Trane SCXG-SVX01B-EN To use Intelligent Copy, Remote Panel Indicator Signals From UCM to ZSM

Page 63

Installation programming

Note: On both programmable zone sensor options, changing either option 9 or 10 will erase the current program. To avoid reprogramming, set options 9 and 10 before programming.

Intelligent Copy

Note: Once you use Intelligent Copy, you cannot use it again until you erase all weekday and weekend time periods by pressing ERASE for 5 seconds.

If your heating and cooling requirements are the same for each day of the week, and for each day of the weekend, your ZSM is designed to employ Intelligent Copy.

To program the five weekdays, Monday through Friday, program only one weekday. Likewise, to program the weekend, Saturday and Sunday, pro- gram only one day. After programming one weekday and/or one weekend day, Intelligent Copy automatically copies your program to the other days.

To use Intelligent Copy:

1)Be sure to select the seven day programming format in the Options Menu. SeeTables I-P-1 and I-P-2.

2)Be sure the entire program is blank.

3)Go to Program Menu.

4)Enter your setpoint parameters. Intelligent Copy will automatically copy these parameters to the other weekdays.

5)Depress the DAY pushbutton until a weekend day icon appears.

6)Enter setpoint parameters. Intelligent Copy will automatically copy these parameters to the other weekend day.

Remote Panel Indicator Signals From UCM to ZSM

The unit control module (UCM) can send four signals to the ZSM.

Heat

Cool

On

Service

Each of these four signals have three different conditions. SeeTable I-P-3.

Off

On

Flashing

Table I-P-2. Zone sensor BAYSENS020 option menu settings

option

description

value

factory

 

 

 

 

setting

1

morning warmup

0 = disabled

0

 

 

1 = enabled

 

2

economizer minimum

0

= disabled

1

 

position override

1 = enabled

 

3

temperature scale

0

= Fahrenheit

0

 

 

1 = enabled

 

4

heat installed

0

= no

0

 

 

1

= yes

 

5

time clock

0

= 12 hours

0

 

 

1

= 24 hours

 

6

hydronic heat

0

= no

0

 

 

1

= yes

 

7

daytime warmup

0

= disabled

0

 

 

1 = enabled

 

8

programmable days/week

0 = 7 days (M,T,W,T,F,S,S)

0

 

 

1 = 3 days (M-F, S, S

 

 

 

2 = 2 days (M-F, S,S)

 

9

programmable periods/day

2,3,4

4

10

remote sensor installed

0

= no

0

 

 

1

= yes

 

11

check filter interval

0

= disabled

350

 

 

3000 to 50 in 50 hour

 

 

 

increments

 

12

display zone temperature

0

= no

1

 

 

1

= yes

 

13

keypad lockout rnabled

0

= disabled

1

 

 

1 = enabled

 

14

initial time setting in temporary

1,2,3,4,5

3

 

override mode (hrs.)

 

 

 

15

buzzer options

0

= key press only

1

 

 

1 = key press & check filter

 

 

 

2 = key press, check filter,

 

 

 

and system failures

 

16

zone temperature calibration

displays current temp.

0 offset

 

 

with any offsets

 

17

default cooling setpoint

45 to 98°F (unoccupied)

74°F

18

default heating setpoint

43 to 96°F (unoccupied)

68°F

19

default supply air cool

40 to 80°F (occupied)

55°F

20

default supply air heat

60 to 160°F

100°F

21

default warmup

50 to 90°F (occupied)

68°F

22

minimum cooling setpoint

45 to 98°F

45°F

23

maximum heating setpoint

43 to 96°F

96°F

24

minimum supply air cool

40 to 80°F (occupied)

40°F

25

maximum supply air heat

60 to 160°F

160°F

26

maximum warmup

50 to 90°F

90°F

Table I-P-3. UCM signal conditions

 

signal

condition

heat

on

FlashingHEAT is ON and indicated by a solid HEAT icon in the

 

 

Display. Failure in the cooling system indicated by a flashing COOL

 

