System Test (cont’d)
7.Press Start test to begin the test.
8.Activate each Holdup, Fire, or Supervisory device. You will hear a beep once per minute as a reminder that the system is in the test mode. A history event will be logged for each sensor activated.
9.Upon completion of the test, return to the operating panel and
10.Press Reset to display the reset options.
11.Press Test to exit the test mode and to return the system to normal operation.
12.Press Continue to display Action Menu 1.
13.Check the system history to see that all points tested properly.
Bell and Operating Panel Display
Testing the bell and operating panel display will not affect any other operation, nor will it interfere with protection from any point or group.
1.Using the operating panel’s numeric keypad, enter a valid ID code to display Action Menu 1.
2.Press More to display Action Menu 2.
3.Press Test to display Test Menu 1.
4.Press More to display Test Menu 2.
5.Press Bell and display to begin automatic test of your system’s bell and display.
Note: A test pattern of all LCD elements will be shown for 4 seconds, and the bell will ring for the last 4 seconds of this
6.The display will indicate the completion of the test.
7.Press Quit to display Test Menu 2.
8.Press Quit to display Action Menu 2.
– 74 –