Trane SCXG-SVX01B-EN manual General Operation information

Page 80

general

Operation information

stage of cooling, in occupied or unoccupied mode and when ambient conditions are favorable for economizing. Inherent in the unit controller is the ability to suppress the setpoint below the normal unit setpoint. This allows the building to improve comfort levels when possible, and at the same time, optimize building mechanical cooling operation for peak operating efficiency. An outside air temperature and relative humidity sensor are provided to allow monitoring of reference enthalpy and are field installed.

If the unit has the ECEM board, econo- mizer operation enables when the outside air enthalpy is less than 25 BTU’s/ lb. default (adjustable 19-28 BTU’s/lb). During occupied mode, the outside air damper opens to 15% (adjustable 0- 100% at the HI) for ventilation purposes. Also, the ability to alter the outside air damper position to compensate forVAV supply air modulation is inherent in the unit controls, and can be enabled by the operator.

If the unit does not have an ECEM board, it will economize when the O/A tempera- ture falls below the O/A economizer setpoint.

The mixing box fabrication is galvanized steel. Opposed low leak damper blades are fabricated from galvanized steel and rotate on rustproof nylon bushings. A factory installed 24V modulating spring return actuator controls both damper positions.

When outdoor conditions are not suitable for economizer cooling, the enthalpy control disables the economizer function and permits the outdoor air damper to open only to the minimum position.

On water-cooled units, compressor operation lockout will not occur at low ambient air temperatures. However, lockout will still occur via low condenser water temperature.

The outdoor air dampers drive fully closed whenever the supply air fan is off, provided there is power to the unit.

Comparative Enthalpy Control Comparative enthalpy controls the economizer operation and measures temperature and humidity of both return air and outside air to determine which

source has lower enthalpy.This allows true comparison of outdoor air and return air enthalpy by measurement of outdoor air and return air temperatures and humidities. A factory-installed control board, with field-installed outside and return air temperature and relative humidity sensors, allows monitoring of outside and return air.

Note: If comparative enthalpy is not ordered, the standard method is to compare outdoor air enthalpy with the fixed reference enthalpy. The reference enthalpy is set through the human interface panel.

Units with comparative enthalpy control are equipped with the necessary control sequences to allow using outside air for the first stage of cooling, in occupied or unoccupied mode and when ambient conditions are favorable for economizing. Inherent in the unit controller is the ability to suppress the setpoint below the normal unit setpoint. This allows the building to improve comfort levels when possible, and at the same time, optimize building mechanical cooling operation for peak operating efficiency.

Economizer operation enables when the outside air enthalpy is 3 BTu/lb less than the return air enthalpy. During occupied mode, the outside air damper opens to 15% (adjustable 0-100%) for ventilation purposes. Also, the ability to alter the outside air damper position to compen- sate forVAV supply air modulation is inherent in the unit controls, and can be enabled by the operator.

The mixing box fabrication is galvanized steel. Opposed low leak damper blades are fabricated from galvanized steel and rotate on rustproof nylon bushings. A factory installed 24V modulating spring return actuator controls both damper positions.

Airside Economizers withTraqTM Damper Outside air enters the unit through the TraqTM damper assembly and is measured by velocity pressure flow rings. The velocity pressure flow rings are connected to a pressure transducer/ solenoid assembly, which compensates for temperature swings that could affect the transducer.The ventilation control

module (VCM) utilizes the velocity pressure input, the RTM outdoor air temperature input, and the minimum outside air cfm setpoint to modify the volume (cfm) of fresh air entering the unit as the measured airflow deviates from setpoint.

When the optional preheat temperature sensor is installed at the auxiliary temperature on the VCM and the preheat function is enabled, the sensor will monitor the combined (averaged) fresh air and return air temperatures. As this mixed air temperature falls below the preheat actuate temperature setpoint, the VCM activates the preheat binary output to control a field-installed heater. The output deactivates when the tem- perature rises 5°F above the preheat actuate temperature setpoint.