 

FAIL icon.

cool

on

FlashingCOOLING is ON and indicated by a solid COOL icon in the

 

 

Display. Failure in the cooling system indicated by a flashing

 

 

COOL FAIL icon.

on

off

FlashingSystem is OFF and indicated by a solid colon on the time of

 

on

day display. System is ON and indicated by a flashing colon on

 

 

the time of day display. System is in TEST mode and indicated by a

 

 

flashing TEST icon.

service

flashing

ON System requires service and is indicated by a solid SERVICE

 

 

icon.There is a FAN failure indicated by a flashing SERVICE icon.

Note: There is no indication for a signal in the OFF condition. If option 16 is set to “2,” any flashing signals will also give audible buzzer indication

SCXG-SVX01B-EN

63

Image 63
Contents Models JO and later design sequenceHazardousVoltage w/Capacitors IntroductionHazard Identification Special Note on Refrigeration EmissionsContents Refrigerant Handling Procedures Features and BenefitsModular Series Self-Contained Unit Components Unit Nameplate Installation informationModel Number Description Model Number Description ScwgDigit 24 Unit Connection Digit 31 Compressor ServiceValvesDigit 22 Unit Finish DigitModel Number Description Pswg Self-Contained Ship-WithAccessory Model Number DescriptionAfter-ShipmentAccessory Model Number Shipping Package Receiving and HandlingInstallation Preparation TopView CCRC/CIRC 20, 29 ServiceAccessTable I-PC-1. Service and code clearance requirements SectionLifting Equipment Capacity Rigging and Unit HandlingFigure I-PC-7.Assembled modular unit proper rigging Unit Handling ProcedureUnits with Thermostat Only Split-Apart Unit AssemblyIntelliPak UnitsUCM Only Remove panels FML, FMM, and FMRFigure I-PC-9 How to assemble the split apart modular unit Pre-Installation Checklist Skid RemovalExternal Unit Isolation Left-side view DimensionsWeights SCWG/SIWG Dimensions,SCRG/SIRG Dimensions, SCRG/SIRGWeight, lbsLeft-side View Right-side view Top view Detail Dimensions, Dimensions WeightsCCRC/CIRC Refrigerant connections, CCRC/CIRC Air-cooled condenser dimensions & weight, in-lbsCCRC/CIRC -Air-Cooled Condenser CCRC/CIRC Electrical connections,Hot Water Coil Hot water coil dimensions & weight, in-lbsSteam Coil Steam coil dimensions, in-lbsElectric heat coil dimensions & weight, in-lbs Electric Heat CoilFlexible Horizontal Discharge Plenum Waterside Economizer Waterside economizer weight, in-lbsAirside economizer dimensions & weight, in-lbs Airside EconomizerDetail a Detail B Result in death or serious injury Mounting Requirements Dimensions Weights VFDVariable Frequency Drive Option VFD Control and LineVoltageElectrical Installation Procedure VFD with bypass dimensions,Variable Frequency Drive with Bypass Hazardous Voltage w/Capaci- tors Mechanical SpecificationsDuct Connections Water PipingTable I-MR-1. Water Connection Sizes Waterside Piping ArrangementsBrazing Procedures Refrigerant Piping Air-Cooled Units OnlyHazard of Explosion and Deadly Gases Equipment Damage Unit Wiring DiagramsSupply PowerWiring Live Electrical ComponentsSelection Procedures Shipping bracket Installation requirementsPre-Startup Procedures Supply Fan IsolatorsFigure I-PR-3. Correct plenum insulation placement Unit Handling Airside Economizer InstallationUnit Installation Field Wiring ConnectionsStatic PressureTransducer Installation VAV units only Installing theTransducerTransducer Location Figure I-PR-7. Installing the waterside economizer Waterside Economizer Installation ProcedureTubing assemblies for waterside econo Mizer left-hand piping Waterside Economizer Ship-Separate Parts List Hydronic Coil Installation Installation ProcedureUnit Structural Integrity Electric Heat Installation Electric Heat CoilWiring ProcedureTable I-PR-2.Available Electric Heat kW BAYSENS077* Description Standard with All IntelliPak UnitsZone Sensor Options for IntelliPak Control Units CV Unit Zone Sensor OptionsBAYSENS073 Description CV andVAV Unit Zone Sensor OptionsVAV Unit Zone Sensor Option BAYSENS074 DescriptionMounting the Subbase Zone Sensor InstallationWiring Mounting LocationRight Mounting Directly to the Wall Mounting to Junction Box ConstantVolume Zone Sensor BAYSENS019 Description Variable AirVolume Zone Sensor BAYSENS020B DescriptionProgrammable Zone Sensors Airflows from adjacent zones or other units Programmable Zone Sensor InstallationTime Clock Option Time Clock InstallationTime Clock Installation Checklist Wiring theTimeclockLocation Recommendations Remote Human