Trane SCXG-SVX01B-EN manual Inspecting and Cleaning the Drain Pan, Inspecting and Cleaning the Fan

Page 93

maintenance

Maintenance procedures

Inspecting and Cleaning the Drain Pan

Check the condensate drain pan and drain line to ensure that the condensate drains properly at least every six months or as dictated by operating experience.

If evidence of standing water or conden- sate overflow exists, take steps to identify and remedy the cause immediately. Refer to the trouble shooting section of this manual for possible causes and solutions.

￿WARNING

Hazardous Voltage w/Capaci- tors!

Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout proce- dures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided byTrane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors.Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.

Note: For additional information regard- ing the safe discharge of capacitors, see PROD-SVB06A-EN or PROD-SVB06A-FR.

Clean drain pans using the following procedure:

1.Disconnect all electrical power to the unit.

2.Don the appropriate personal protective equipment (PPE).

3.Remove all standing water.

4.Use a scraper or other tools to remove and solid matter. Remove solid matter with a vacuum device that utilizes high efficiency particulate arrestance (HEPA) filters with a minimum efficiency of 99.97% at 0.3 micron particle size.

5.Thoroughly clean the contaminated area(s) with a mild bleach and water solution or an EPA-approved sanitizer specifically designed for HVAC use.

Carefully follow the sanitizer manufacturer’s instructions regarding product use.

6.Immediately rinse the drain pan thoroughly with fresh water to prevent potential corrosion from the cleaning solution.

7.Allow the unit to dry thoroughly before putting the system back into service.

8.Properly dispose of all contaminated materials and cleaning solution.

Inspecting and Cleaning the Fan

Inspect the fan section every six months or more frequently if operating experience dictates. Clean accumulated dirt and organic matter on the fan interior surfaces following the procedure below:

1.Disconnect all electrical power to the unit.

2.Wear the appropriate personal protective equipment (PPE).

3.Use a portable vacuum with HEPA filtration to remove the loose dirt and organic matter.The filter should be 99.97% efficient at 0.3 micron particle size.

4.Thoroughly clean the fan and associated components with an industrial cleaning solution. Carefully follow the cleaning solution manufacturer’s instructions regarding personal protection and ventilation when using their product.

5.Rinse the affected surfaces thoroughly with fresh water and a fresh sponge to prevent potential corrosion of metal surfaces.

6.Allow the unit to dry completely before putting it back into service.

7.Properly dispose of all contaminated materials and cleaning solution.

