fan Variable Frequency Drive VFDFan Drive Table M-MP-1. Baldor Fan Bearing Lubrication Schedule Fan BearingsTable M-MP-2.AO Smith Bearing Lubrication Schedule Table M-MP-3. Compatible Fan Bearing GreaseFan BeltTension Deflection = belt span/64Table M-MP-4. Fan shaft bearing torques Belt Adjusting BeltTensionRefrigerant System Confined Space HazardsRefrigerant Evacuation Motor Winding Damage Refrigerant LeakTestingUse of Pressure Regulator Valves Gauges R407cMaintenance Coil Fin Cleaning Proper Coil CleaningAgentInlet GuideVanes Coil Freezeup Flow Switch Maintenance Chemical Cleaning of Condenser and Economizer CoilCleaning the Flow Switch Piping ComponentsMonthly Checklist Maintenance Periodic ChecklistsSemi-Annual Maintenance Annual MaintenanceOperating Procedures Check the zone thermostat settingsCommon Unit Problems and Solutions System ChecksDiagnostics Maintenance diagnosticsEmergency Stop Heat Module Auxilliary Temperature Sensor FailEntering Cond WaterTemp Sensor Fail Entering Water Temp Sensor FailLow Air Temp Limit Trip Mode Input FailureLow Pressure Control Open Circuit 1, 2, 3, or MCM Communications FailureCheck Field/unit wiring between RTM and NSB Panel NSB Panel ZoneTemperature Sensor FailureHumidity Sensor Failure Temp. Sensor FailureRTM Zone Sensor Failure RTM Data Storage ErrorProblemThe LCI-I has lost communication withTracer Summit Supply Fan VFD Bypass EnabledSupply Fan Failure LCI-I Module Comm FailureRender all HI keystrokes ineffective VOM Communications FailureWSM Communications Fail Water Flow Fail WSM Mixed AirTemp Sensor Fail114 115 Literature Order Number

SCXG-SVX01B-EN specifications

The Trane SCXG-SVX01B-EN is an advanced variable refrigerant flow (VRF) system designed to provide efficient and flexible heating and cooling solutions for commercial and residential applications. This system exemplifies Trane's commitment to innovation, energy efficiency, and ease of installation, making it a standout choice in the industry.

One of the main features of the SCXG-SVX01B-EN is its ability to deliver precise temperature control across multiple zones. The system utilizes a modular design that allows for the connection of multiple indoor units to a single outdoor unit, enabling simultaneous heating and cooling in different areas of a building. This zoned comfort not only enhances occupant satisfaction but also contributes to energy savings by allowing for targeted climate control where it is most needed.

Trane's VRF technology is complemented by its inverter-driven compressors, which adjust their speed according to the demand for heating or cooling. This means that the system operates more efficiently than traditional systems by consuming less energy during partial load conditions. The SCXG-SVX01B-EN also integrates advanced heat recovery capabilities, allowing it to transfer heat from one zone to another, further optimizing energy usage.

The unit's compact design simplifies installation, making it suitable for both retrofit projects and new constructions. The flexible piping layout supports various configurations, allowing easy adaptation to the building's architecture. The model also incorporates intelligent controls, offering a user-friendly interface that enhances operational flexibility and promotes energy management.

In addition to its performance features, the Trane SCXG-SVX01B-EN emphasizes sustainability. It uses advanced refrigerants with low global warming potential (GWP), aligning with environmental regulations and helping to minimize the system's ecological footprint. The durable construction of the system ensures longevity and reliability, reducing maintenance costs and enhancing overall operational efficiency.

Finally, Trane supports its products with comprehensive warranties and a network of service professionals, ensuring that customers have access to expert assistance throughout the life cycle of their system. The SCXG-SVX01B-EN represents a blend of technology, efficiency, and versatility, making it an ideal choice for those seeking an effective heating and cooling solution.