Interface Panel InstallationHuman Interface HI Panel Remote Human Interface PanelProcedure Mounting the Remote Human Interface RHI PanelWall Mounting the RHI Panel Pre-startup Interprocessor Communication Bridge ModuleWiring Wiring the Remote Human InterfaceLowVoltage AC FieldWiring Connections Communication Link ShieldedTwisted PairWiringPre-Startup Checklist Connecting toTracer SummitProgrammable Zone Sensor Options Installation programmingDuring Programming Indicates Heat supply air Cool supply air Warmup temperatureKeypad Operation Up and Down Button Arrows Temporary Manual OverrideTime Button Keypad LockoutFigure I-P-6.Temporary manual override menu screen Temporary Override Run ModeTable I-P-1. Zone sensor BAYSENS019 option menu settings Figure I-P-7.Temporary manual override run mode screenOff Flashing Remote Panel Indicator Signals From UCM to ZSMIntelligent Copy To use Intelligent CopyFigure I-P-9.BAYSENS019 complete icon display Icon DescriptionsFigure I-P-10.BAYSENS020 complete icon display To review and change programs Setting theTimeProgramming theTime Clock Option ProgrammingCompressor Damage Installation startupUnit Startup Procedures Pre-Startup ChecklistStartup Log EvaporatorCompressor Amp Draw Air Cooled Units Water Cooled UnitsPoints List -TracerTMLCI-I Module Points List RTM ModulePoints List Gbas Module Points List Ecem ModuleRTM Module Board Standard on all Units Unit Control ComponentsTable O-GI-2. RTM sensor resistance vs. temperature VAV Box OptionTable O-GI-3. RTM setpoint analog inputs Human Interface Module Standard on all Units Heat ModuleVentilation Override Module VOM Option Supply fan on Supply fan VFD on if equipped Purge sequence DGeneric BuildingAutomation System Module Option Table O-GI-7. Gbas input voltage corresponding setpoints Table O-GI-6. Gbas analog input setpointsWaterside Components Figure O-GI-3. Basic water piping, constant water flow UnitAirside Components General Operation information Air-Cooled Condensers Airside Economizer Interface with Comparative EnthalpyProperWaterTreatment Input Devices and System FunctionsFilter Switch Return AirTemperature SensorSupply Air Temperature Sensor Supply Airflow Proving SwitchesTracer Summit System Operation operationControl Sequences Operation Unoccupied Sequence of OperationMorning Warmup Cycling Capacity Morning Warmup MWUTimed Override Activation ICS Occupied Sequence Electric Heat Supply Air Setpoint Reset VAV Units OnlyMechanical Cooling Water-Cooled Units OnlyCompressors Compressor Lead/Lag OperationTable O-SO-1. Compressor Stages Step Control Evaporator Coil Frost ProtectionTable O-SO-2. Pressure cutouts Operation Service Valve OptionTable M-GI-1. SCWG/SIWG/SCRG/SIRG General Maintenance Data Maintenance informationMaintenance procedures Maintenance ProceduresAir Filters Inspecting and Cleaning the Drain Pan Inspecting and Cleaning the FanRemove all standing water Supply Fan Variable Frequency Drive VFDFan Drive Table M-MP-3. Compatible Fan Bearing Grease Fan BearingsTable M-MP-1. Baldor Fan Bearing Lubrication Schedule Table M-MP-2.AO Smith Bearing Lubrication ScheduleFan BeltTension Deflection = belt span/64Table M-MP-4. Fan shaft bearing torques Belt Adjusting BeltTensionRefrigerant System Confined Space HazardsRefrigerant Evacuation R407c Refrigerant LeakTestingMotor Winding Damage Use of Pressure Regulator Valves GaugesMaintenance Coil Fin Cleaning Proper Coil CleaningAgentInlet GuideVanes Coil Freezeup Piping Components Chemical Cleaning of Condenser and Economizer CoilFlow Switch Maintenance Cleaning the Flow SwitchAnnual Maintenance Maintenance Periodic ChecklistsMonthly Checklist Semi-Annual MaintenanceSystem Checks Check the zone thermostat settingsOperating Procedures Common Unit Problems and SolutionsDiagnostics Maintenance diagnosticsEntering Water Temp Sensor Fail Heat Module Auxilliary Temperature Sensor FailEmergency Stop Entering Cond WaterTemp Sensor FailMCM Communications Failure Mode Input FailureLow Air Temp Limit Trip Low Pressure Control Open Circuit 1, 2, 3, orTemp. Sensor Failure NSB Panel ZoneTemperature Sensor FailureCheck Field/unit wiring between RTM and NSB Panel Humidity Sensor FailureRTM Zone Sensor Failure RTM Data Storage ErrorLCI-I Module Comm Failure Supply Fan VFD Bypass EnabledProblemThe LCI-I has lost communication withTracer Summit Supply Fan FailureRender all HI keystrokes ineffective VOM Communications FailureWSM Communications Fail Water Flow Fail WSM Mixed AirTemp Sensor Fail114 115 Literature Order Number