Using a field-installed CO2 sensor with CO2 reset enabled, as the CO2 concentra- tion increases above the CO2 reset start value, the VCM modifies the minimum outside air cfm setpoint to increase the amount of fresh air entering the unit. The setpoint adjusts upward until reaching the CO2 maximum reset value. The maxi- mum effective (reset) setpoint value for fresh air is limited to the system’s operating cfm. As the CO2 concentration decreases, the effective (reset) setpoint value adjusts downward toward the minimum outside air cfm setpoint. See Figure O-GI-6 for an airflow cfm vs. CO2 concentration curve.

Standard Two-Position Damper Interface Units with the two-position damper interface are provided with a 0-10 VDC control output suitable for controlling a field-provided modulating actuator. In occupied mode, the output drives to the maximum position.

Airside Economizer Interface

Units with airside economizer interface are equipped with the necessary control sequences to allow using outside air for the first stage of cooling, in occupied or unoccupied mode and when ambient conditions are favorable for economizing. Inherent in the unit controller is the ability to suppress the setpoint below the normal unit setpoint. This allows the building to improve comfort levels when possible, and at the same time, optimize building mechanical cooling operation for

80

SCXG-SVX01B-EN

Image 80
Contents JO and later design sequence ModelsIntroduction Hazard IdentificationSpecial Note on Refrigeration Emissions HazardousVoltage w/CapacitorsContents Features and Benefits Refrigerant Handling ProceduresModular Series Self-Contained Unit Components Installation information Unit NameplateModel Number Description Scwg Model Number DescriptionDigit 31 Compressor ServiceValves Digit 22 Unit FinishDigit Digit 24 Unit ConnectionSelf-Contained Ship-WithAccessory Model Number Description Model Number Description PswgAfter-ShipmentAccessory Model Number Receiving and Handling Shipping PackageInstallation Preparation ServiceAccess Table I-PC-1. Service and code clearance requirementsSection TopView CCRC/CIRC 20, 29Rigging and Unit Handling Lifting Equipment CapacityUnit Handling Procedure Figure I-PC-7.Assembled modular unit proper riggingSplit-Apart Unit Assembly IntelliPak UnitsUCM OnlyRemove panels FML, FMM, and FMR Units with Thermostat OnlyFigure I-PC-9 How to assemble the split apart modular unit External Unit Isolation Pre-Installation ChecklistSkid Removal Dimensions WeightsSCWG/SIWG Dimensions, Left-side viewLeft-side View Right-side view Top view SCRG/SIRG Dimensions,SCRG/SIRGWeight, lbs Dimensions Weights Detail Dimensions,CCRC/CIRC Air-cooled condenser dimensions & weight, in-lbs CCRC/CIRC -Air-Cooled CondenserCCRC/CIRC Electrical connections, CCRC/CIRC Refrigerant connections,Hot water coil dimensions & weight, in-lbs Hot Water CoilSteam coil dimensions, in-lbs Steam CoilFlexible Horizontal Discharge Plenum Electric heat coil dimensions & weight, in-lbsElectric Heat Coil Waterside economizer weight, in-lbs Waterside EconomizerDetail a Detail B Airside economizer dimensions & weight, in-lbsAirside Economizer Dimensions Weights VFD Variable Frequency Drive Option VFDControl and LineVoltage Result in death or serious injury Mounting RequirementsVariable Frequency Drive with Bypass Electrical Installation ProcedureVFD with bypass dimensions, Mechanical Specifications Duct ConnectionsWater Piping Hazardous Voltage w/Capaci- torsWaterside Piping Arrangements Table I-MR-1. Water Connection SizesHazard of Explosion and Deadly Gases Brazing ProceduresRefrigerant Piping Air-Cooled Units Only Unit Wiring Diagrams Supply PowerWiringLive Electrical Components Equipment DamageSelection Procedures Installation requirements Pre-Startup ProceduresSupply Fan Isolators Shipping bracketFigure I-PR-3. Correct plenum insulation placement Airside Economizer Installation Unit InstallationField Wiring Connections Unit HandlingTransducer Location Static PressureTransducer Installation VAV units onlyInstalling theTransducer Waterside Economizer Installation Procedure Figure I-PR-7. Installing the waterside economizerTubing assemblies for waterside econo Mizer left-hand piping Waterside Economizer Ship-Separate Parts List Unit Structural Integrity Hydronic Coil InstallationInstallation Procedure Table I-PR-2.Available Electric Heat kW Electric Heat InstallationElectric Heat CoilWiring Procedure Standard with All IntelliPak Units Zone Sensor Options for IntelliPak Control UnitsCV Unit Zone Sensor Options BAYSENS077* DescriptionCV andVAV Unit Zone Sensor Options VAV Unit Zone Sensor OptionBAYSENS074 Description BAYSENS073 DescriptionZone Sensor Installation WiringMounting Location Mounting the SubbaseRight Mounting Directly to the Wall Mounting to Junction Box Programmable Zone Sensors