Trane SCXG-SVX01B-EN manual Cycling Capacity Morning Warmup MWU, Timed Override Activation ICS

Page 85

sequence of

Operation operation

For units without volume control entering unoccupied mode, the following se- quence will occur:

The occupied/unoccupied relay ener- gizes and the economizer option fully closes.

The fan mode is set to auto and the unit will control to the unoccupied zone temperature setpoints.

With MWU enabled at the HI, if the zone temperature is below the MWU setpoint, the unit enters the MWU mode.

Morning Warmup

This feature can be enabled at the HI, and can be used with factory or field-installed heat. If MWU is not required disable the function in the setup menu at the HI. MWU transitions the zone from unoccupied to occupied. It will heat until the MWU setpoint is met. The unit is then released to occupied mode. Supply duct static pressure is maintained during this sequence. MWU can be set (at the HI) to function as either full or cycling capacity.

Full Capacity Morning Warmup (MWU) Full capacity morning warmup uses full heating capacity to heat the zone as quickly as possible. Full heating capacity is provided until the morning warmup setpoint is met. At this point, the unit is released to daytime mode.

Cycling Capacity Morning Warmup (MWU)

Cycling capacity morning warmup provides a more gradual heating to overcome “building sink” as the zone is heated. Normal zone temperature control with varying capacity is used to raise the zone temperature to the MWU zone temperature setpoint. This method of warmup is used to overcome the “building sink” effect.

Reference Figure O-SO-1 on page 73 for a pictorial explanation of the cycling MWU sequence. Cycling capacity MWU will heat until MWU temperature setpoint

is reached. Next a 60 minute timer begins. If the building load reaches the MWU ventilation setpoint, or the 60 minutes expire, whichever is first, the airside economizer will control to the minimum position. MWU will end when the zone temperature rises above the MWU terminate setpoint.

Timed Override Activation - ICS™

This function is operational whenever the unit’s RTM module is used as the zone temperature sensor source, which can be set at the HI panel. When this function is initiated by the push of the override button on the zone sensor, the unit will switch to the occupied mode. Unit operation (occupied mode) during timed override is terminated by a signal from Tracer.

Timed Override Activation - Non-ICS This function is active whenever the unit’s RTM module board is selected as the zone temperature source, which can be set at the human interface panel. When this function is initiated by the push of the override button on the zone sensor, the unit will switch to the occupied mode. Automatic cancellation of the timed override mode occurs after three hours of operation.

VAV Drive Max Output

This is a single-pole, double-throw relay rated at a maximum voltage of 24 vac, two amps max. The relay contacts of this relay switch when the unit goes from the occupied mode to the unoccupied mode by means of the unoccupied binary input, night setback zone sensor, orTracer Summit. The contacts will stay switched during the unoccupied and morning warmup mode. They will return to the position shown on the unit wiring diagram when the unit returns to the occupied mode. The intent of this binary output is to signal theVAV boxes or other terminal devices to go to a full open airflow position.