SCXG-SVX01B-EN specifications

The Trane SCXG-SVX01B-EN is an advanced variable refrigerant flow (VRF) system designed to provide efficient and flexible heating and cooling solutions for commercial and residential applications. This system exemplifies Trane's commitment to innovation, energy efficiency, and ease of installation, making it a standout choice in the industry.

One of the main features of the SCXG-SVX01B-EN is its ability to deliver precise temperature control across multiple zones. The system utilizes a modular design that allows for the connection of multiple indoor units to a single outdoor unit, enabling simultaneous heating and cooling in different areas of a building. This zoned comfort not only enhances occupant satisfaction but also contributes to energy savings by allowing for targeted climate control where it is most needed.

Trane's VRF technology is complemented by its inverter-driven compressors, which adjust their speed according to the demand for heating or cooling. This means that the system operates more efficiently than traditional systems by consuming less energy during partial load conditions. The SCXG-SVX01B-EN also integrates advanced heat recovery capabilities, allowing it to transfer heat from one zone to another, further optimizing energy usage.

The unit's compact design simplifies installation, making it suitable for both retrofit projects and new constructions. The flexible piping layout supports various configurations, allowing easy adaptation to the building's architecture. The model also incorporates intelligent controls, offering a user-friendly interface that enhances operational flexibility and promotes energy management.

In addition to its performance features, the Trane SCXG-SVX01B-EN emphasizes sustainability. It uses advanced refrigerants with low global warming potential (GWP), aligning with environmental regulations and helping to minimize the system's ecological footprint. The durable construction of the system ensures longevity and reliability, reducing maintenance costs and enhancing overall operational efficiency.

Finally, Trane supports its products with comprehensive warranties and a network of service professionals, ensuring that customers have access to expert assistance throughout the life cycle of their system. The SCXG-SVX01B-EN represents a blend of technology, efficiency, and versatility, making it an ideal choice for those seeking an effective heating and cooling solution.