ConstantVolume Zone Sensor BAYSENS019 DescriptionVariable AirVolume Zone Sensor BAYSENS020B Description Programmable Zone Sensor Installation Airflows from adjacent zones or other unitsTime Clock Installation Time Clock Installation ChecklistWiring theTimeclock Time Clock OptionRemote Human Interface Panel Installation Human Interface HI PanelRemote Human Interface Panel Location RecommendationsWall Mounting the RHI Panel ProcedureMounting the Remote Human Interface RHI Panel Pre-startup Wiring the Remote Human Interface LowVoltage AC FieldWiring ConnectionsCommunication Link ShieldedTwisted PairWiring Interprocessor Communication Bridge ModuleWiringConnecting toTracer Summit Pre-Startup ChecklistInstallation programming Programmable Zone Sensor OptionsHeat supply air Cool supply air Warmup temperature During Programming IndicatesKeypad Operation Temporary Manual Override Time ButtonKeypad Lockout Up and Down Button ArrowsTemporary Override Run Mode Figure I-P-6.Temporary manual override menu screenFigure I-P-7.Temporary manual override run mode screen Table I-P-1. Zone sensor BAYSENS019 option menu settingsRemote Panel Indicator Signals From UCM to ZSM Intelligent CopyTo use Intelligent Copy Off FlashingIcon Descriptions Figure I-P-9.BAYSENS019 complete icon displayFigure I-P-10.BAYSENS020 complete icon display Setting theTime Programming theTime Clock OptionProgramming To review and change programsInstallation startup Unit Startup ProceduresPre-Startup Checklist Compressor DamageCompressor Amp Draw Startup LogEvaporator Water Cooled Units Air Cooled UnitsPoints List RTM Module Points List Gbas ModulePoints List Ecem Module Points List -TracerTMLCI-I ModuleUnit Control Components RTM Module Board Standard on all UnitsTable O-GI-3. RTM setpoint analog inputs Table O-GI-2. RTM sensor resistance vs. temperatureVAV Box Option Ventilation Override Module VOM Option Human Interface Module Standard on all UnitsHeat Module Purge sequence D Supply fan on Supply fan VFD on if equippedGeneric BuildingAutomation System Module Option Table O-GI-6. Gbas analog input setpoints Table O-GI-7. Gbas input voltage corresponding setpointsWaterside Components Figure O-GI-3. Basic water piping, constant water flow UnitAirside Components General Operation information Airside Economizer Interface with Comparative Enthalpy Air-Cooled CondensersInput Devices and System Functions ProperWaterTreatmentReturn AirTemperature Sensor Supply Air Temperature SensorSupply Airflow Proving Switches Filter SwitchOperation operation Control Sequences OperationUnoccupied Sequence of Operation Tracer Summit SystemTimed Override Activation ICS Morning WarmupCycling Capacity Morning Warmup MWU Occupied Sequence Supply Air Setpoint Reset VAV Units Only Mechanical CoolingWater-Cooled Units Only Electric HeatTable O-SO-1. Compressor Stages CompressorsCompressor Lead/Lag Operation Table O-SO-2. Pressure cutouts Step ControlEvaporator Coil Frost Protection Service Valve Option OperationMaintenance information Table M-GI-1. SCWG/SIWG/SCRG/SIRG General Maintenance DataAir Filters Maintenance proceduresMaintenance Procedures Remove all standing water Inspecting and Cleaning the Drain PanInspecting and Cleaning the Fan Fan Drive Supply FanVariable Frequency Drive VFD Fan Bearings Table M-MP-1. Baldor Fan Bearing Lubrication ScheduleTable M-MP-2.AO Smith Bearing Lubrication Schedule Table M-MP-3. Compatible Fan Bearing GreaseTable M-MP-4. Fan shaft bearing torques Fan BeltTensionDeflection = belt span/64 Adjusting BeltTension BeltRefrigerant Evacuation Refrigerant SystemConfined Space Hazards Refrigerant LeakTesting Motor Winding DamageUse of Pressure Regulator Valves Gauges R407cMaintenance Inlet GuideVanes Coil Fin CleaningProper Coil CleaningAgent Coil Freezeup Chemical Cleaning of Condenser and Economizer Coil Flow Switch MaintenanceCleaning the Flow Switch Piping ComponentsMaintenance Periodic Checklists Monthly ChecklistSemi-Annual Maintenance Annual MaintenanceCheck the zone thermostat settings Operating ProceduresCommon Unit Problems and Solutions System ChecksMaintenance diagnostics DiagnosticsHeat Module Auxilliary Temperature Sensor Fail Emergency StopEntering Cond WaterTemp Sensor Fail Entering Water Temp Sensor FailMode Input Failure Low Air Temp Limit TripLow Pressure Control Open Circuit 1, 2, 3, or MCM Communications FailureNSB Panel ZoneTemperature Sensor Failure Check Field/unit wiring between RTM and NSB PanelHumidity Sensor Failure Temp. Sensor FailureRTM Data Storage Error RTM Zone Sensor FailureSupply Fan VFD Bypass Enabled ProblemThe LCI-I has lost communication withTracer SummitSupply Fan Failure LCI-I Module Comm FailureWSM Communications Fail Render all HI keystrokes ineffectiveVOM Communications Failure WSM Mixed AirTemp Sensor Fail Water Flow Fail114 115 Literature Order Number