SCXG-SVX01B-EN

85

Image 85
Contents Models JO and later design sequenceHazard Identification IntroductionSpecial Note on Refrigeration Emissions HazardousVoltage w/CapacitorsContents Refrigerant Handling Procedures Features and BenefitsModular Series Self-Contained Unit Components Unit Nameplate Installation informationModel Number Description Model Number Description ScwgDigit 22 Unit Finish Digit 31 Compressor ServiceValvesDigit Digit 24 Unit ConnectionModel Number Description Pswg Self-Contained Ship-WithAccessory Model Number DescriptionAfter-ShipmentAccessory Model Number Shipping Package Receiving and HandlingInstallation Preparation Table I-PC-1. Service and code clearance requirements ServiceAccessSection TopView CCRC/CIRC 20, 29Lifting Equipment Capacity Rigging and Unit HandlingFigure I-PC-7.Assembled modular unit proper rigging Unit Handling ProcedureIntelliPak UnitsUCM Only Split-Apart Unit AssemblyRemove panels FML, FMM, and FMR Units with Thermostat OnlyFigure I-PC-9 How to assemble the split apart modular unit Skid Removal Pre-Installation ChecklistExternal Unit Isolation Weights DimensionsSCWG/SIWG Dimensions, Left-side viewSCRG/SIRGWeight, lbs SCRG/SIRG Dimensions,Left-side View Right-side view Top view Detail Dimensions, Dimensions WeightsCCRC/CIRC -Air-Cooled Condenser CCRC/CIRC Air-cooled condenser dimensions & weight, in-lbsCCRC/CIRC Electrical connections, CCRC/CIRC Refrigerant connections,Hot Water Coil Hot water coil dimensions & weight, in-lbsSteam Coil Steam coil dimensions, in-lbsElectric Heat Coil Electric heat coil dimensions & weight, in-lbsFlexible Horizontal Discharge Plenum Waterside Economizer Waterside economizer weight, in-lbsAirside Economizer Airside economizer dimensions & weight, in-lbsDetail a Detail B Variable Frequency Drive Option VFD Dimensions Weights VFDControl and LineVoltage Result in death or serious injury Mounting RequirementsVFD with bypass dimensions, Electrical Installation ProcedureVariable Frequency Drive with Bypass Duct Connections Mechanical SpecificationsWater Piping Hazardous Voltage w/Capaci- torsTable I-MR-1. Water Connection Sizes Waterside Piping ArrangementsRefrigerant Piping Air-Cooled Units Only Brazing ProceduresHazard of Explosion and Deadly Gases Supply PowerWiring Unit Wiring DiagramsLive Electrical Components Equipment DamageSelection Procedures Pre-Startup Procedures Installation requirementsSupply Fan Isolators Shipping bracketFigure I-PR-3. Correct plenum insulation placement Unit Installation Airside Economizer InstallationField Wiring Connections Unit HandlingInstalling theTransducer Static PressureTransducer Installation VAV units onlyTransducer Location Figure I-PR-7. Installing the waterside economizer Waterside Economizer Installation ProcedureTubing assemblies for waterside econo Mizer left-hand piping Waterside Economizer Ship-Separate Parts List Installation Procedure Hydronic Coil InstallationUnit Structural Integrity Electric Heat CoilWiring Procedure Electric Heat InstallationTable I-PR-2.Available Electric Heat kW Zone Sensor Options for IntelliPak Control Units Standard with All IntelliPak UnitsCV Unit Zone Sensor Options BAYSENS077* DescriptionVAV Unit Zone Sensor Option CV andVAV Unit Zone Sensor OptionsBAYSENS074 Description BAYSENS073 DescriptionWiring Zone Sensor InstallationMounting Location Mounting the SubbaseRight Mounting Directly to the Wall Mounting to Junction Box Variable AirVolume Zone Sensor BAYSENS020B Description ConstantVolume Zone Sensor BAYSENS019 DescriptionProgrammable Zone Sensors Airflows from adjacent zones or other units Programmable Zone Sensor InstallationTime Clock Installation Checklist Time Clock InstallationWiring theTimeclock Time Clock OptionHuman Interface HI Panel Remote Human Interface Panel InstallationRemote Human Interface Panel Location RecommendationsMounting the Remote Human Interface RHI Panel ProcedureWall Mounting the RHI Panel Pre-startup LowVoltage AC FieldWiring Connections Wiring the Remote Human InterfaceCommunication Link ShieldedTwisted PairWiring Interprocessor Communication Bridge ModuleWiringPre-Startup Checklist Connecting toTracer SummitProgrammable Zone Sensor Options Installation programmingDuring Programming Indicates Heat supply air Cool supply air Warmup temperatureKeypad Operation Time Button Temporary Manual OverrideKeypad Lockout Up and Down Button ArrowsFigure I-P-6.Temporary manual override menu screen Temporary Override Run ModeTable I-P-1. Zone sensor BAYSENS019 option menu settings Figure I-P-7.Temporary manual override run mode screenIntelligent Copy Remote Panel Indicator Signals From UCM to ZSMTo use Intelligent Copy Off FlashingFigure I-P-9.BAYSENS019 complete icon display Icon DescriptionsFigure I-P-10.BAYSENS020 complete icon display Programming theTime Clock Option Setting theTimeProgramming To review and change programsUnit Startup Procedures Installation startupPre-Startup Checklist Compressor DamageEvaporator Startup LogCompressor Amp Draw Air Cooled Units Water Cooled UnitsPoints List Gbas Module Points List RTM ModulePoints List Ecem Module Points List -TracerTMLCI-I ModuleRTM Module Board Standard on all Units Unit Control ComponentsVAV Box Option Table O-GI-2. RTM sensor resistance vs. temperatureTable O-GI-3. RTM setpoint analog inputs Heat Module Human Interface Module Standard on all UnitsVentilation Override Module VOM Option Supply fan on Supply fan VFD on if equipped Purge sequence DGeneric BuildingAutomation System Module Option Table O-GI-7. Gbas input voltage corresponding setpoints Table O-GI-6. Gbas analog input setpointsWaterside Components Figure O-GI-3. Basic water piping, constant water flow UnitAirside Components General Operation information Air-Cooled Condensers Airside Economizer Interface with Comparative EnthalpyProperWaterTreatment Input Devices and System FunctionsSupply Air Temperature Sensor Return AirTemperature SensorSupply Airflow Proving Switches Filter SwitchControl Sequences Operation Operation operationUnoccupied Sequence of Operation Tracer Summit SystemCycling Capacity Morning Warmup MWU Morning WarmupTimed Override Activation ICS Occupied Sequence Mechanical Cooling Supply Air Setpoint Reset VAV Units OnlyWater-Cooled Units Only Electric HeatCompressor Lead/Lag Operation CompressorsTable O-SO-1. Compressor Stages Evaporator Coil Frost Protection Step ControlTable O-SO-2. Pressure cutouts Operation Service Valve OptionTable M-GI-1. SCWG/SIWG/SCRG/SIRG General Maintenance Data Maintenance informationMaintenance Procedures Maintenance proceduresAir Filters Inspecting and Cleaning the Fan Inspecting and Cleaning the Drain PanRemove all standing water Variable Frequency Drive VFD Supply FanFan Drive Table M-MP-1. Baldor Fan Bearing Lubrication Schedule Fan BearingsTable M-MP-2.AO Smith Bearing Lubrication Schedule Table M-MP-3. Compatible Fan Bearing GreaseDeflection = belt span/64 Fan BeltTensionTable M-MP-4. Fan shaft bearing torques Belt Adjusting BeltTensionConfined Space Hazards Refrigerant SystemRefrigerant Evacuation Motor Winding Damage Refrigerant LeakTestingUse of Pressure Regulator Valves Gauges R407cMaintenance Proper Coil CleaningAgent Coil Fin CleaningInlet GuideVanes Coil Freezeup Flow Switch Maintenance Chemical Cleaning of Condenser and Economizer CoilCleaning the Flow Switch Piping ComponentsMonthly Checklist Maintenance Periodic ChecklistsSemi-Annual Maintenance Annual MaintenanceOperating Procedures Check the zone thermostat settingsCommon Unit Problems and Solutions System ChecksDiagnostics Maintenance diagnosticsEmergency Stop Heat Module Auxilliary Temperature Sensor FailEntering Cond WaterTemp Sensor Fail Entering Water Temp Sensor FailLow Air Temp Limit Trip Mode Input FailureLow Pressure Control Open Circuit 1, 2, 3, or MCM Communications FailureCheck Field/unit wiring between RTM and NSB Panel NSB Panel ZoneTemperature Sensor FailureHumidity Sensor Failure Temp. Sensor FailureRTM Zone Sensor Failure RTM Data Storage ErrorProblemThe LCI-I has lost communication withTracer Summit Supply Fan VFD Bypass EnabledSupply Fan Failure LCI-I Module Comm FailureVOM Communications Failure Render all HI keystrokes ineffectiveWSM Communications Fail Water Flow Fail WSM Mixed AirTemp Sensor Fail114 115 Literature Order Number