SCXG-SVX01B-EN

93

Image 93
Contents Models JO and later design sequenceHazard Identification IntroductionSpecial Note on Refrigeration Emissions HazardousVoltage w/CapacitorsContents Refrigerant Handling Procedures Features and BenefitsModular Series Self-Contained Unit Components Unit Nameplate Installation informationModel Number Description Model Number Description ScwgDigit 22 Unit Finish Digit 31 Compressor ServiceValvesDigit Digit 24 Unit ConnectionModel Number Description Pswg Self-Contained Ship-WithAccessory Model Number DescriptionAfter-ShipmentAccessory Model Number Shipping Package Receiving and HandlingInstallation Preparation Table I-PC-1. Service and code clearance requirements ServiceAccessSection TopView CCRC/CIRC 20, 29Lifting Equipment Capacity Rigging and Unit HandlingFigure I-PC-7.Assembled modular unit proper rigging Unit Handling ProcedureIntelliPak UnitsUCM Only Split-Apart Unit AssemblyRemove panels FML, FMM, and FMR Units with Thermostat OnlyFigure I-PC-9 How to assemble the split apart modular unit Pre-Installation Checklist Skid RemovalExternal Unit Isolation Weights DimensionsSCWG/SIWG Dimensions, Left-side viewSCRG/SIRG Dimensions, SCRG/SIRGWeight, lbsLeft-side View Right-side view Top view Detail Dimensions, Dimensions WeightsCCRC/CIRC -Air-Cooled Condenser CCRC/CIRC Air-cooled condenser dimensions & weight, in-lbsCCRC/CIRC Electrical connections, CCRC/CIRC Refrigerant connections,Hot Water Coil Hot water coil dimensions & weight, in-lbsSteam Coil Steam coil dimensions, in-lbsElectric heat coil dimensions & weight, in-lbs Electric Heat CoilFlexible Horizontal Discharge Plenum Waterside Economizer Waterside economizer weight, in-lbsAirside economizer dimensions & weight, in-lbs Airside EconomizerDetail a Detail B Variable Frequency Drive Option VFD Dimensions Weights VFDControl and LineVoltage Result in death or serious injury Mounting RequirementsElectrical Installation Procedure VFD with bypass dimensions,Variable Frequency Drive with Bypass Duct Connections Mechanical SpecificationsWater Piping Hazardous Voltage w/Capaci- torsTable I-MR-1. Water Connection Sizes Waterside Piping ArrangementsBrazing Procedures Refrigerant Piping Air-Cooled Units OnlyHazard of Explosion and Deadly Gases Supply PowerWiring Unit Wiring DiagramsLive Electrical Components Equipment DamageSelection Procedures Pre-Startup Procedures Installation requirementsSupply Fan Isolators Shipping bracketFigure I-PR-3. Correct plenum insulation placement Unit Installation Airside Economizer InstallationField Wiring Connections Unit HandlingStatic PressureTransducer Installation VAV units only Installing theTransducerTransducer Location Figure I-PR-7. Installing the waterside economizer Waterside Economizer Installation ProcedureTubing assemblies for waterside econo Mizer left-hand piping Waterside Economizer Ship-Separate Parts List Hydronic Coil Installation Installation ProcedureUnit Structural Integrity Electric Heat Installation Electric Heat CoilWiring ProcedureTable I-PR-2.Available Electric Heat kW Zone Sensor Options for IntelliPak Control Units Standard with All IntelliPak UnitsCV Unit Zone Sensor Options BAYSENS077* DescriptionVAV Unit Zone Sensor Option CV andVAV Unit Zone Sensor OptionsBAYSENS074 Description BAYSENS073 DescriptionWiring Zone Sensor InstallationMounting Location Mounting the SubbaseRight Mounting Directly to the Wall Mounting to Junction Box ConstantVolume Zone Sensor BAYSENS019 Description Variable AirVolume Zone Sensor BAYSENS020B DescriptionProgrammable Zone Sensors Airflows from adjacent zones or other units Programmable Zone Sensor InstallationTime Clock Installation Checklist Time Clock InstallationWiring theTimeclock Time Clock OptionHuman Interface HI Panel Remote Human Interface Panel InstallationRemote Human Interface Panel Location RecommendationsProcedure Mounting the Remote Human Interface RHI PanelWall Mounting the RHI Panel Pre-startup LowVoltage AC FieldWiring Connections Wiring the Remote Human InterfaceCommunication Link ShieldedTwisted PairWiring Interprocessor Communication Bridge ModuleWiringPre-Startup Checklist Connecting toTracer SummitProgrammable Zone Sensor Options Installation programmingDuring Programming Indicates Heat supply air Cool supply air Warmup temperatureKeypad Operation Time Button Temporary Manual OverrideKeypad Lockout Up and Down Button ArrowsFigure I-P-6.Temporary manual override menu screen Temporary Override Run ModeTable I-P-1. Zone sensor BAYSENS019 option menu settings Figure I-P-7.Temporary manual override run mode screenIntelligent Copy Remote Panel Indicator Signals From UCM to ZSMTo use Intelligent Copy Off FlashingFigure I-P-9.BAYSENS019 complete icon display Icon DescriptionsFigure I-P-10.BAYSENS020 complete icon display Programming theTime Clock Option Setting theTimeProgramming To review and change programsUnit Startup Procedures Installation startupPre-Startup Checklist Compressor DamageStartup Log EvaporatorCompressor Amp Draw Air Cooled Units Water Cooled UnitsPoints List Gbas Module Points List RTM ModulePoints List Ecem Module Points List -TracerTMLCI-I ModuleRTM Module Board Standard on all Units Unit Control ComponentsTable O-GI-2. RTM sensor resistance vs. temperature VAV Box OptionTable O-GI-3. RTM setpoint analog inputs Human Interface Module Standard on all Units Heat ModuleVentilation Override Module VOM Option Supply fan on Supply fan VFD on if equipped Purge sequence DGeneric BuildingAutomation System Module Option Table O-GI-7. Gbas input voltage corresponding setpoints Table O-GI-6. Gbas analog input setpointsWaterside Components Figure O-GI-3. Basic water piping, constant water flow UnitAirside Components General Operation information Air-Cooled Condensers Airside Economizer Interface with Comparative EnthalpyProperWaterTreatment Input Devices and System FunctionsSupply Air Temperature Sensor Return AirTemperature SensorSupply Airflow Proving Switches Filter SwitchControl Sequences Operation Operation operationUnoccupied Sequence of Operation Tracer Summit SystemMorning Warmup Cycling Capacity Morning Warmup MWUTimed Override Activation ICS Occupied Sequence Mechanical Cooling Supply Air Setpoint Reset VAV Units OnlyWater-Cooled Units Only Electric HeatCompressors Compressor Lead/Lag OperationTable O-SO-1. Compressor Stages Step Control Evaporator Coil Frost ProtectionTable O-SO-2. Pressure cutouts Operation Service Valve OptionTable M-GI-1. SCWG/SIWG/SCRG/SIRG General Maintenance Data Maintenance informationMaintenance procedures Maintenance ProceduresAir Filters Inspecting and Cleaning the Drain Pan Inspecting and Cleaning the FanRemove all standing water Supply Fan Variable Frequency Drive VFDFan Drive Table M-MP-1. Baldor Fan Bearing Lubrication Schedule Fan BearingsTable M-MP-2.AO Smith Bearing Lubrication Schedule Table M-MP-3. Compatible Fan Bearing GreaseFan BeltTension Deflection = belt span/64Table M-MP-4. Fan shaft bearing torques Belt Adjusting BeltTensionRefrigerant System Confined Space HazardsRefrigerant Evacuation Motor Winding Damage Refrigerant LeakTestingUse of Pressure Regulator Valves Gauges R407cMaintenance Coil Fin Cleaning Proper Coil CleaningAgentInlet GuideVanes Coil Freezeup Flow Switch Maintenance Chemical Cleaning of Condenser and Economizer CoilCleaning the Flow Switch Piping ComponentsMonthly Checklist Maintenance Periodic ChecklistsSemi-Annual Maintenance Annual MaintenanceOperating Procedures Check the zone thermostat settingsCommon Unit Problems and Solutions System ChecksDiagnostics Maintenance diagnosticsEmergency Stop Heat Module Auxilliary Temperature Sensor FailEntering Cond WaterTemp Sensor Fail Entering Water Temp Sensor FailLow Air Temp Limit Trip Mode Input FailureLow Pressure Control Open Circuit 1, 2, 3, or MCM Communications FailureCheck Field/unit wiring between RTM and NSB Panel NSB Panel ZoneTemperature Sensor FailureHumidity Sensor Failure Temp. Sensor FailureRTM Zone Sensor Failure RTM Data Storage ErrorProblemThe LCI-I has lost communication withTracer Summit Supply Fan VFD Bypass EnabledSupply Fan Failure LCI-I Module Comm FailureRender all HI keystrokes ineffective VOM Communications FailureWSM Communications Fail Water Flow Fail WSM Mixed AirTemp Sensor Fail114 115 Literature Order Number