SCXG-SVX01B-EN specifications

The Trane SCXG-SVX01B-EN is an advanced variable refrigerant flow (VRF) system designed to provide efficient and flexible heating and cooling solutions for commercial and residential applications. This system exemplifies Trane's commitment to innovation, energy efficiency, and ease of installation, making it a standout choice in the industry.

One of the main features of the SCXG-SVX01B-EN is its ability to deliver precise temperature control across multiple zones. The system utilizes a modular design that allows for the connection of multiple indoor units to a single outdoor unit, enabling simultaneous heating and cooling in different areas of a building. This zoned comfort not only enhances occupant satisfaction but also contributes to energy savings by allowing for targeted climate control where it is most needed.

Trane's VRF technology is complemented by its inverter-driven compressors, which adjust their speed according to the demand for heating or cooling. This means that the system operates more efficiently than traditional systems by consuming less energy during partial load conditions. The SCXG-SVX01B-EN also integrates advanced heat recovery capabilities, allowing it to transfer heat from one zone to another, further optimizing energy usage.

The unit's compact design simplifies installation, making it suitable for both retrofit projects and new constructions. The flexible piping layout supports various configurations, allowing easy adaptation to the building's architecture. The model also incorporates intelligent controls, offering a user-friendly interface that enhances operational flexibility and promotes energy management.

In addition to its performance features, the Trane SCXG-SVX01B-EN emphasizes sustainability. It uses advanced refrigerants with low global warming potential (GWP), aligning with environmental regulations and helping to minimize the system's ecological footprint. The durable construction of the system ensures longevity and reliability, reducing maintenance costs and enhancing overall operational efficiency.

Finally, Trane supports its products with comprehensive warranties and a network of service professionals, ensuring that customers have access to expert assistance throughout the life cycle of their system. The SCXG-SVX01B-EN represents a blend of technology, efficiency, and versatility, making it an ideal choice for those seeking an effective heating and cooling solution.