SCXG-SVX01B-EN specifications

The Trane SCXG-SVX01B-EN is an advanced variable refrigerant flow (VRF) system designed to provide efficient and flexible heating and cooling solutions for commercial and residential applications. This system exemplifies Trane's commitment to innovation, energy efficiency, and ease of installation, making it a standout choice in the industry.

One of the main features of the SCXG-SVX01B-EN is its ability to deliver precise temperature control across multiple zones. The system utilizes a modular design that allows for the connection of multiple indoor units to a single outdoor unit, enabling simultaneous heating and cooling in different areas of a building. This zoned comfort not only enhances occupant satisfaction but also contributes to energy savings by allowing for targeted climate control where it is most needed.

Trane's VRF technology is complemented by its inverter-driven compressors, which adjust their speed according to the demand for heating or cooling. This means that the system operates more efficiently than traditional systems by consuming less energy during partial load conditions. The SCXG-SVX01B-EN also integrates advanced heat recovery capabilities, allowing it to transfer heat from one zone to another, further optimizing energy usage.

The unit's compact design simplifies installation, making it suitable for both retrofit projects and new constructions. The flexible piping layout supports various configurations, allowing easy adaptation to the building's architecture. The model also incorporates intelligent controls, offering a user-friendly interface that enhances operational flexibility and promotes energy management.

In addition to its performance features, the Trane SCXG-SVX01B-EN emphasizes sustainability. It uses advanced refrigerants with low global warming potential (GWP), aligning with environmental regulations and helping to minimize the system's ecological footprint. The durable construction of the system ensures longevity and reliability, reducing maintenance costs and enhancing overall operational efficiency.

Finally, Trane supports its products with comprehensive warranties and a network of service professionals, ensuring that customers have access to expert assistance throughout the life cycle of their system. The SCXG-SVX01B-EN represents a blend of technology, efficiency, and versatility, making it an ideal choice for those seeking an effective heating and cooling solution.