SCXG-SVX01B-EN specifications

The Trane SCXG-SVX01B-EN is an advanced variable refrigerant flow (VRF) system designed to provide efficient and flexible heating and cooling solutions for commercial and residential applications. This system exemplifies Trane's commitment to innovation, energy efficiency, and ease of installation, making it a standout choice in the industry.

One of the main features of the SCXG-SVX01B-EN is its ability to deliver precise temperature control across multiple zones. The system utilizes a modular design that allows for the connection of multiple indoor units to a single outdoor unit, enabling simultaneous heating and cooling in different areas of a building. This zoned comfort not only enhances occupant satisfaction but also contributes to energy savings by allowing for targeted climate control where it is most needed.

Trane's VRF technology is complemented by its inverter-driven compressors, which adjust their speed according to the demand for heating or cooling. This means that the system operates more efficiently than traditional systems by consuming less energy during partial load conditions. The SCXG-SVX01B-EN also integrates advanced heat recovery capabilities, allowing it to transfer heat from one zone to another, further optimizing energy usage.

The unit's compact design simplifies installation, making it suitable for both retrofit projects and new constructions. The flexible piping layout supports various configurations, allowing easy adaptation to the building's architecture. The model also incorporates intelligent controls, offering a user-friendly interface that enhances operational flexibility and promotes energy management.

In addition to its performance features, the Trane SCXG-SVX01B-EN emphasizes sustainability. It uses advanced refrigerants with low global warming potential (GWP), aligning with environmental regulations and helping to minimize the system's ecological footprint. The durable construction of the system ensures longevity and reliability, reducing maintenance costs and enhancing overall operational efficiency.

Finally, Trane supports its products with comprehensive warranties and a network of service professionals, ensuring that customers have access to expert assistance throughout the life cycle of their system. The SCXG-SVX01B-EN represents a blend of technology, efficiency, and versatility, making it an ideal choice for those seeking an effective heating and cooling solution.